12 Operation

Installation and operation manual

27

5TMV1B
VRV IV-S system air conditioner
4P399985-1B – 2015.06

Result: 

The  operation  lamp  goes  out  and  the  system  stops

operating.

NOTICE

Do not turn off power immediately after the unit stops, but
wait for at least 5 minutes.

12.4

Adjusting the air flow direction

Refer to the operation manual of the user interface.

12.4.1

About the air flow flap

Double flow+multi-flow units

Corner units

Ceiling suspended units

Wall-mounted units

For  the  following  conditions,  a  micro  computer  controls  the  air  flow
direction which may be different from the display.

Cooling

Heating

▪ When the room temperature is

lower 

than 

the 

set

temperature.

▪ When starting operation.

▪ When the room temperature is

higher 

than 

the 

set

temperature.

▪ At defrost operation.

▪ When operating continuously at horizontal air flow direction.

▪ When continuous operation with downward air flow is performed

at the time of cooling with a ceiling-suspended or a wall-mounted
unit, the micro computer may control the flow direction, and then
the user interface indication will also change.

The air flow direction can be adjusted in one of the following ways:

▪ The air flow flap itself adjusts its position.

▪ The air flow direction can be fixed by the user.

▪ Automatic 

 and desired position  .

WARNING

Never touch the air outlet or the horizontal blades while the
swing  flap  is  in  operation.  Fingers  may  become  caught  or
the unit may break down.

NOTICE

▪ The  movable  limit  of  the  flap  is  changeable.  Contact

your dealer for details. (only for double-flow, multi-flow,
corner, ceiling-suspended and wall-mounted).

▪ Avoid operating in the horizontal direction 

. It may

cause dew or dust to settle on the ceiling or flap.

12.5

Setting the master user interface

12.5.1

About setting the master user interface

g

d

d

c

c

f

e

b

a

g

f

e

a

VRV IV-S Heat pump outdoor unit

b

Refrigerant piping

c

VRV direct expansion (DX) indoor unit

d

User interface (dedicated depending on indoor unit type)

e

BP box (required to connect Residential Air (RA) or Sky Air
(SA) direct expansion (DX) indoor units)

f

Residential Air (RA) direct expansion (DX) indoor units

g

User interface (wireless, dedicated depending on indoor
unit type)

When  the  system  is  installed  as  shown  in  the  figure  above,  it  is
necessary to designate one of the user interfaces as the master user
interface.

The  displays  of  slave  user  interfaces  show 

  (change-over

under  centralised  control)  and  slave  user  interfaces  automatically
follow the operation mode directed by the master user interface.

Only the master user interface can select heating or cooling mode.

12.5.2

To designate the master user interface
(VRV DX)

In  case  only  VRV  DX  indoor  units  are  connected  to  the  VRV  IV-S
system:

1

Press the operation mode selector button of the current master
user interface for 4 seconds. In case this procedure was not yet
performed,  the  procedure  can  be  executed  on  the  first  user
interface operated.

Result: 

The  display  showing 

  (change-over  under

centralised control) of all slave user interfaces connected to the
same outdoor unit flashes.

2

Press  the  operation  mode  selector  button  of  the  controller  that
you wish to designate as the master user interface.

Result: 

Designation  is  completed.  This  user  interface  is

designated  as  the  master  user  interface  and  the  display
showing 

  (change-over  under  centralised  control)

vanishes.  The  displays  of  other  user  interfaces  show 
(change-over under centralised control).

12.5.3

To designate the master user interface
(RA DX)

In  case  only  RA  DX  indoor  units  are  connected  to  the  VRV  IV-S
system

:

1

Stop all indoor units.

2

When the system is not operating (all indoor units thermo OFF),
you can define the master RA DX indoor unit by addressing that
unit  with  infrared  user  interface  (instruct  thermo  ON  in  desired
mode).

The only way to change the master unit is by repeating the previous
procedure.  A  cool/heat  switchover  (or  opposite)  is  only  possible  by
changing the operation mode of the defined master indoor unit.

Summary of Contents for RXYSCQ4TMV1B

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...sete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti...

Page 4: ...settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 16 6 1 6 To use m...

Page 5: ...nit Outdoor unit installation and operation manual Installation and operation instructions Installer and user reference guide Preparation of the installation technical specifications reference data De...

Page 6: ...eep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warming up operation range b Operation range TAI Ambien...

Page 7: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6 2 To determine the additional refrigerant amount on page 12 A Piping...

Page 8: ...wer supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage protector in accordance with the applicable legislation Selection an...

Page 9: ...es dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 5 2 4 To prevent the outdoor unit from falling over Connect cables field supply as shown 4 5 3 Connecting the refrigerant pi...

Page 10: ...the service cover and the piping intake plate 6 Seal all gaps example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be u...

Page 11: ...be leak and vacuum tested Keep any possible field supplied field piping valves open as well Refer to the indoor unit installation manual for more details Leak test and vacuum drying should be done be...

Page 12: ...shed in a correct way between outdoor unit s and indoor units NOTICE Before starting charging procedures check if the 7 LEDs display is as normal see 6 1 4 To access mode 1 or 2 on page 16 and there i...

Page 13: ...valves At this point valve A must remain closed 7 Take all the precautions mentioned in 6 Configuration on page 15 and 7 Commissioning on page 20 into account 8 Turn on the power of the indoor units...

Page 14: ...to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when co...

Page 15: ...ed as applicable DANGER RISK OF ELECTROCUTION 6 1 Making field settings 6 1 1 About making field settings To configure the heat pump system you must give input to the outdoor unit s main PCB A1P This...

Page 16: ...ON the display goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have...

Page 17: ...he unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable...

Page 18: ...uto 46 C 43 C 2 12 Enable the low noise function and or power consumption limitation via external control adaptor DTA104A61 62 If the system needs to be running under low noise operation or under powe...

Page 19: ...efault Level 2 Level 3 2 26 Low noise operation start time This setting is used in conjunction with setting 2 22 20h00 default 22h00 24h00 2 27 Low noise operation stop time This setting is used in co...

Page 20: ...s Once all below checks are fulfilled the unit must be closed only then can the unit be powered up You read the complete installation and operation instructions as described in the installer and user...

Page 21: ...ud and the display indication may change These are not malfunctions 7 3 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 6 1 Making field settings on page 15...

Page 22: ...correctly Recalculate the required amount of refrigerant from the piping length and add an adequate amount of refrigerant Refrigerant overcharge Recalculate the required amount of refrigerant from th...

Page 23: ...the side is not possible Single unit Single row of units See figure 1 on the inside of the front cover A B C D Obstacles walls baffle plates E Obstacle roof a b c d e Minimum service space between the...

Page 24: ...pipe S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch Y1E Electronic expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way v...

Page 25: ...expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way valve Z1C Z7C Noise filter ferrite core Z1F Z5F Noise filter For the user 10 About the system The in...

Page 26: ...1 minute after the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 12 2 3 About the heating ope...

Page 27: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Page 28: ...and details of the defect WARNING Do not modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your deal...

Page 29: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Page 30: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Page 31: ...tem When another unit is running some refrigerant will still flow through the unit 15 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requires technical expert...

Page 32: ...4P399985 1 B 0000000E 4P399985 1B 2015 06 Copyright 2015 Daikin...