background image

11

English

(Refer to figure 26)

1. 

R410A Tank (Siphon system)

2. 

Measuring instrument

3. 

Valve A

4. 

Indoor unit

5. 

Stop valve service port

6. 

Gas line stop valve

7. 

Outdoor unit

8. 

Liquid line stop valve

State of valve A and the stop valve

Valve A

Liquid 

line stop 

valve

Gas line 

stop 

valve

Before starting to charge the refrigerant

Close

Close

Close

During charging of the refrigerant

Open

Close

Close

3.  Close valve A after charging is complete.
Note:  If all the refrigerant to be added cannot be charged using the 

above procedure, re-charge the refrigerant as below.

If all the refrigerant could not be added

Add refrigerant referring to the “Service Precautions” plate attached to 
the outdoor unit for details on the settings for adding refrigerant.

9.     POST-WORK  CHECKS

Perform the following checks after work is complete.
(1)  Drain pipe connection, removal of transport bracket 

 

See “

5. PRECAUTIONS ON INSTALLATION

”.

(2)  Incorrect power supply wiring, loose screws 

  

See “

7-3 How to connect the power supply wiring

”.

(3)  Incorrect transmission wiring, loose screws 

  

See “

7-4 Transmission wiring connection procedure

”.

(4)  Incorrect refrigerant piping connections 

  

See “

6. REFRIGERANT PIPING

”.

(5)  Piping sizes, use of insulation 

  

See :  “

6-2 Selecting piping material

”.

 “

6-6 Thermal insulation of piping

”.

(6)  Stop valve check 

  

Make sure both the liquid-side and gas-side stop valves are open.

(7)  Record of Amount of Refrigerant Added 

 

Record it on “Record of Amount of Refrigerant Added” on the “Ser-
vice Precautions” label.

(8)  Measuring the insulation of the main power circuit 

 

• Use a 500V mega-tester. 
• Do not use the mega-tester for low voltage other than 208/230V. 

(Transmission wiring)

 

CAUTION

To the piping installer

After completing installation, be sure to open the valves.
(Operating the unit with the valve shut will break the compressor.)

10.    TEST  OPERATION

This unit is equipped with a crank case heater to ensure smooth 
startup. Be sure to turn the power on at least 6 hours before opera

-

tion in order to have power running to the crank case heater.

 

WARNING

When leaving the unit with the power on, be sure to switch  
with another person doing the installation or close the front  
panel.

Precautions before turning the power on

•  Using insulating sheets, tape electric parts as described in the “Ser-

vice Precautions” label on the back of the front panel.

•  The indoor unit connected to the outdoor unit operates automatically. 

Complete work on the indoor unit in order to ensure maximum safety.

10-1 

Power On–Check Operation

•  Make sure to perform the check operation after installation.  

(If the air conditioner is operated using the indoor remote controller 
without performing the check operation, the malfunction code “U3” is  
displayed in the indoor remote controller, and normal operation is 
disabled.)

•  When making settings on the outdoor unit PC board (A1P or A2P) 

after turning the power on, do not touch anything other than the 
push-button switches and dip switches.  
(See the “Service Precautions” label for the locations of the push-
button switches (BS1-5) and dip switches (DS1-1, 2) on the PC 
board (A1P or A2P).)

•  During the operation, monitor the outdoor unit operation status and 

check for any incorrect wiring.

1. Close the outdoor unit’s front panel.

 

Turn the power

 on for the outdoor 

  unit and the indoor unit.

2.  • Open the outdoor unit’s front panel.

  • Make sure the LED display on the outdoor unit’s PC board (A1P or A2P) is 

      as shown in the following table. 

6. Close the front panel of the outdoor unit after check operation is complete.

Do not leave any stop valve closed 

otherwise the compressor will fail.

Caution

Be sure to turn the power on at least 

6 hours before operation in order to have 

power running to the crank case heater.

To avoid the risk of electric shock, do not touch anything other than the 

push-button switches on the PC board (A1P or A2P) when making settings.

Caution

LED display 
(Default status 
before delivery)

HAP

<30~48 type>

A1P

H1P

H2P

H3P

H4P

H5P

H6P

H7P

LED display 
(Default status 
before delivery)

HAP

<18·24 type>

A2P

A1P

H1P

H2P

H3P

H4P

H5P

H6P

H7P

LED display:     OFF      ON      Blinking

Use caution to avoid electric shock while 

working, since the outdoor unit is on.

•  Only set the push-button switches (BS1-5) 

after making sure the operation pilot lamp on 

PC board is lit up.

•  See the “Service Precautions” label on the 

back side of the front panel for details on how 

to make the settings. 

  (Do not forget to write the settings down on 

the “Service Precautions” label.)

•  The dip switch (DS1-1) does not need to be 

set, so do not touch it. 

  Doing so may cause malfunction.

• If you have to leave the outdoor unit during 

check operation, either switch with another 

worker or close the front panel. 

• The system operates for about 30 minutes 

(60 minutes at maximum) and automatically 

stops the check operation.

• The system can start normal operation about 

3 minutes 

after the check operation if

 the 

remote controller does not display any 

malfunction code.

The remote controller will show the test 

operation display during check operation. 

3.  • When the customer requests

  quiet operation or demand

  operation, make these settings

  using the push-button switches

  (BS1-5) on the outdoor unit’s

  PC board (A1P or A2P).

  • Operate the push-button

  switches through the opening

  after protecting it with an

  insulation cover. 

  (See the “Service Precautions”

  label for details.)

4.  • Check that the liquid and gas-side

  stop valves are open, and if

  they are closed, open them.
5. Press the test operation button 

  (BS4) for at least five seconds and 

  perform check operation. 

 For details, see “How to perform

  check operation” on the “Service

  Precautions” label.

<Precautions During Check Operation>

•   

If operation is performed within 12 minutes of the indoor and 
outdoor units being turned on, H2P will light up, and the com

-

pressor will not run.

 

Only perform operation after checking that the LED display is as 
shown in “

10-1 Power On–Check Operation

” 2. table.

•   In order to ensure uniform refrigerant distribution, it may take up to  

around 10 minutes for the compressor to start up after the unit 
begins running. This is not a malfunction.

•  The check operation cannot be performed in other modes.
•  If the discharge pipe thermistor (R2T), the suction pipe thermistor 

(R3T), and the pressure sensors (S1NPH and S1NPL) are removed 
before operation, the compressor might burn out, so avoid this under 
all circumstances.

01_EN_3P591321-10C.indd   11

01_EN_3P591321-10C.indd   11

2022/08/25   16:03:44

2022/08/25   16:03:44

Summary of Contents for RZQ18TBVJUA

Page 1: ...re reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tr...

Page 2: ...ore 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm gure 5 gure 6 1 2 3 4 20 500 or more 4 100 or more 4 100 or more 20 500 or less 20 500 or less 20 500 or more 40 10...

Page 3: ...ore 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 gure 9 gure 10 gure 11 gure 12 inch mm inch mm 4 4 6 5 16 160 6 5 16 160...

Page 4: ...2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 gure 26 gure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate accessory 2 4 2 Lock nut Cover Conduit 5 1 8 2 4 4 2 7 3 6 5 L...

Page 5: ...ne wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explos...

Page 6: ...r or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage b...

Page 7: ...ration and where the unit can be installed level A locations where there is enough space to install the unit Places where the indoor and outdoor unit s piping and wiring lengths come within the allowa...

Page 8: ...to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and on both sides of the unit Refer to figure 5 3...

Page 9: ...sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 foundation bolts M12 or equivalent It is best to screw in the foundation bol...

Page 10: ...rial Jointless phosphor deoxidized copper pipe Thickness Select a thickness for the refrigerant piping which com plies with national and local laws Maximum piping length and height difference between...

Page 11: ...9 16 inch 15 mm Minimum thickness 3 4 inch 20 mm When using commercial copper pipes and fittings observe the following a Insulation of pipes should be done after performing air tight test and vacuum d...

Page 12: ...e a push rod provided charging hose for operation Be sure to tighten the valve cap securely after operation Tightening torque 8 5 10 3 ft lbf 10 8 14 7 N m 7 ELECTRIC WIRING CAUTION To the electrician...

Page 13: ...ut make sure there are no burrs and protect the wiring with protective tape If small animals might enter the unit block the knockout with an appropriate material field supply Burr Refer to figure 23 1...

Page 14: ...igerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition changes if charged in a gaseous state and normal system operation would no...

Page 15: ...tdoor unit operation status and check for any incorrect wiring 1 Close the outdoor unit s front panel Turn the power on for the outdoor unit and the indoor unit 2 Open the outdoor unit s front panel M...

Page 16: ...place the indoor unit UF The stop valve of outdoor unit is left closed Open the gas side stop valve and the liquid side stop valve If the right indoor unit piping and wiring are not properly con necte...

Page 17: ...he steady state condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjuncti...

Page 18: ...rature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve default automatic mo...

Page 19: ...Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout is controlled by AB...

Page 20: ...h h k h h k 1 6 C 35 F k h h k h k h 4 4 C 40 F k h h k h k k 7 2 C 45 F k h h k k h h 10 C 50 F k h h k k h k Forced heat pump lockout k h h k k k h Heat pump lockout release differential Heat pump...

Page 21: ...rant from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the...

Page 22: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P591321 10E EM22A013A 2208 SP 00_CV_3P591321 10E indd 5 00_CV_3P591321 10E indd 5 2022 08 31 18 52 35 2022 08 31 18 52 35...

Reviews: