12. CAUTION FOR REFRIGERANT LEAKS

(Points to note in connection with refrigerant leaks)

Introduction

The installer and system specialist shall secure safety against 
leakage according to local regulations or standards. The following 
standards may be applicable if local regulations are not available.

The SPLIT System, like other air conditioning systems, uses R410A as 
refrigerant. R410A itself is an entirely safe non-toxic, non-combustible 
refrigerant. Nevertheless care must be taken to ensure that air condi-
tioning facilities are installed in a room which is sufficiently large. This 
assures that the maximum concentration level of refrigerant gas is not 
exceeded, in the unlikely event of major leak in the system and this in 
accordance to the local applicable regulations and standards.

Maximum concentration level

The maximum charge of refrigerant and the calculation of the maximum 
concentration of refrigerant is directly related to the humanly occupied 
space in to which it could leak.

The unit of measurement of the concentration is lb./ft

3

 (the weight in lb. 

of the refrigerant gas in 1ft

3

 volume of the occupied space).

Compliance to the local applicable regulations and standards for the 
maximum allowable concentration level is required.

Pay a special attention to the place, such as a basement, etc. 
where refrigerant can stay, since refrigerant is heavier than air.

Procedure for checking maximum concentration

Check the maximum concentration level in accordance with steps 1 to 4 
below and take whatever action is necessary to comply.

1.

Calculate the amount of refrigerant (lb.) charged to each system
separately.

NOTE

Where a single refrigerant facility is divided into 2 entirely indepen-
dent refrigerant systems then use the amount of refrigerant with
which each separate system is charged.

2.

Calculate a room volume (ft

3

)

3.

Calculating the refrigerant concentration by using the results of the
calculations in steps 1 and 2 above.

4.

Dealing with the situations where the result exceeds the maximum
concentration level.
Where the installation of a facility results in a concentration in excess
of the maximum concentration level then it will be necessary to
revise the system. 
Please consult your dealer.

amount of refriger-
ant in the unit 
(amount of refrig-
erant with which 
the system is 
charged before 
leaving the factory)

+

additional charging 
amount (amount of 
refrigerant added 
locally in accordance 
with the length of the 
refrigerant piping and 
type of indoor unit)

=

total amount 
of refriger-
ant (lb.) in 
the system

total amount of refrigerant in the 
refrigerant system

maximum concen-
tration level (lb./ft

3

)

volume (ft

3

) of the room in which 

there is an indoor unit installed

Direction of the refrigerant flow

Room where 
refrigerant leak has 
occurred (outflow of 
all the refrigerant 
from the system)

01_EN_3P435164-5M.fm  Page 17  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ18TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: