background image

17

English

12.   CAUTION FOR REFRIGERANT LEAKS

(Points to note in connection with refrigerant leaks)
Introduction
The installer and system specialist shall secure safety against 
leakage according to local regulations or standards. The following 
standards may be applicable if local regulations are not available.

The SPLIT System, like other air conditioning systems, uses R410A as 
refrigerant. R410A itself is an entirely safe non-toxic, non-combustible 
refrigerant. Nevertheless care must be taken to ensure that air condi-

tioning facilities are installed in a room which is sufficiently large. This 

assures that the maximum concentration level of refrigerant gas is not 
exceeded, in the unlikely event of major leak in the system and this in 
accordance to the local applicable regulations and standards.

Maximum concentration level

The maximum charge of refrigerant and the calculation of the maximum 
concentration of refrigerant is directly related to the humanly occupied 
space in to which it could leak.
The unit of measurement of the concentration is lb./ft

3

 ( the weight in lb. 

of the refrigerant gas in 1ft

3

 volume of the occupied space).

Compliance to the local applicable regulations and standards for the 
maximum allowable concentration level is required.

Direction of the refrigerant flow

Room where 

refrigerant leak has 

occurred (outflow of 

all the refrigerant 

from the system)

Pay a special attention to the place, such as a basement, etc. 
where refrigerant can stay, since refrigerant is heavier than air.
Procedure for checking maximum concentration

Check the maximum concentration level in accordance with steps 1 to 4 
below and take whatever action is necessary to comply.

1. 

Calculate the amount of refrigerant (lb.) charged to each system 
separately.

amount of refriger-

ant in the unit 

(amount of refriger-

ant with which  

the system is 

charged before 

leaving the factory)

+

additional charging 

amount (amount of 

refrigerant added 

locally in accordance 

with the length or 

diameter of the refrig-

erant piping and type 

of indoor unit)

=

total amount 

of refriger-

ant (lb.) in 

the system

NOTE 

•  Where a single refrigerant facility is divided into 2 entirely indepen-

dent refrigerant systems then use the amount of refrigerant with 
which each separate system is charged.

2. 

Calculate a room volume (ft

3

)

3. 

Calculating the refrigerant concentration by using the results of the 
calculations in steps 1 and 2 above.

total amount of refrigerant in the 

refrigerant system

maximum concen-

tration level (lb./ft

3

)

volume (ft

3

) of the room in which 

there is an indoor unit installed

4. 

Dealing with the situations where the result exceeds the maximum 
concentration level. 
Where the installation of a facility results in a concentration in excess 
of the maximum concentration level then it will be necessary to 
revise the system.  
Please consult your dealer.

01_EN_3P591321-10C.indd   17

01_EN_3P591321-10C.indd   17

2022/08/16   20:03:54

2022/08/16   20:03:54

Summary of Contents for RZQ18TBVJUA

Page 1: ...re reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tr...

Page 2: ...ore 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm gure 5 gure 6 1 2 3 4 20 500 or more 4 100 or more 4 100 or more 20 500 or less 20 500 or less 20 500 or more 40 10...

Page 3: ...ore 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 gure 9 gure 10 gure 11 gure 12 inch mm inch mm 4 4 6 5 16 160 6 5 16 160...

Page 4: ...2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 gure 26 gure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate accessory 2 4 2 Lock nut Cover Conduit 5 1 8 2 4 4 2 7 3 6 5 L...

Page 5: ...ne wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explos...

Page 6: ...r or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage b...

Page 7: ...ration and where the unit can be installed level A locations where there is enough space to install the unit Places where the indoor and outdoor unit s piping and wiring lengths come within the allowa...

Page 8: ...to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and on both sides of the unit Refer to figure 5 3...

Page 9: ...sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 foundation bolts M12 or equivalent It is best to screw in the foundation bol...

Page 10: ...rial Jointless phosphor deoxidized copper pipe Thickness Select a thickness for the refrigerant piping which com plies with national and local laws Maximum piping length and height difference between...

Page 11: ...9 16 inch 15 mm Minimum thickness 3 4 inch 20 mm When using commercial copper pipes and fittings observe the following a Insulation of pipes should be done after performing air tight test and vacuum d...

Page 12: ...e a push rod provided charging hose for operation Be sure to tighten the valve cap securely after operation Tightening torque 8 5 10 3 ft lbf 10 8 14 7 N m 7 ELECTRIC WIRING CAUTION To the electrician...

Page 13: ...ut make sure there are no burrs and protect the wiring with protective tape If small animals might enter the unit block the knockout with an appropriate material field supply Burr Refer to figure 23 1...

Page 14: ...igerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition changes if charged in a gaseous state and normal system operation would no...

Page 15: ...tdoor unit operation status and check for any incorrect wiring 1 Close the outdoor unit s front panel Turn the power on for the outdoor unit and the indoor unit 2 Open the outdoor unit s front panel M...

Page 16: ...place the indoor unit UF The stop valve of outdoor unit is left closed Open the gas side stop valve and the liquid side stop valve If the right indoor unit piping and wiring are not properly con necte...

Page 17: ...he steady state condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjuncti...

Page 18: ...rature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve default automatic mo...

Page 19: ...Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout is controlled by AB...

Page 20: ...h h k h h k 1 6 C 35 F k h h k h k h 4 4 C 40 F k h h k h k k 7 2 C 45 F k h h k k h h 10 C 50 F k h h k k h k Forced heat pump lockout k h h k k k h Heat pump lockout release differential Heat pump...

Page 21: ...rant from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the...

Page 22: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P591321 10E EM22A013A 2208 SP 00_CV_3P591321 10E indd 5 00_CV_3P591321 10E indd 5 2022 08 31 18 52 35 2022 08 31 18 52 35...

Reviews: