background image

12

English

10-2 Temperature control operation checklist

•   After check operation is complete, check the temperature control 

using normal operation. 
(Heating is not possible if the outdoor temperature is 75°F (24°C) or 
higher.)
(1)  Make sure the indoor and outdoor units are operating normally. 

(If liquid compression by the compressor or other abnormal 
noises can be heard, stop the unit immediately, heat the crank 

case for a sufficient amount of time, and try again.)

(2)  Check to see if cold (or hot) air is coming out of the indoor unit.
(3)  Press the fan direction and fan speed buttons on the indoor unit 

to see if they operate properly.

<Precautions during temperature control checks>

•   For around 5 minutes after the compressor stops, the compressor 

will not run even if the “On/Off” button on the remote controller is 
pressed.

•  When the system operation is stopped by the remote controller, the 

outdoor unit may continue operating for up to 1 minute.

•  Malfunction code “U3” is displayed if check operation is not per-

formed using the test operation button the first time after installation. 

Perform the check operation in accordance with “

10-1 Power On–

Check Operation

”.

[Remote controller displays malfunction code]
(Check on a remote controller)

Malfunc-

tion code

Installation error

Remedial action

E3

The stop valve of outdoor unit 

is left closed.

Open the gas-side stop valve and the 

liquid-side stop valve.

Refrigerant overcharge.

Recalculate the required amount of refrig-

erant from the piping length and correct 

the refrigerant charge level by recovering 

any excessive refrigerant with a refriger-

ant recovery unit.

F6

Refrigerant overcharge.

Recalculate the required amount of refrig-

erant from the piping length and correct 

the refrigerant charge level by recovering 

any excessive refrigerant with a refriger-

ant recovery unit.

E4

The stop valve of outdoor unit 

is left closed.

Open the gas-side stop valve and the 

liquid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant charge 

has been finished correctly.

Recalculate the required amount of refrig-

erant from the piping length and add an 

adequate amount of refrigerant.

F3

Refrigerant overcharge.

Recalculate the required amount of refrig-

erant from the piping length and correct 

the refrigerant charge level by recovering 

any excessive refrigerant with a refriger-

ant recovery unit.

The stop valve of outdoor unit 

is left closed.

Open the gas-side stop valve and the 

liquid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant charge 

has been finished correctly.

Recalculate the required amount of refrig-

erant from the piping length and add an 

adequate amount of refrigerant.

U2

Insufficient power supply 

voltage

Check to see if the power supply voltage 

is supplied properly.

U3

If check operation has not been 

performed.

Perform check operation.

U4

No power is supplied to 

outdoor unit.

Turn the power on for the outdoor 

unit.

UA

If no dedicated indoor unit is 

being used.

Check the indoor unit. If it is not a dedi-

cated unit, replace the indoor unit.

UF

The stop valve of outdoor unit is 

left closed.

Open the gas-side stop valve and the 

liquid-side stop valve.

If the right indoor unit piping and  

wiring are not properly con-

nected to the outdoor unit.

Make sure that the right indoor unit piping 

and wiring are properly connected to the 

outdoor unit.

UH

If the transmission wiring has 

not be connected or it has 

shorted.

Make sure the transmission wiring is cor-

rectly attached to terminals (X2M) F1/F2 

(TO IN/D UNIT) on the outdoor unit circuit 

board.

•   When using a central controller, see the installation manual or ser-

vice manual which came with the central controller.

[If nothing is displayed on the remote controller]

•   There might be a problem with the connections or communication 

between the indoor unit and the remote controller. 
Make sure all the wiring is properly connected.

 

CAUTION

To the piping installer, To the electrician

After the test operation, when handing the unit over to the customer, 
make sure the front panel on the unit and all screws are attached.

10-3 Final refrigerant charge adjustment

It is not necessary to do this final adjustment normally, but perform the 

 

following operation only when the most adequate refrigerant charge for  

the best performance is required and the piping length between the out-

door and indoor units is less than 50 ft.(15 m). 

The outdoor temperature must be between 65°F (18°C) and 105°F (40°C).
The number of revolutions of the compressor must be greater than or equal 

to the charge mode. (It can be confirmed by LED display on PC board)
The number of revolutions of the compressor LED display.

 

 :Chargeable  

 :Impossible to charge)

Run the system for 60 minutes in cooling by the forced operation using 

the field setting mode 2, No.20 LED 

:ON, mode 2, No.7 LED 

:ON,  

(Refer to Service Manual.) to allow pressures to stabilize.

Check subcooling of outdoor unit at LSV. Systems should have the 

target subcooling in the table below.

a.  If the subcooling is low, add charge little by little to raise subcooling 

to the target value. (The maximum additional charge is 2.2 lbs. (1kg))

b.  If the subcooling is high, remove charge to lower the subcooling to 

the target value.

Model

Target subcooling

18·24 type

6±1°F (3.33±0.56°C)

30·36 type

7±1°F (3.89±0.56°C)

42 type

8±1°F (4.44±0.56°C)

48 type

9±1°F (5.00±0.56°C)

However, if the connected indoor unit is FCQ or FBQ, refer to the table below.

Model

Target subcooling

18·24·30 type

6±1°F (3.33±0.56°C)

36 type

7±1°F (3.89±0.56°C)

42 type

8±1°F (4.44±0.56°C)

48 type

9±1°F (5.00±0.56°C)

11.    ENERGY SAVING AND OPTIMUM  

OPERATION

The unit is equipped with advanced energy saving functionality. 
Depending on the priority, emphasis can be put on energy saving or 
comfort level. Several parameters can be selected, resulting
in the optimal balance between energy consumption and comfort for the 
particular application.

Several patterns are available and explained below. Modify the param-
eters to the needs of your building and to realize the best balance  
between energy consumption and comfort.

Refer to Service Manual for changing the field settings.
Setting definition: [A-B]=C; A=mode, B=setting NO., C=setting value.

01_EN_3P591321-10E.indd   12

01_EN_3P591321-10E.indd   12

2022/08/31   18:53:22

2022/08/31   18:53:22

Summary of Contents for RZQ18TBVJUA

Page 1: ...re reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tr...

Page 2: ...ore 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm gure 5 gure 6 1 2 3 4 20 500 or more 4 100 or more 4 100 or more 20 500 or less 20 500 or less 20 500 or more 40 10...

Page 3: ...ore 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 gure 9 gure 10 gure 11 gure 12 inch mm inch mm 4 4 6 5 16 160 6 5 16 160...

Page 4: ...2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 gure 26 gure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate accessory 2 4 2 Lock nut Cover Conduit 5 1 8 2 4 4 2 7 3 6 5 L...

Page 5: ...ne wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explos...

Page 6: ...r or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage b...

Page 7: ...ration and where the unit can be installed level A locations where there is enough space to install the unit Places where the indoor and outdoor unit s piping and wiring lengths come within the allowa...

Page 8: ...to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and on both sides of the unit Refer to figure 5 3...

Page 9: ...sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 foundation bolts M12 or equivalent It is best to screw in the foundation bol...

Page 10: ...rial Jointless phosphor deoxidized copper pipe Thickness Select a thickness for the refrigerant piping which com plies with national and local laws Maximum piping length and height difference between...

Page 11: ...9 16 inch 15 mm Minimum thickness 3 4 inch 20 mm When using commercial copper pipes and fittings observe the following a Insulation of pipes should be done after performing air tight test and vacuum d...

Page 12: ...e a push rod provided charging hose for operation Be sure to tighten the valve cap securely after operation Tightening torque 8 5 10 3 ft lbf 10 8 14 7 N m 7 ELECTRIC WIRING CAUTION To the electrician...

Page 13: ...ut make sure there are no burrs and protect the wiring with protective tape If small animals might enter the unit block the knockout with an appropriate material field supply Burr Refer to figure 23 1...

Page 14: ...igerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition changes if charged in a gaseous state and normal system operation would no...

Page 15: ...tdoor unit operation status and check for any incorrect wiring 1 Close the outdoor unit s front panel Turn the power on for the outdoor unit and the indoor unit 2 Open the outdoor unit s front panel M...

Page 16: ...place the indoor unit UF The stop valve of outdoor unit is left closed Open the gas side stop valve and the liquid side stop valve If the right indoor unit piping and wiring are not properly con necte...

Page 17: ...he steady state condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjuncti...

Page 18: ...rature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve default automatic mo...

Page 19: ...Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout is controlled by AB...

Page 20: ...h h k h h k 1 6 C 35 F k h h k h k h 4 4 C 40 F k h h k h k k 7 2 C 45 F k h h k k h h 10 C 50 F k h h k k h k Forced heat pump lockout k h h k k k h Heat pump lockout release differential Heat pump...

Page 21: ...rant from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the...

Page 22: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P591321 10E EM22A013A 2208 SP 00_CV_3P591321 10E indd 5 00_CV_3P591321 10E indd 5 2022 08 31 18 52 35 2022 08 31 18 52 35...

Reviews: