background image

8

English

(Refer to figure 21)

1. 

Decompression valve

2. 

Nitrogen

3. 

Vacuum pump

4. 

Valve (Open)

5. 

Charge hose

6. 

Stop valve service port

7. 

Indoor unit

8. 

Gas line stop valve (Close)

9. 

Liquid line stop valve (Close)

10. 

Indicates local procurement

11. 

Outdoor unit

NOTE 

The stop valve must always be turned to “closed”. 
Otherwise the refrigerant in the outdoor unit will pour out.

Stop valve operation procedure

Precautions when handling the stop valve

•  The names of parts needed to operate the stop valve are shown in 

the figure below. The unit is shipped from the factory with the stop 

valve turned to the “closed” position.

Servicing port

Valve stem

Flare nut

Valve cap

Field piping connection

•  Since the side boards may be deformed if only a torque wrench is 

used when loosening or tightening flare nuts, always lock the stop 

valve with a wrench and then use a torque wrench.

•   In cases where the unit is run in heating mode when the outside tem-

perature is low or in other situations where the operating pressure 

might drop, seal the gas-side flare nut on the stop valve with silicon 
sealant or the like to prevent it from freezing.

Silicon sealing pad

(Make sure that there is no gap)

Stop valve operation procedure

Have a hex wrench ready (size: 0.2 in. (4 mm) and 0.3 in. (6 mm)).

Opening the valve

1. 

Place the hex wrench on the valve stem and turn counter-clockwise.

2. 

Stop when the valve stem no longer turns. It is now open.

Close the valve

1. 

Place the hex wrench on the valve stem and turn clockwise.

2. 

Stop when the valve stem no longer turns. It is now closed.

Direction to open

Direction to open

<Gas pipe>

<Liquid pipe>

Precautions for handling valve cap

•   A seal is attached to the point indicated by the arrow. 

Take care not to damage it.

Valve cap

Stop valve 
(cap attachment)

•   Be sure to tighten the valve cap securely after operating the valves.

Liquid-side tightening torque

Gas-side tightening torque

10.0 ~ 12.2 ft·lbf

(13.5 ~ 16.5 N·m)

16.6 ~ 20.3 ft·lbf

(22.5 ~ 27.5 N·m)

Precautions for handling servicing port

•  Use a push-rod-provided charging hose for operation.
•  Be sure to tighten the valve cap securely after operation. 

Tightening torque ..................

8.5 ~ 10.3 ft·lbf (10.8 ~ 14.7 N·m)

7. 

  ELECTRIC WIRING

 

CAUTION

To the electrician

• 

Do not operate until refrigerant piping work is completed.

 

(Failure to adhere by this caution may lead to irrepairable com-
pressor damage.)

7-1  Wiring connection example for whole system

• 

Electrical wiring work should be done by a certified professional.

•  Follow the “Wiring diagram” label when carrying out any electrical 

wiring. 

Only proceed with wiring work after turning off all power.

•  Always ground wires in accordance with relevant local and national 

regulations. 

•  Ground the indoor and outdoor units.
•   

Do not connect the ground wire to gas pipes, sewage pipes, lightning 
rods, or telephone ground wires.

• 

Gas pipes:

 can explode or catch fire if there is a gas leak.

• 

 Sewage pipes:

 no grounding effect is possible if hard plastic pip-

ing is used.

• 

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 

grounding.

•  Use copper wire.
• 

When doing the electrical wiring, always shut off the power supply 
before working, and do not turn on the switch until all work is com

-

plete.

• 

This unit has an inverter, so it must be grounded in order to reduce 
noise and prevent it affecting other appliances, and also to release 
any electrical build-up in the unit case due to leaked current.

•  Do not install a power-factor improving phase-advancing capacitor 

under any circumstances. 

(Not only will this not improve the power factor, but it might cause a fire.)

• 

 Connect the wire securely using designated wire and fix it with 

 

attached clamp without applying external pressure on the terminal  

parts (terminal for power supply wiring, terminal for transmission 

wiring and ground terminal). See “

7-3 How to connect the power 

supply wiring

”.

•  Leftover wiring should not be wrapped and stuffed into the unit.
•  Secure the wiring with the included clamp so that it does not come in 

contact with the piping or stop valve.  
(See “

7-3 How to connect the power supply wiring

”.)

01_EN_3P591321-10C.indd   8

01_EN_3P591321-10C.indd   8

2022/08/04   10:39:25

2022/08/04   10:39:25

Summary of Contents for RZQ18TBVJUA

Page 1: ...re reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tr...

Page 2: ...ore 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm gure 5 gure 6 1 2 3 4 20 500 or more 4 100 or more 4 100 or more 20 500 or less 20 500 or less 20 500 or more 40 10...

Page 3: ...ore 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 gure 9 gure 10 gure 11 gure 12 inch mm inch mm 4 4 6 5 16 160 6 5 16 160...

Page 4: ...2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 gure 26 gure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate accessory 2 4 2 Lock nut Cover Conduit 5 1 8 2 4 4 2 7 3 6 5 L...

Page 5: ...ne wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explos...

Page 6: ...r or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage b...

Page 7: ...ration and where the unit can be installed level A locations where there is enough space to install the unit Places where the indoor and outdoor unit s piping and wiring lengths come within the allowa...

Page 8: ...to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and on both sides of the unit Refer to figure 5 3...

Page 9: ...sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 foundation bolts M12 or equivalent It is best to screw in the foundation bol...

Page 10: ...rial Jointless phosphor deoxidized copper pipe Thickness Select a thickness for the refrigerant piping which com plies with national and local laws Maximum piping length and height difference between...

Page 11: ...9 16 inch 15 mm Minimum thickness 3 4 inch 20 mm When using commercial copper pipes and fittings observe the following a Insulation of pipes should be done after performing air tight test and vacuum d...

Page 12: ...e a push rod provided charging hose for operation Be sure to tighten the valve cap securely after operation Tightening torque 8 5 10 3 ft lbf 10 8 14 7 N m 7 ELECTRIC WIRING CAUTION To the electrician...

Page 13: ...ut make sure there are no burrs and protect the wiring with protective tape If small animals might enter the unit block the knockout with an appropriate material field supply Burr Refer to figure 23 1...

Page 14: ...igerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition changes if charged in a gaseous state and normal system operation would no...

Page 15: ...tdoor unit operation status and check for any incorrect wiring 1 Close the outdoor unit s front panel Turn the power on for the outdoor unit and the indoor unit 2 Open the outdoor unit s front panel M...

Page 16: ...place the indoor unit UF The stop valve of outdoor unit is left closed Open the gas side stop valve and the liquid side stop valve If the right indoor unit piping and wiring are not properly con necte...

Page 17: ...he steady state condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjuncti...

Page 18: ...rature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve default automatic mo...

Page 19: ...Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout is controlled by AB...

Page 20: ...h h k h h k 1 6 C 35 F k h h k h k h 4 4 C 40 F k h h k h k k 7 2 C 45 F k h h k k h h 10 C 50 F k h h k k h k Forced heat pump lockout k h h k k k h Heat pump lockout release differential Heat pump...

Page 21: ...rant from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the...

Page 22: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P591321 10E EM22A013A 2208 SP 00_CV_3P591321 10E indd 5 00_CV_3P591321 10E indd 5 2022 08 31 18 52 35 2022 08 31 18 52 35...

Reviews: