background image

English

3

2-1 Standard operation limit

Normal operation

The figures below assume following operating conditions for indoor and 
outdoor units:

Equivalent pipe length .................................................. 25 ft. (7.6 m)
Level difference.................................................................. 0 ft. (0 m)

Cooling

Heating

Range for operation
Range for pull down operation
Range for warming up operation

2-2 Standard supplied accessories

Make sure that the accessories shown below are all present. 
(The accessories can be found behind the front panel.)

(Refer to figure 1)

1.

Accessories

2.

Screw for front panel

3.

Front panel

3.

BEFORE INSTALLATION

<Transporting the unit>

As shown in figure 2, move the unit slowly. (Take care not to let hands or 
other objects come in contact with rear fins.)

(Refer to figure 2)

1.

Air outlet grille

2.

Intake hole

3.

Corner

4.

Outdoor unit

5.

Handle

6.

Front

7.

Rear

8.

Always hold the unit by the corners, as holding it by the side 
intake holes on the casing may cause them to deform.

Use only accessories and parts which are of the designated specifica-
tion when installing.

4.

SELECTING INSTALLATION SITE

(1) Select an installation site where the following conditions are 

satisfied and that meets with your customer’s approval.

• Places which are well-ventilated.
• Places where the unit does not bother next-door neighbors.
• A location where small animals will not make nests in the unit.
• Safe places which can withstand the unit’s weight and vibration and 

where the unit can be installed level.

• A locations where there is enough space to install the unit.
• Places where the indoor and outdoor unit’s piping and wiring 

lengths come within the allowable ranges.

• A location where there is no risk of flammable gas leaking. 

(2) If the unit is installed in a location where it might be exposed to 

strong wind, install as per figure 3.

• 11 mph (5 m/s) or higher winds blown against the outdoor unit’s 

exhaust cause a deterioration in the system performance. High 
winds force re-circulation of the exhaust air into the inlet, which is 
known to cause the following effects:

• Reduction in performance.
• Increased frost formation in heating mode.
• System shut down due to increased pressures.

• If very strong wind blows continuously on the air outlet side of the 

outdoor unit, the fan may turn in reverse at high speed and break, 
so install as per figure 3.

(Refer to figure 3)

1.

Turn the air outlet side toward the building’s wall, fence or 
windbreak screen.

2.

Air inlet grille

3.

Ensure there is enough space for installing the unit.

4.

Set the outlet side at a right angle to the direction of the 
wind.

5.

Strong wind

6.

Blown air

(3) When installing the unit in a place frequently exposed to snow, 

pay special attention to the following:

• Install the outdoor unit on a stand (field supply), so that the bottom 

frame is more than 20 in. (500 mm) higher than the expected snow 
fall to prevent it from being covered by snow.

• Attach a snow hood (field supply) and a snow vizor (field supply).
• Avoid installation at the place where a snowdrift is generated.
• Further, perform the following countermeasures, since there is risk 

that the drain water produced at the defrost operation freezes.

• Install the outdoor unit so that its bottom place level has a sufficient 

height from foundation level, so that ice does not grow at the lower 
surface of the bottom place of the outdoor unit. (Recommended 
clearance: 20 in. (500 mm) or more)

Name

Clamp

Conduit mounting plate

Wire clamp 

and screw

Quantity

4 pcs.

2 pcs.

2 pcs.

1 (only 18·24 

type)

Shape

Name

Insulation tube

Installation 

manual

Warranty 

card

Quantity

1 pc.

1 pc.

1

1

Shape

67

(19)

57.2
(14)

77

(25)

50

(10)

23(–5)

82.4
(28)

Outdoor temperature °FDB (°CDB)

95(35)

122(50)

Indoor temperature 

°FWB (°CWB)

Rated 
cooling 
capacity

41(5)

–4(–20)

50

(10)

68

(20)

43(6)

80.6

(27)

59

(15)

Outdoor temperature °FWB (°CWB)

60(15.5)

Rated 
heating 
capacity

Indoor temperature 

°FDB (°CDB)

(Large)

(Small)

01_EN_3P435164-5M.fm  Page 3  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ18TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: