background image

English

5

When something is obstructing the top

1.

Installation of single unit 

(Refer to figure 8-[7])

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

Note)
Get the lower part of the frame sealed so that air from the outlet does 
not bypass.

2.

Series installation (up to two units) 

(Refer to figure 8-[8])

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

Note)
1. Get the lower part of the frame sealed so that air from the outlet 

does not bypass.

2. Only two units at most can be installed in series.

(7)-4 IN CASE OF STACKED INSTALLATION

(1) In case obstacles exist in front of the outlet side 

(Refer to figure 9-[1])

(2) In case obstacles exist in front of the air inlet 

(Refer to figure 9-[2])

Note)
1. No more than two units should be stacked.
2. If there is a danger of water from the drain falling on the lower out-

door unit and freezing, install a roof (field supply) as shown in the 
figure 9.

3. To prevent the formation and growth of ice in the bottom frame of 

the 2nd level outdoor unit, install the outdoor unit so that the bot-
tom frame will be sufficiently higher than the roof. (It is recom-
mended to leave 19.6 in. (500 mm) or more)

4. About 4 in. (100 mm) is required as the dimension for laying the 

upper outdoor unit’s drain pipe.

5. Shut off the Z part (the area between the upper outdoor unit and 

the lower outdoor unit) so that outlet air does not bypass.

(7)-5 IN CASE OF MULTIPLE-ROW INSTALLATION (FOR ROOF 

TOP USE, ETC.)

1.

In case of installing one unit per row 

(Refer to figure 10-[1])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row 

(Refer to figure 10-[2])

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

5.

PRECAUTIONS ON INSTALLATION

• Before installation, make sure the unit is level and the foundation is 

sturdy enough to prevent vibration and noise.

• Fasten the unit in place using 4 foundation bolts M12 or equivalent. 

It is best to screw in the foundation bolt until their length remains 
13/16 in. (20 mm) above the foundation surface.

(Refer to figure 11)

1.

Diagram of lower surface

<Drain pipe installation>

• Locations where drain water from the outdoor unit might be a prob-

lem.
In such locations, for example, where the drain water might drip onto 
passersby, lay the drain pipe using the separately sold drain plug and 
seal up the drain holes in the bottom frame. For details, please con-
tact your dealer.
In case of installing the outdoor unit in cold climates, do not take this 
centralized drainage way. Otherwise, drain pipe freeze-up and ice 
build-up on the bottom frame way occur.

• When laying the drain pipe, at least 4 in. (100 mm) from the bottom 

of the outdoor unit is needed.

• Make sure the drainage works properly. 

(Watch out for water leaks if piping is brought out the bottom.)

(Refer to figure 12)

1.

Drain plug

2.

4 tabs

3.

Drain receiver

4.

Insert the drain receiver into the drain plug and hook the 
tabs.

5.

Bottom frame drain hole

6.

(1) Insert the drain plug through the drain hole in the 

bottom frame shown in figure 13.

(2) Turn the drain plug along the guides until it stops 

(approx. 40°).

7.

Guide

(Refer to figure 13)

1.

Air outlet side

2.

Diagram of lower surface 

3.

Drain hole (For plug)

4.

Drain hole

[How to remove the transport bracket] (30·36·42·48 type)

• A yellow transport bracket and washer are attached to the leg of the 

compressor to protect the unit during transportation, so remove 
them as shown in figure 14.

(Refer to figure 14)

1.

Compressor

2.

Securing nut

3.

Transport bracket (Yellow)

4.

Turn in the direction of the arrow and remove.

(1) Open the sound-proof cover as shown in figure 14. 

Do not pull the sound-proof cover or remove it from the compressor.

(2) Remove the securing nut.
(3) Remove the washer.
(4) Remove the transport bracket as shown in figure 14.
(5) Retighten the securing nut.
(6) Return the sound-proof cover as it was.

L

A

 H

0 < L 

 1/2H

4 (100)

1/2H < L 

 

H

8  (200)

H < L

Set the frame to be L 

 H

L

A

 H

0 < L 

 1/2H

10 (250)

1/2H < L 

 

H

12  (300)

H < L

Set the frame to be L 

 H

L

A

 H

0 < L 

 1/2H

10 (250)

1/2H < L 

 H

12 (300)

H < L

Installation impossible.

01_EN_3P435164-5M.fm  Page 5  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ18TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: