background image

6

English

6.

REFRIGERANT PIPING

CAUTION

• Do not allow anything other than the designated refrigerant to get 

mixed into the refrigerant cycle, such as air, nitrogen, etc. If any 
refrigerant gas leaks while working on the unit, ventilate the room 
thoroughly right away.

• Use R410A only when adding refrigerant.

6-1 Installation tools

Make sure to use speciality tools to withstand the pressure and to pre-
vent foreign materials from mixing into the system.

6-2 Selecting piping material

CAUTION

Piping and other pressure containing parts shall comply with the 
applicable legislation and shall be suitable for refrigerant. Use phos-
phoric acid deoxidized seamless copper for refrigerant.

CAUTION

• All field piping must be installed by a licensed refrigeration techni-

cian and must comply with relevant local and national regulations.

• After piping work is complete, do not under any circumstances 

open the stop valve until 

7. ELECTRIC WIRING

 on page 8 and 

9. POST-WORK CHECKS

 on page 11 are complete.

• Do not use flux when brazing the refrigerant piping. Use the phos-

phor copper brazing filler metal (B-Cu93P-710/795:ISO 3677) 
which does not require flux. Flux has extremely negative effect on 
refrigerant piping systems. For instance, if the chlorine based flux 
is used, it will cause pipe corrosion or, in particular, if the flux con-
tains fluorine, it will damage the refrigerant oil.

• Use only pipes which are clean inside and outside and which do not 

accumulate harmful sulfur, oxidants, dirt, cutting oils, moisture, or 
other contamination. (Foreign materials inside pipes including oils 
for fabrication must be 0.14 gr/10 ft. (30 mg/10 m) or less.)

• Use the following items for the refrigerant piping.

Material:

 Jointless phosphor-deoxidized copper pipe.

Thickness: 

Select a thickness for the refrigerant piping which com-

plies with national and local laws.

• Maximum piping length and height difference between the outdoor 

and indoor units.

6-3 Protection against contamination when install-

ing pipes

• Cover the ends of pipe to prevent moisture, dirt, dust, etc. from enter-

ing the piping.

• Exercise caution when passing copper piping through the through-

holes and when passing them out to the outside.

6-4 Pipe connection

• See “Stop valve operation procedure” in “

6-7 Air tight test and vac-

uum drying

” regarding handling of the stop valve.

• Only use the flare nuts included with the unit. Using different flare 

nuts may cause the refrigerant to leak.

Be sure to perform a nitrogen blow when brazing.

(Brazing without performing nitrogen replacement or releasing nitro-
gen into the piping will create large quantities of oxidized film on the 
inside of the pipes, adversely affecting valves and compressors in the 
refrigerating system and preventing normal operation.)

(Refer to figure 15)

1.

Refrigerant pipe

2.

Location to be brazed

3.

Regulator

4.

Nitrogen

5.

Manual valve

6.

Taping

6-5 Connecting the refrigerant piping

• Connection to larger pipe sizes.

In certain configurations this system is designed to be connected to 
larger diameter pipe sizes than the standard factory service valves. 
If the installation requires use of larger pipe diameters, a field setting 
change is required for the system to operate smoothly.

• The local field piping is connectable in four directions.

(Refer to figure 16)

1.

Front panel

2.

Pipe outlet panel

3.

Backward

4.

Sideways

5.

Downward

6.

Pipe outlet panel screw

7.

Forward

8.

Screw for front panel

When connecting the pipings downward, remove the knockout 
by making four holes in the middle on the each side of the 
knockout with a drill.

(Refer to figure 17)

1.

Drill

2.

Center area around knockout

3.

Knockout

4.

Slit

Gauge 
manifold
Charge hose

Make sure to use installation tools that are exclu-
sively made for R410A installations to withstand 
the pressure and to prevent foreign materials (e.g. 
mineral oils such as SUNISO and moisture) from 
mixing into the system.

Vacuum pump

Use a 2-stage vacuum pump with a non-return 
valve.

Make sure the pump oil does not flow backward 
into the system while the pump is not working.

Use a vacuum pump which can evacuate to 
500 microns.

Model

18·24 type

30~48 type

Maximum piping length

164 ft. (50 m)

230 ft. (70 m)

Maximum height 

difference

98 ft. (30 m) (outdoor unit above indoor unit)

98 ft. (30 m) (outdoor unit below indoor unit)

Place

Installation Protection 

method

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Regardless of the period

01_EN_3P435164-5M.fm  Page 6  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ18TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: