background image

10

English

 

CAUTION

• The wiring should be selected in compliance with local laws and 

regulations. See the table above.

• Always turn off the power before doing wiring work.
•  Grounding should be done in compliance with local laws and regula-

tions.

•  

As shown in figure 25, when connecting the power supply wiring to 
the power supply terminal block, be sure to clamp securely.

• 

Once wiring work is completed, check to make sure there are no 

loose connections among the electrical parts in the control box.

(Refer to figure 24)

1. 

Stop valve fixing plate

2. 

Clamp (accessory) 

3. 

Connecting power supply wiring

4. 

Ground wire (Yellow/Green)

5. 

Terminal block (X1M)

6. 

Transmission wiring

7. 

(To X2M [TO IN/ D UNIT] (F1, F2))

8. 

Terminal block (X2M)

9. 

Insulation tube (Large) (accessory)

10. 

Insulation tube (Small) (accessory)

11. 

Cut off the insulation tube sticking out of the outdoor unit.

12. 

Wire clamp and screw (accessory)

7-4  Transmission wiring connection procedure

• 

If an excessive force is applied while connecting a wire to the termi

-

nal block, the connection may be damaged.

(Refer to figure 25)

1. 

Terminal block (X2M)

2. 

Use balance type shield wire (with no polarity).

3. 

Indoor unit

4. 

Under no circumstances should 208/230V be connected.

Precautions regarding the length of wiring between units

 Exceeding the following limits may cause transmission malfunctions, so 

observe them.

Max. wiring length 

Max. 3280 ft. (1000 m)

Precautions regarding wiring between units

• 

 Do not connect 208/230V power supply wiring to terminals for 

 

the transmission wiring. Doing so would destroy the entire sys

-

tem.

• 

Wiring to the indoor unit should be wired to F1 and F2 (TO IN/D unit) 
on the outdoor unit’s terminal block (X2M).

NOTE 

• 

The above wiring should be wired using AWG18-16 (0.75-1.25 mm

2

stranded, non-shielded wiring. 

 

(See figure 25 for how to ground the shielded parts.)

•  All transmission wiring is to be procured on site.

8.     ADDITIONAL REFRIGERANT CHARGE

 

WARNING

•  

When leaving the unit with the power on, be sure to 

 

switch with another person doing the installation or close  
the front panel.

8-1 

Before adding refrigerant

• 

Make sure the following work and inspection is complete, in accor

-

dance with the installation manual.
• Piping
• Wiring
• 

Air tight test, Vacuum drying

8-2  Checking the refrigerant tank

•   Charge the refrigerant to the liquid pipe in its liquid state. 

Since R410A is a mixed refrigerant, its composition changes if 

charged in a gaseous state and normal system operation would no 
longer be assured.

•   Check whether the tank has a siphon pipe before charging and place the 

tank so that the refrigerant is charged in liquid form. (See the figure below.)

Tank with siphon pipe

Other tanks

There is a siphon 
pipe inside, so the 
cylinder need not be 
upside-down to fill 
with liquid.
(Stand the cylinder 
upright when filling.)

Stand the tank 
upside down and 
charge.

8-3 

Adding refrigerant

 

WARNING

•  To avoid injury always use protective gloves and eye protection 

when charging refrigerant.

• To avoid injury do not charge with unsuitable substances. 

Use only the appropriate refrigerant.

 

NOTE

•  

Refrigerant cannot be charged until field wiring has been completed.

 

Refrigerant may only be charged after performing the airtight test 
and the vacuum drying (see above). 

When charging refrigerant into the system, take care that its maxi

-

mum allowable charge is never exceeded, in view of the danger of 

liquid slugging. 
Refrigerant containers shall be opened slowly. 

To avoid compressor breakdown, do not charge the refrigerant 
more than the specified amount to raise the condensing pressure.

Filling after calculating the amount of refrigerant to add

1.  Calculate the amount of refrigerant to add as described below.

<Calculation for refrigerant charging amount>

 Refrigerant equivalent to 25 ft. (7.6 m) liquid piping is factory-charged in 

the outdoor unit.
Calculate the refrigerant charging amount based on the following formula.

• 

If the liquid piping length is 25 ft. (7.6 m) or less 

(lbs)

Additional refrigerant 

charging amount [

A

]

Indoor unit 

type

FBQ30, 36, 42, 48

FCQ30, 36, 42, 48
FAQ, FBQ18

0.15

FBQ24

0.20

FCQ18, 24

0.36

FTQ18, 24

0.46

FTQ30, 36

1.07

FTQ42, 48

1.41

• 

If the liquid piping length is more than 25 ft. (7.6 m)

[

A

]

+

(Liquid piping length–25) ft. 

× 0.036

=

Additional refrigerant 

charging amount

lbs

lbs

lbs

Record the additional amount to the label stuck on the back of front panel.

2.  After the vacuum drying is finished, open valve A and charge the 

calculated amount of refrigerant through the service port for the 
liquid-side stop valve. 
(See “Stop valve operation procedure” in “

6. REFRIGERANT PIP-

ING

” for details on how to use the stop valve.) 

01_EN_3P591321-10C.indd   10

01_EN_3P591321-10C.indd   10

2022/08/16   20:03:52

2022/08/16   20:03:52

Summary of Contents for RZQ18TBVJUA

Page 1: ...re reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tr...

Page 2: ...ore 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm gure 5 gure 6 1 2 3 4 20 500 or more 4 100 or more 4 100 or more 20 500 or less 20 500 or less 20 500 or more 40 10...

Page 3: ...ore 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 gure 9 gure 10 gure 11 gure 12 inch mm inch mm 4 4 6 5 16 160 6 5 16 160...

Page 4: ...2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 gure 26 gure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate accessory 2 4 2 Lock nut Cover Conduit 5 1 8 2 4 4 2 7 3 6 5 L...

Page 5: ...ne wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explos...

Page 6: ...r or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage b...

Page 7: ...ration and where the unit can be installed level A locations where there is enough space to install the unit Places where the indoor and outdoor unit s piping and wiring lengths come within the allowa...

Page 8: ...to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and on both sides of the unit Refer to figure 5 3...

Page 9: ...sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 foundation bolts M12 or equivalent It is best to screw in the foundation bol...

Page 10: ...rial Jointless phosphor deoxidized copper pipe Thickness Select a thickness for the refrigerant piping which com plies with national and local laws Maximum piping length and height difference between...

Page 11: ...9 16 inch 15 mm Minimum thickness 3 4 inch 20 mm When using commercial copper pipes and fittings observe the following a Insulation of pipes should be done after performing air tight test and vacuum d...

Page 12: ...e a push rod provided charging hose for operation Be sure to tighten the valve cap securely after operation Tightening torque 8 5 10 3 ft lbf 10 8 14 7 N m 7 ELECTRIC WIRING CAUTION To the electrician...

Page 13: ...ut make sure there are no burrs and protect the wiring with protective tape If small animals might enter the unit block the knockout with an appropriate material field supply Burr Refer to figure 23 1...

Page 14: ...igerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition changes if charged in a gaseous state and normal system operation would no...

Page 15: ...tdoor unit operation status and check for any incorrect wiring 1 Close the outdoor unit s front panel Turn the power on for the outdoor unit and the indoor unit 2 Open the outdoor unit s front panel M...

Page 16: ...place the indoor unit UF The stop valve of outdoor unit is left closed Open the gas side stop valve and the liquid side stop valve If the right indoor unit piping and wiring are not properly con necte...

Page 17: ...he steady state condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjuncti...

Page 18: ...rature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve default automatic mo...

Page 19: ...Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout is controlled by AB...

Page 20: ...h h k h h k 1 6 C 35 F k h h k h k h 4 4 C 40 F k h h k h k k 7 2 C 45 F k h h k k h h 10 C 50 F k h h k k h k Forced heat pump lockout k h h k k k h Heat pump lockout release differential Heat pump...

Page 21: ...rant from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the...

Page 22: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P591321 10E EM22A013A 2208 SP 00_CV_3P591321 10E indd 5 00_CV_3P591321 10E indd 5 2022 08 31 18 52 35 2022 08 31 18 52 35...

Reviews: