background image

7

English

•   After knocking out the knockout, it is recommended to apply repair 

paint to the edge and the surrounding end surfaces to prevent rust-
ing.

(Refer to figure 18)

1. 

Bottom frame

2. 

Field piping

<Precautions when connecting pipes>

• 

PleaserefertotheTable1forthedimensionsforprocessingflares.

• 

Whenconnectingtheflarenut,coattheflarebothinsideandoutside

with refrigerating unit oil and initially tighten by hand 3 or 4 turns 

beforetighteningfirmly.

•  Please refer to the Table 1 for the tightening torque. (Too much tight-

eningwillendupinsplittingoftheflare.)

Table 1

Pipe size 

(in.)

Tightening 

torque(ft·lbf)

A dimen-

sions for 

processing 

flares(in.)

Flareshape(in.)

φ

 3/8” 

(9.5mm)

24.1~29.4

(32.7~39.9N·m)

0.504~0.520

(12.8~13.2mm)

A

45

°± 2

°

90

°± 2

°

R0.016~0.031

(0.4~0.8 mm)

φ

 5/8” 

(15.9mm)

45.6~55.6

(61.8~75.4N·m)

0.760~0.776

(19.3~19.7mm)

Refrigerant oil

•  After all the piping has been connected, use nitrogen to perform a 

gas leak check.

Precautions for connecting pipes

• 

 

Becarefulnottoletthefieldpipingcomeintocontactwiththecom

-

pressor terminal cover. 
Adjust the height of the insulation material on liquid pipe when it has 
the possibility of getting in contact with the terminal. Also make sure 

thatthefieldpipingdoesnottouchthemountingboltofthecompres

-

sor.

(Refer to figure 19)

1. 

Compressor

2. 

Corking, etc.

3. 

Insulation material

4. 

Bolts

5. 

Field piping

• 

 

If installing the outdoor unit higher than the indoor unit, caulk the 
space around insulation and tubes because condensation on the 
check valve can seep through to the indoor unit side.

[Preventing foreign objects from entering]

•   Plug the pipe through-holes with putty or insulating material (pro 

curedlocally)tostopupallgaps,asshowninfigure20.(Figure20
indicatestheforwardcase.Dothesameincaseofotherdirections.)

Insects or small animals entering the outdoor unit may cause a short 
in the control box.

(Refer to figure 20)

1. 

Putty or insulating material

2. 

(fieldsupply)

6-6 

Thermal insulation of piping

• 

Insulatethefieldpiping(liquidandgas-side).(Notinsulatingthem
maycauseleaking.)

•  The insulation dimension is recommended as following:

Ambienttemperature:86°F(30°C),

humidity : Below 80% RH

Ambienttemperature:86°F(30°C),

humidity : 80% RH and above

Minimum thickness : 9/16 inch  

(15mm)

Minimum thickness : 3/4 inch  

(20mm)

•   

Whenusingcommercialcopperpipesandfittings,observethefollowing:
a)Insulationofpipesshouldbedoneafterperformingairtighttest

and vacuum drying.

b)Heattransferrate:0.024to0.030BTU/fth°F(0.041to0.052W/Mk

(0.035to0.045kcal/mh°C))

c)

Be sure to use insulation that is designed for use with HVAC Sys-
tems.

d)Thehighesttemperaturethatthegas-sidepipingcanreachis

around248°F(120°C),sobesuretouseinsulatingmaterialwhich
issufficientlyresistanttothistemperature.

 

CAUTION

For local insulation, be sure to insulate all the way to the pipe con-
nections inside the unit.
Exposed piping may cause leaks or burns on contact.

6-7 

Air tight test and vacuum drying

After doing the piping, perform the following inspections.

Air tight test

Besuretousenitrogengas.(Seethefigure(“Stopvalveoperationpro

-

cedure”)forthelocationoftheserviceport.)

[Procedure]

Pressurizefromtheliquidpipesandgaspipesto550psi(3.8MPa)
(andnotabove550psi(3.8MPa)).Ifthereisnotpressuredropoverthe

next 24 hours, the equipment has passed the test.

Ifthepressuredrops,checkforleakagepositions.(Confirmthatthereis
noleakage,thenreleasenitrogen.)
IfaFTQindoorunitisused,onlypressurizeto450psi(3.1MPa).

Vacuum drying

Useavacuumpumpthatcancreateavacuumdowntoatleast

 

500 microns.

[Procedure]
Operate the vacuum pump for 

at least 2 hours

 from 

both the liquid  and 

gas pipes

 and decrease the pressure to at least 500 microns. 

Leave at below 500 microns for at least 1 hour and make sure that the 
vacuum gauge does not rise. (If it does rise, there is either still moisture 

inthesystemoraleak.)

Cases where moisture might enter the piping

 (i.e., if doing work  

during the rainy season, if the actual work takes long enough that con-
densation may form on the inside of the pipes, if rain might enter the  

pipesduringwork,etc.)

After performing the vacuum drying for 2 hours, pressurize to 7.2 psi 

(0.05MPa)(i.e.,vacuumbreakdown)withnitrogengas,thendepressur

-

ize down to at least 500 microns a for an hour using the vacuum pump 

(vacuumdrying).(Ifthepressuredoesnotreachatleast500microns

even after depressurizing for at least 2 hours, repeat the vacuum break-

down-vacuumdryingprocess.)Leaveasavacuumfor1hourafterthat,

and make sure the vacuum gauge does not rise.

01_EN_3P591321-10C.indd   7

01_EN_3P591321-10C.indd   7

2022/07/13   13:48:55

2022/07/13   13:48:55

Summary of Contents for RZQ18TBVJUA

Page 1: ...re reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tr...

Page 2: ...ore 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm gure 5 gure 6 1 2 3 4 20 500 or more 4 100 or more 4 100 or more 20 500 or less 20 500 or less 20 500 or more 40 10...

Page 3: ...ore 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 gure 9 gure 10 gure 11 gure 12 inch mm inch mm 4 4 6 5 16 160 6 5 16 160...

Page 4: ...2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 gure 26 gure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate accessory 2 4 2 Lock nut Cover Conduit 5 1 8 2 4 4 2 7 3 6 5 L...

Page 5: ...ne wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explos...

Page 6: ...r or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage b...

Page 7: ...ration and where the unit can be installed level A locations where there is enough space to install the unit Places where the indoor and outdoor unit s piping and wiring lengths come within the allowa...

Page 8: ...to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and on both sides of the unit Refer to figure 5 3...

Page 9: ...sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 foundation bolts M12 or equivalent It is best to screw in the foundation bol...

Page 10: ...rial Jointless phosphor deoxidized copper pipe Thickness Select a thickness for the refrigerant piping which com plies with national and local laws Maximum piping length and height difference between...

Page 11: ...9 16 inch 15 mm Minimum thickness 3 4 inch 20 mm When using commercial copper pipes and fittings observe the following a Insulation of pipes should be done after performing air tight test and vacuum d...

Page 12: ...e a push rod provided charging hose for operation Be sure to tighten the valve cap securely after operation Tightening torque 8 5 10 3 ft lbf 10 8 14 7 N m 7 ELECTRIC WIRING CAUTION To the electrician...

Page 13: ...ut make sure there are no burrs and protect the wiring with protective tape If small animals might enter the unit block the knockout with an appropriate material field supply Burr Refer to figure 23 1...

Page 14: ...igerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition changes if charged in a gaseous state and normal system operation would no...

Page 15: ...tdoor unit operation status and check for any incorrect wiring 1 Close the outdoor unit s front panel Turn the power on for the outdoor unit and the indoor unit 2 Open the outdoor unit s front panel M...

Page 16: ...place the indoor unit UF The stop valve of outdoor unit is left closed Open the gas side stop valve and the liquid side stop valve If the right indoor unit piping and wiring are not properly con necte...

Page 17: ...he steady state condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjuncti...

Page 18: ...rature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve default automatic mo...

Page 19: ...Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout is controlled by AB...

Page 20: ...h h k h h k 1 6 C 35 F k h h k h k h 4 4 C 40 F k h h k h k k 7 2 C 45 F k h h k k h h 10 C 50 F k h h k k h k Forced heat pump lockout k h h k k k h Heat pump lockout release differential Heat pump...

Page 21: ...rant from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the...

Page 22: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P591321 10E EM22A013A 2208 SP 00_CV_3P591321 10E indd 5 00_CV_3P591321 10E indd 5 2022 08 31 18 52 35 2022 08 31 18 52 35...

Reviews: