background image

English

13

11-1 Three main operation methods are available:

Basic

The refrigerant temperature is fixed independent from the situation.
It corresponds to the standard operation which is known and can be 
expected from/under previous systems:

• To activate this operation method under cooling operation:

change field setting [2-8]=2.

• To activate this operation method under heating operation:

change field setting [2-9]=2.

Automatic (default)

The refrigerant temperature is set depending on the outdoor ambient 
conditions. As such adjusting the refrigerant temperature to match the 
required load (which is also related to the outdoor ambient conditions).
E.g., when your system is operating in cooling, you do not need as much 
cooling under low outdoor ambient temperatures (e.g., 77°F (25°C)) as 
under high outdoor ambient temperatures (e.g., 95°F (35°C)).
Using this idea, the system automatically starts increasing its refrig-
erant temperature, automatically reducing the delivered capacity 
and increasing the system’s

 

efficiency.

• To activate this operation method under cooling operation:

change field setting [2-8]=3 (default).

E.g., when your system is operating in heating, you do not need as much 
heating under high outdoor ambient temperatures (e.g., 59°F (15°C)) as 
under low outdoor ambient temperatures (e.g., 23°F (-5°C)).
Using this idea, the system automatically starts decreasing its refrig-
erant temperature, automatically reducing the delivered capacity 
and increasing the system’s efficiency.

• To activate this operation method under heating operation:

change field setting [2-9]=1 (default).

Hi-sensible (cooling)

The refrigerant temperature is set higher (cooling) compared to 
basic operation. The focus under high sensible mode is improved 
comfort for the customer.
The selection method of indoor units is important and has to be con-
sidered as the available capacity is not the same as under basic 
operation. For details concerning to Hi-sensible applications, please 
contact your dealer.

• To activate this setting under cooling operation: change field set-

ting [2-8] to the appropriate value, matching the requirements of 
the pre-designed system containing a high

 

sensible solution.

11-2 Several comfort settings are available

For each of above modes a comfort level can be selected. The comfort 
level is related to the timing and the effort (energy consumption) which 
is put in achieving a certain room temperature by temporarily changing
the refrigerant temperature to different values in order to achieve 
requested conditions more quickly.

Powerful

Overshoot (during heating operation) or undershoot (during cooling 
operation) is allowed compared to the requested refrigerant temper-
ature, in order to achieve the required room temperature very fast. 
The overshoot is allowed from the start up moment.
In case of cooling operation the evaporating temperature is allowed 
to go down to 37°F (3°C) on temporary base depending on the situ-
ation.
In case of heating operation the condense temperature is allowed to 
go up to 120°F (49°C) on temporary base depending on the situation.
When the request from the indoor units becomes more moderate, 
the system will eventually go to the steady state condition which is 
defined by the operation method above.

• To activate the powerful comfort setting under cooling opera-

tion, change field setting [2-41]=3. 

This setting is used in conjunction with setting [2-8].

•  To activate the powerful comfort setting under heating opera-

tion, change field setting [2-42]=3.

This setting is used in conjunction with setting [2-9].

Quick

Overshoot (during heating operation) or undershoot (during cooling 
operation) is allowed compared to the requested refrigerant temper-
ature, in order to achieve the required room temperature very fast. 
The overshoot is allowed from the start up moment.
In case of cooling operation the evaporating temperature is allowed to 
go down to 43°F (6°C) on temporary base depending on the situation.
In case of heating operation the condense temperature is allowed to 
go up to 115°F (46°C) on temporary base depending on the situation.
When the request from the indoor units becomes more moderate, 
the system will eventually go to the steady state condition which is 
defined by the operation method above.

• To activate the quick comfort setting under cooling operation, 

change field setting [2-41]=2.

This setting is used in conjunction with setting [2-8].

• To activate the quick comfort setting under heating operation, 

change field setting [2-42]=2.

This setting is used in conjunction with setting [2-9].

Mild

Overshoot (during heating operation) or undershoot (during cooling 
operation) is allowed compared to the requested refrigerant temper-
ature, in order to achieve the required room temperature very
fast. The overshoot is not allowed from the start up moment. The 
start up occurs under the condition which is defined by the operation 
mode above.
In case of cooling operation the evaporating temperature is allowed to 
go down to 43°F (6°C) on temporary base depending on the situation.
In case of heating operation the condense temperature is allowed to 
go up to 115°F (46°C) on temporary base depending on the situation.
When the request from the indoor units becomes more moderate, 
the system will eventually go to the steady state condition which is 
defined by the operation method above.
The start up condition is different from the powerful and quick com-
fort setting.

• To activate the mild comfort setting under cooling operation, 

change field setting [2-41]=1.

This setting is used in conjunction with setting [2-8].

• To activate the mild comfort setting under heating operation, 

change field setting [2-42]=1.

This setting is used in conjunction with setting [2-9].

Eco

The original refrigerant temperature target, which is defined by the 
operation method (see above) is kept without any correction, unless 
for protection control.

• To activate the mild comfort setting under cooling operation, 

change field setting [2-41]=0.

This setting is used in conjunction with setting [2-8].

• To activate the mild comfort setting under heating operation, 

change field setting [2-42]=0.

This setting is used in conjunction with setting [2-9].

No matter which control is selected, variations on the behavior of the 
system are still possible due to protection controls to keep the unit oper-
ating under reliable conditions. The intentional target, however, is fixed 
and will be used to obtain the best balance between energy consump-
tion and comfort, depending on the application type.

Value

To target

4

46°F (8°C) 

5

48°F  (9°C)

6

50°F (10°C)

7

52°F (11°C)

01_EN_3P435164-5M.fm  Page 13  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ18TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: