background image

3

English

2-1  Standard operation limit

Normal operation

The figures below assume following operating conditions for indoor and 
outdoor units:

Equivalent pipe length

....................................................

25 ft. (7.6 m)

Level difference

 ...................................................................

0 ft. (0 m)

Cooling Heating

67

(19)

57.2
(14)

77

(25)

50

(10)

23(–5)

82.4
(28)

Outdoor temperature °FDB (°CDB)

95(35)

122(50)

Indoor temperature 

°FWB (°CWB)

Rated 

cooling 

capacity

41(5)

–4(–20)

50

(10)

68

(20)

43(6)

80.6

(27)

59

(15)

Outdoor temperature °FWB (°CWB)

60(15.5)

Rated 

heating 

capacity

Indoor temperature 

°FDB (°CDB)

 

Range for operation

 

Range for pull down operation

 

Range for warming up operation

2-2  Standard supplied accessories

Make sure that the accessories shown below are all present.

 

(The accessories can be found behind the front panel.)

Name

Clamp

Conduit mounting plate

Wire clamp 

and screw

Quantity

4 pcs.

2 pcs.

2 pcs.

1 (only 18·24 

type)

Shape

Name

Insulation tube

Installation 

 

manual

Warranty 

 

card

Quantity

1 pc.

1 pc.

1

1

Shape

(Large)

(Small)

(Refer to figure 1)

1. 

Accessories

2. 

Screw for front panel

3. 

Front panel

3.    BEFORE INSTALLATION

<Transporting the Unit>

As shown in figure 2, move the unit slowly. (Take care not to let hands or 
other objects come in contact with rear fins.)

(Refer to figure 2)

1. 

Air outlet grille

2. 

Intake hole

3. 

Corner

4. 

Outdoor unit

5. 

Handle

6. 

Front

7. 

Rear

8. 

Always hold the unit by the corners, as holding it by the side 
intake holes on the casing may cause them to deform.

Use only accessories and parts which are of the designated specifica

-

tion when installing.

4.    SELECTING INSTALLATION SITE

(1)  Select an installation site where the following conditions are 

satisfied and that meets with your customer’s approval.

• 

Places which are well-ventilated.

• 

Places where the unit does not bother next-door neighbors.

• 

A location where small animals will not make nests in the unit.

• 

Safe places which can withstand the unit’s weight and vibration and 
where the unit can be installed level.

• 

A locations where there is enough space to install the unit.

• 

Places where the indoor and outdoor unit’s piping and wiring 
lengths come within the allowable ranges.

• 

A location where there is no risk of flammable gas leaking. 

(2)  If the unit is installed in a location where it might be exposed to 

strong wind, install as per figure 3.

• 

11 mph (5 m/s) or higher winds blown against the outdoor unit’s 
exhaust cause a deterioration in the system performance. High 
winds force re-circulation of the exhaust air into the inlet, which is 
known to cause the following effects:

• 

Reduction in performance.

• 

Increased frost formation in heating mode.

• 

System shut down due to increased pressures.

• 

If very strong wind blows continuously on the air outlet side of the 
outdoor unit, the fan may turn in reverse at high speed and break, 
so install as per figure 3.

(Refer to figure 3)

1. 

Turn the air outlet side toward the building’s wall, fence or 
windbreak screen.

2. 

Air inlet grille

3. 

Ensure there is enough space for installing the unit.

4. 

Set the outlet side at a right angle to the direction of the 
wind.

5. 

Strong wind

6. 

Blown air

(3)  When installing the unit in a place frequently exposed to snow, 

pay special attention to the following:

• 

Install the outdoor unit on a stand (field supply), so that the bottom 
frame is more than 20 in. (500 mm) higher than the expected snow 
fall to prevent it from being covered by snow.

• 

Attach a snow hood (field supply) and a snow vizor (field supply).

• 

Avoid installation at the place where a snowdrift is generated.

• 

Further, perform the following countermeasures, since there is risk 
that the drain water produced at the defrost operation freezes.

• 

Install the outdoor unit so that its bottom place level has a sufficient 
height from foundation level, so that ice does not grow at the lower 
surface of the bottom place of the outdoor unit. (Recommended 
clearance: 20 in. (500 mm) or more)

01_EN_3P591321-10C.indd   3

01_EN_3P591321-10C.indd   3

2022/07/13   13:48:55

2022/07/13   13:48:55

Summary of Contents for RZQ18TBVJUA

Page 1: ...re reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tr...

Page 2: ...ore 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm gure 5 gure 6 1 2 3 4 20 500 or more 4 100 or more 4 100 or more 20 500 or less 20 500 or less 20 500 or more 40 10...

Page 3: ...ore 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 gure 9 gure 10 gure 11 gure 12 inch mm inch mm 4 4 6 5 16 160 6 5 16 160...

Page 4: ...2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 gure 26 gure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate accessory 2 4 2 Lock nut Cover Conduit 5 1 8 2 4 4 2 7 3 6 5 L...

Page 5: ...ne wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explos...

Page 6: ...r or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage b...

Page 7: ...ration and where the unit can be installed level A locations where there is enough space to install the unit Places where the indoor and outdoor unit s piping and wiring lengths come within the allowa...

Page 8: ...to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and on both sides of the unit Refer to figure 5 3...

Page 9: ...sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 foundation bolts M12 or equivalent It is best to screw in the foundation bol...

Page 10: ...rial Jointless phosphor deoxidized copper pipe Thickness Select a thickness for the refrigerant piping which com plies with national and local laws Maximum piping length and height difference between...

Page 11: ...9 16 inch 15 mm Minimum thickness 3 4 inch 20 mm When using commercial copper pipes and fittings observe the following a Insulation of pipes should be done after performing air tight test and vacuum d...

Page 12: ...e a push rod provided charging hose for operation Be sure to tighten the valve cap securely after operation Tightening torque 8 5 10 3 ft lbf 10 8 14 7 N m 7 ELECTRIC WIRING CAUTION To the electrician...

Page 13: ...ut make sure there are no burrs and protect the wiring with protective tape If small animals might enter the unit block the knockout with an appropriate material field supply Burr Refer to figure 23 1...

Page 14: ...igerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition changes if charged in a gaseous state and normal system operation would no...

Page 15: ...tdoor unit operation status and check for any incorrect wiring 1 Close the outdoor unit s front panel Turn the power on for the outdoor unit and the indoor unit 2 Open the outdoor unit s front panel M...

Page 16: ...place the indoor unit UF The stop valve of outdoor unit is left closed Open the gas side stop valve and the liquid side stop valve If the right indoor unit piping and wiring are not properly con necte...

Page 17: ...he steady state condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjuncti...

Page 18: ...rature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve default automatic mo...

Page 19: ...Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout is controlled by AB...

Page 20: ...h h k h h k 1 6 C 35 F k h h k h k h 4 4 C 40 F k h h k h k k 7 2 C 45 F k h h k k h h 10 C 50 F k h h k k h k Forced heat pump lockout k h h k k k h Heat pump lockout release differential Heat pump...

Page 21: ...rant from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the...

Page 22: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P591321 10E EM22A013A 2208 SP 00_CV_3P591321 10E indd 5 00_CV_3P591321 10E indd 5 2022 08 31 18 52 35 2022 08 31 18 52 35...

Reviews: