![Daikin SkyAir Super Inverter 70 D Series Service Manual Download Page 45](http://html1.mh-extra.com/html/daikin/skyair-super-inverter-70-d-series/skyair-super-inverter-70-d-series_service-manual_4705686045.webp)
Field Piping and Wiring
SiE25-110
36
Field Piping and Wiring
(4) Precautions for pumping-down operation
(When moving and remounting the indoor or outdoor units, etc.)
Turn on the power and enter pump-down operation using the following procedure.
This is the end of pumping-down operation. After pumping-down oper-
ation, the remote controller shows “U4” even when ON button on the remote controller is pressed, and it will
not operate. Turn off the main power supply switch and turn it on again in need of operation.
To all persons doing pipe work.
Be sure to open the shut-off valve after finishing pipe work. (Operating the unit with it closed will cause the
compressor to break.)
Procedure
Precautions
1
Start fan operation with the
remote controller.
Confirm that stop valves both on
the liquid and gas side are open.
Take care when the procedure 2
is done first because the indoor
unit fan may operate automati-
cally.
2
Push the pumping down but-
ton on the PC board of the out-
door unit.
Compressor and outdoor fan will
start operation automatically.
3
Once operation stops after about 3 or 5 minutes, close the shut-
off valves for the gas and liquid sides. (Refer to Fig. 11)
BS1
BS1
BS1
When running pump-down operation, turn off the power and protect the terminal block to prevent it
from coming into contact with the insulating sheet, as shown in the figure.
Pump-down
push switch
Pump-down
push switch
Terminal block
Top plate
PC-board (A3P)
Vinyl or other insulation sheet
(secure with tape)
Figure of front side of outdoor unit (PC-board (A3P) vicinity)
Pressing the pump-down push switch on the outdoor PC-board (A3P) may cause the indoor fan to
automatically start spinning, so use caution.
71 TYPE
100, 125, 140
TYPE
Switch box
Closing direction
(Liquid pipe)
Fig. 11
(Gas pipe)
(S2536)
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...