Method of Field Set (Reset after Maintenance Inspection/Repair)
SiE25-110
44
Field Setting
1.4
Local Setting Mode No.
Example
To set the filter sign time to “filter contamination - heavy” for all units in a group:
Set mode No. to “10,” setting switch No. to “0,” and setting position No. to “02.”
Table
Mode
No.
Note 1
Setting
Switch
No.
Setting Description
Setting Position No. *Note 2
01
02
03
10
(20)
0
Filter contamination - heavy /
light (Setting of operating
hours for filter sign indication)
(Change setting when
reducing filter sign indication
time to half due to quick soiling
of filter)
Ultra-Long-
Life Type
Light
Approx.
10,000
hours
Heavy
Approx.
5,000
hours
—
Long-Life
Type
Approx.
2,500
hours
Approx.
1,250
hours
Standard
Type
Approx.
200
hours
Approx.
100
hours
1
Long-life filter type (Setting of filter sign
indication time)
(Change setting when Ultra-long-life filter is
installed)
Long-Life Filter
Ultra-Long-Life
Filter (1)
—
2
Remote control thermostat
(Set when remote control thermostat sensor
is used.)
Use
Not use
3
Estimation of filter operating hour
(Change setting when filter sign indication is
not used)
ON
OFF
—
11
(21)
0
No. of Sky Air indoor units connected for
simultaneous ON-OFF multi system
(Change setting when simultaneous
operation multi system is used) *Note 3
Pair
Twin
Triple
2
Indoor unit fan OFF when cooling/heating is
OFF
—
Fan OFF
—
4
PMV Control
Permitted
Prohibited
—
12
(22)
5
Automatic restart after power outage reset
*Note 6
OFF
ON
—
13
(23)
0
High
Ceiling
Ceiling-mounted built-in multi-
flow cassette type, Ceiling
suspended cassette type
N
H
S
Ceiling-suspended type,
wall-mounted type
2.7 m or Lower
2.7~3.5 m
—
Fan speed increase (wall-mounted type)
Standard
Slight Increase
Normal Increase
1
Air flow direction selection (Change setting
when blocking kit is installed) *Note 4
F
T
W
3
Air flow direction adjustment (Change
setting when decorative air outlet panel is
installed)
Equipped
Equipped
—
4
Setting of air flow direction adjustment
range
Upward
Standard
Downward
6
External static pressure setting (To be set
according to connected duct resistance)
Standard
(Standard)
High Static
Pressure (High
Ceiling Setting)
Low Static
Pressure
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...