background image

English

9

CAUTION

• Use a conduit for field wiring.
• Outside the unit, make sure the low voltage wiring (i.e. for the 

remote controller wire, between units, etc.) and the high voltage 
wiring do not pass near each other, 

keeping them at least 

2 in. (50 mm) apart

.

Proximity may cause electrical interference, malfunctions, and 
breakage.

• Be sure to connect the power supply wiring to the power supply wir-

ing terminal block and secure it as described in “

7-3 How to con-

nect the power supply wiring

”.

• Transmission wiring should be secured as described in “

7-4 Trans-

mission wiring connection procedure

”.

• Secure wiring with clamp (accessory) to avoid contact with piping.
• Make sure the wiring and the front panel do not stick up above the 

structure, and close the panel firmly.

(Refer to figure 22)

1.

Fuse/Breaker

2.

Power supply

3.

Outdoor unit

4.

16V

5.

208/230V

6.

Indoor unit

7.

Remote controller

8.

Ground wire

7-2 How to lay the power supply wiring and trans-

mission wiring

Let the power supply wiring and transmission wiring with a conduit pass 
through one of the knockout on the front or side cover, and let the trans-
mission wiring with a conduit pass through another knockout.

• For protection from uninsulated live parts, thread the power supply 

wiring and the transmission wiring through the included insulation 
tube and secure it with the included clamp.

Precautions knockout

• Open the knockout with a hammer or the like.
• After knocking out the knockout, we recommend you remove burrs in the knockout and paint 

the edges and areas around the edges using the repair paint to prevent rusting.

• When passing wiring through knockout, make sure there are no 

burrs, and protect the wiring with protective tape.

(Refer to figure 23)

1.

Stop valve fixing plate

2.

Power supply wiring (including ground wire) or transmission 
wiring.

3.

Back of unit

4.

Knockout

5.

Side of unit

6.

Front of unit

7.

Terminal block

8.

Control Box

<Precautions when laying power supply wiring>

• Wiring of different thicknesses cannot be connected to the power 

supply terminal block. 
(Slack in the power supply wiring may cause abnormal heat.)

• Use sleeve-insulated round pressure terminals for connections to 

the power supply terminal block. When none are available, connect 
wire of the same diameter to both sides, as shown in the figure.

Follow the instructions below if the wiring gets very hot due to 
slack in the power supply wiring.

• For wiring, use the designated power wire and connect firmly, then 

secure using the included clamping material to prevent outside pres-
sure being exerted on the terminal board.

• Use an appropriate screwdriver for tightening the terminal screws.

A screwdriver with a small head will strip the head and make proper 
tightening impossible.

• Over-tightening the terminal screw may break it.

See the table below the tightening torque of the terminal screws.

7-3 How to connect the power supply wiring

CAUTION

Attach a circuit breaker or fuse. 

Insulation tube
(accessory)

Clamp
(accessory)

Power supply 
wiring

3 in. (75 mm)

2 in. (50 mm)
or more

5/8 in. (15.9 mm)

Insulation tube
(accessory)

Clamp
(accessory)

Transmission
wiring

3 in. (75 mm)

<Power supply wiring>

<Transmission wiring>

Ground wire

If small animals might enter the 
unit, block the knockout with an 
appropriate material (field supply).

Burr

Tightening torque (ft·lbf / N·m)

M5

Power supply terminal

1.76~2.15 / 2.39~2.91

M4

Shield ground

0.87~1.06 / 1.18~1.44

M3

Transmission wiring terminal block

0.58~0.72 / 0.8~0.97

Model

Phase and 

frequency

Voltage

Maximum 

overcurrent 

protective 

device

Minimum 

circuit 

ampacity

18·24 type

1~60Hz

208/230V

25A

16.5A

30·36·
42·48 type

1~60Hz

208/230V

35A

29.1A

Insulating sleeve 

Round crimp-style 
terminal

Electric Wire

Connect wires 
of the same gauge 
to both side.

Do not connect 
wires of different 
gauges.

Do not connect 
wires of the same 
gauge to one side.

01_EN_3P435164-5M.fm  Page 9  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ18TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: