background image

4

English

• In areas where the outside air temperature drops below 32°F (0°C) 

for more than 12 hours continuously, install a drain-pan heater 
(optional accessory) on the bottom frame to prevent the drain from 
freezing.

• An optional drain pan heater is available when the unit is installed 

in a climate where the drain may freeze.

• The installer should use their local knowledge to determine if this 

accessory is necessary to prevent the drain from freezing.

• Do not use a concentrated drain plug (field supply).

(If a drain plug and/or drain pipe are/is used, there is a risk of freez-
ing.)

• If there is a problem with drain dripping from the bottom frame 

drain, set up a roof (field supply) below the outdoor unit, or enact 
other countermeasures.

• Remove the rear inlet grille to prevent snow from accumulating on 

the rear fins.

(4)

When there is possibility of short-circuit depending on the ambient 
situation, use the wind direction adjusting plate (optional acces-
sory).

(5)

The refrigerant gas (R410A) is a safe, non-toxic and non-flammable 
gas, but if it leaks into the room, the concentration may exceed tol-
erance levels, especially in small rooms, so steps need to be taken 
to prevent refrigerant leakage. See the equipment design reference 
for details.

(6)

Inverter-type air conditioners sometimes cause static in other elec-
trical appliances.
When selecting an installation location, make sure the air condi-
tioner and all wiring are sufficiently far away from radios, computers, 
stereos, and other appliances, as shown in figure 4.
Particularly for locations with weak reception, ensure there is a dis-
tance of at least 9.8 ft. (3 m) for indoor remote controllers, place 
power supply wiring and transmission wiring in conduits, and 
ground the conduits. Use non-shielded wire for transmission wiring.

(Refer to figure 4)

1.

Indoor unit

2.

Fuse/Breaker

3.

Remote controller

4.

Personal computer or radio

(7)

Space needed for installation
<

Precautions when installing units in series

>

• The direction for field piping is either forward or down when install-

ing units in series, as shown in the figure (5~10).

• If the piping is brought out from the back, the outdoor unit will 

require at least 10 in. (250 mm) from its right side. 

(7)-1 IN CASE OBSTACLES EXIST ONLY IN FRONT OF THE AIR 

INLET

When nothing is obstructing the top

1.

Installation of single unit
• In case obstacles exist only in front of the air inlet

(Refer to figure 5-[1])

• In case obstacles exist in front of the air inlet and on both sides of 

the unit 

(Refer to figure 5-[2])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row
• In case obstacles exist in front of the air inlet and on both sides of 

the unit 

(Refer to figure 5-[3])

When something is obstructing the top

1.

Installation of single unit
• In case obstacles exist only in front of the air inlet

(Refer to figure 6-[1])

• In case obstacles exist in front of the air inlet and on both sides of 

the unit 

(Refer to figure 6-[2])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row
• In case obstacles exist in front of the air inlet and on both sides of 

the unit 

(Refer to figure 6-[3])

(7)-2 IN CASE OBSTACLES EXIST IN FRONT OF THE OUTLET 

SIDE

When nothing is obstructing the top

1.

Installation of single unit 

(Refer to figure 7-[1])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row 

(Refer to figure 7-[2])

When something is obstructing the top

1.

Installation of single unit 

(Refer to figure 7-[3])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row 

(Refer to figure 7-[4])

(7)-3 IN CASE OBSTACLES EXIST IN FRONT OF BOTH THE AIR 

INLET AND OUTLET SIDES

Pattern 1:

Where obstacle in front of the air outlet is higher than the 
unit.
(There is no height limit for obstructions on the intake side.)

When nothing is obstructing the top

1.

Installation of single unit 

(Refer to figure 8-[1])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row 

(Refer to figure 8-[2])

When something is obstructing the top

1.

Installation of single unit 

(Refer to figure 8-[3])

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

Note) 
Close the area under the frame so the outlet air does not bypass 
there.

2.

Series installation (up to two units) 

(Refer to figure 8-[4])

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

Note)
1. Close the area under the frame so the outlet air does not bypass 

there.

2. No more than two units can be installed in series.

Pattern 2:

Where obstacles in front of the air outlet is lower than the 
unit.
(There is no height limit for obstructions on the intake side.)

When nothing is obstructing the top

1.

Installation of single unit 

(Refer to figure 8-[5])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row 

(Refer to figure 8-[6])

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

L

A

 H

0 < L 

 1/2H

30 (750)

1/2H < L 

 H

40 (1000)

H < L

Set the frame to be L 

 H

L

A

 H

0 < L 

 1/2H

40 (1000)

1/2H < L 

 H

50 (1250)

H < L

Set the frame to be L 

 H

L

A

0 < L 

 1/2H

10 (250)

1/2H < L 

 H

12 (300)

01_EN_3P435164-5M.fm  Page 4  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ18TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: