background image

5

English

When something is obstructing the top

1.  Installation of single unit 

(Refer to figure 8-[7])

 

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

L

A

L ≤ H

0 < L ≤ 1/2H

4(100)

1/2H < L ≤ H

8(200)

H < L

Set the frame to be L ≤ H

Note)
Get the lower part of the frame sealed so that air from the outlet does 
not bypass.

2. 

Series installation (up to two units) 

(Refer to figure 8-[8])

 

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

L

A

L ≤ H

0 < L ≤ 1/2H

10(250)

1/2H < L ≤ H

12(300)

H < L

Set the frame to be L ≤ H

Note)
1.  Get the lower part of the frame sealed so that air from the outlet 

does not bypass.

2. 

Only two units at most can be installed in series.

(7)-4  IN CASE OF STACKED INSTALLATION

(1)  In case obstacles exist in front of the outlet side  

(Refer to figure 9-[1])

(2) In case obstacles exist in front of the air inlet 

(Refer to figure 9-[2])

Note)
1.  No more than two units should be stacked.

2. 

 If there is a danger of water from the drain falling on the lower 

outdoor unit and freezing, install a roof (field supply) as shown in the 
figure 9.

3. 

 To prevent the formation and growth of ice in the bottom frame of  

the 2nd level outdoor unit, install the outdoor unit so that the 
bottom frame will be sufficiently higher than the roof. (It is recom

-

mended to leave 19.6 in. (500 mm) or more)

4.  About 4 in. (100 mm) is required as the dimension for laying the 

upper outdoor unit’s drain pipe.

5.  Shut off the Z part (the area between the upper outdoor unit and 

the lower outdoor unit) so that outlet air does not bypass.

(7)-5   IN CASE OF MULTIPLE-ROW INSTALLATION (FOR ROOF 

TOP USE, ETC.)

1.  In case of installing one unit per row 

(Refer to figure 10-[1])

2.  In case of installing multiple units (2 units or more) in lateral connec

-

tion per row 

(Refer to figure 10-[2])

 

Relation of dimensions of H, A, and L are shown in the table below.

inch (mm)

L

A

L ≤ H

0 < L ≤ 1/2H

10(250)

1/2H < L ≤ H

12(300)

H < L

Installation impossible.

5.    PRECAUTIONS ON INSTALLATION

•  Before installation, make sure the unit is level and the foundation is 

sturdy enough to prevent vibration and noise.

• 

Fasten the unit in place using 4 foundation bolts M12 or equivalent. 

 

It is best to screw in the foundation bolt until their length remains  

13/16 in. (20 mm) above the foundation surface.

(Refer to figure 11)

1. 

Diagram of lower surface

<Drain pipe installation>

•   Locations where drain water from the outdoor unit might be a prob-

lem.  
In such locations, for example, where the drain water might drip onto 
passersby, lay the drain pipe using the separately sold drain plug and  
seal up the drain holes in the bottom frame. For details, please con-
tact your dealer. 
In case of installing the outdoor unit in cold climates, do not take this 
centralized drainage way. Otherwise, drain pipe freeze-up and ice 
build-up on the bottom frame way occur.

•  When laying the drain pipe, at least 4 in. (100 mm) from the bottom 

of the outdoor unit is needed.

•  Make sure the drainage works properly.  

(Watch out for water leaks if piping is brought out the bottom.)

(Refer to figure 12)

1. 

Drain plug

2. 

4 tabs

3. 

Drain receiver

4. 

 Insert the drain receiver into the drain plug and hook the 
tabs.

5. 

Bottom frame drain hole

6. 

(1)  Insert the drain plug through the drain hole in the  

 

bottom frame shown in figure 13.

 

(2) Turn the drain plug along the guides until it stops 

 

 

(approx. 40°).

7. 

Guide

(Refer to figure 13)

1. 

Air outlet side

2. 

Diagram of lower surface 

3. 

Drain hole (For plug)

4. 

Drain hole

[How to remove the transport bracket] (30·36·42·48 type)

•   A yellow transport bracket and washer are attached to the leg of the  

compressor to protect the unit during transportation, so remove 

them as shown in figure 14.

(Refer to figure 14)

1. 

Compressor

2. 

Securing nut

3. 

Transport bracket (Yellow)

4. 

Turn in the direction of the arrow and remove.

(1)  Open the sound-proof cover as shown in figure 14. 

 

Do not pull the sound-proof cover or remove it from the compressor.

(2)  Remove the securing nut.
(3)  

Remove the washer.

(4)  Remove the transport bracket as shown in figure 14.

(5)  Retighten the securing nut.

(6)  

Return the sound-proof cover as it was.

01_EN_3P591321-10C.indd   5

01_EN_3P591321-10C.indd   5

2022/07/12   17:13:29

2022/07/12   17:13:29

Summary of Contents for RZQ18TBVJUA

Page 1: ...re reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tr...

Page 2: ...ore 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm gure 5 gure 6 1 2 3 4 20 500 or more 4 100 or more 4 100 or more 20 500 or less 20 500 or less 20 500 or more 40 10...

Page 3: ...ore 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 gure 9 gure 10 gure 11 gure 12 inch mm inch mm 4 4 6 5 16 160 6 5 16 160...

Page 4: ...2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 gure 26 gure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate accessory 2 4 2 Lock nut Cover Conduit 5 1 8 2 4 4 2 7 3 6 5 L...

Page 5: ...ne wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explos...

Page 6: ...r or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage b...

Page 7: ...ration and where the unit can be installed level A locations where there is enough space to install the unit Places where the indoor and outdoor unit s piping and wiring lengths come within the allowa...

Page 8: ...to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and on both sides of the unit Refer to figure 5 3...

Page 9: ...sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 foundation bolts M12 or equivalent It is best to screw in the foundation bol...

Page 10: ...rial Jointless phosphor deoxidized copper pipe Thickness Select a thickness for the refrigerant piping which com plies with national and local laws Maximum piping length and height difference between...

Page 11: ...9 16 inch 15 mm Minimum thickness 3 4 inch 20 mm When using commercial copper pipes and fittings observe the following a Insulation of pipes should be done after performing air tight test and vacuum d...

Page 12: ...e a push rod provided charging hose for operation Be sure to tighten the valve cap securely after operation Tightening torque 8 5 10 3 ft lbf 10 8 14 7 N m 7 ELECTRIC WIRING CAUTION To the electrician...

Page 13: ...ut make sure there are no burrs and protect the wiring with protective tape If small animals might enter the unit block the knockout with an appropriate material field supply Burr Refer to figure 23 1...

Page 14: ...igerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition changes if charged in a gaseous state and normal system operation would no...

Page 15: ...tdoor unit operation status and check for any incorrect wiring 1 Close the outdoor unit s front panel Turn the power on for the outdoor unit and the indoor unit 2 Open the outdoor unit s front panel M...

Page 16: ...place the indoor unit UF The stop valve of outdoor unit is left closed Open the gas side stop valve and the liquid side stop valve If the right indoor unit piping and wiring are not properly con necte...

Page 17: ...he steady state condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjuncti...

Page 18: ...rature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve default automatic mo...

Page 19: ...Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout is controlled by AB...

Page 20: ...h h k h h k 1 6 C 35 F k h h k h k h 4 4 C 40 F k h h k h k k 7 2 C 45 F k h h k k h h 10 C 50 F k h h k k h k Forced heat pump lockout k h h k k k h Heat pump lockout release differential Heat pump...

Page 21: ...rant from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the...

Page 22: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P591321 10E EM22A013A 2208 SP 00_CV_3P591321 10E indd 5 00_CV_3P591321 10E indd 5 2022 08 31 18 52 35 2022 08 31 18 52 35...

Reviews: