background image

5 Installation

Installation and operation manual

10

5TMV1B

VRV IV-S system air conditioner

4P399985-1B – 2015.06

To handle the service port

▪ Always  use  a  charge  hose  equipped  with  a  valve  depressor  pin,

since the service port is a Schrader type valve.

▪ After  handling  the  service  port,  make  sure  to  tighten  the  service

port  cover  securely.  For  the  tightening  torque,  refer  to  the  table
below.

▪ Check for refrigerant leaks after tightening the service port cover.

Tightening torques

Stop valve

size (mm)

Tightening torque N•m (turn clockwise to close)

Shaft

Valve body Hexagonal

wrench

Cap (valve

lid)

Service

port

Ø9.5

5.4~6.6

4 mm

13.5~16.5

11.5~13.9

Ø15.9

13.5~16.5

6 mm

22.5~27.5

5.3.2

To connect the refrigerant piping to the
outdoor unit

NOTICE

Be sure that the field installed piping does not touch other
pipes,  the  bottom  panel  or  side  panel.  Especially  for  the
bottom  and  side  connection,  be  sure  to  protect  the  piping
with  suitable  insulation,  to  prevent  it  from  coming  into
contact with the casing.

1

Do the following:

▪ Remove  the  service  cover.  See 

"5.1.1  To  open  the  outdoor

unit" on page 8

.

▪ Remove the piping intake plate (a) with screw (b).

a

b

2

Choose a piping route (a, b or c).

a

b

c

3

If you have chosen the downwards piping route:

▪ Drill (a, 4×) and remove the knockout hole (b).
▪ Cut out the slits (c) with a metal saw.

c

c

b

a

4× Ø6 mm

4

Do the following:

▪ Connect the liquid pipe (a) to the liquid stop valve.
▪ Connect the gas pipe (b) to the gas stop valve.

a

b

5

Reattach the service cover and the piping intake plate.

6

Seal  all  gaps  (example:  a)  to  prevent  snow  and  small  animals
from entering the system.

a

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

5.4

Checking the refrigerant piping

5.4.1

About checking the refrigerant piping

Refrigerant piping works are 

finished?

The indoor units and/or 

outdoor unit were already 

powered ON?

Use procedure:
"Method 2: After power ON".

Finish piping work.

Use procedure:
"Method 1: Before power ON 

(regular method)".

Yes

No

No

Yes

It is very important that all refrigerant piping work is done before the
units (outdoor or indoor) are powered on.

When the units are powered on, the expansion valves will initialise.
This means that they will close. Leak test and vacuum drying of field
piping and indoor units is impossible when this happens.

Therefore,  there  will  be  explained  2  methods  for  initial  installation,
leak test and vacuum drying.

Method 1: Before power ON

If  the  system  has  not  yet  been  powered  on,  no  special  action  is
required to perform the leak test and the vacuum drying.

Method 2: After power ON

If  the  system  has  already  been  powered  on,  activate  setting  [2‑21]
(refer  to 

"6.1.4  To  access  mode  1  or  2"  on  page  16

).  This  setting

will  open  field  expansion  valves  to  guarantee  a  R410A  piping
pathway  and  make  it  possible  to  perform  the  leak  test  and  the
vacuum drying.

Summary of Contents for RXYSCQ4TMV1B

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...sete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti...

Page 4: ...settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 16 6 1 6 To use m...

Page 5: ...nit Outdoor unit installation and operation manual Installation and operation instructions Installer and user reference guide Preparation of the installation technical specifications reference data De...

Page 6: ...eep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warming up operation range b Operation range TAI Ambien...

Page 7: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6 2 To determine the additional refrigerant amount on page 12 A Piping...

Page 8: ...wer supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage protector in accordance with the applicable legislation Selection an...

Page 9: ...es dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 5 2 4 To prevent the outdoor unit from falling over Connect cables field supply as shown 4 5 3 Connecting the refrigerant pi...

Page 10: ...the service cover and the piping intake plate 6 Seal all gaps example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be u...

Page 11: ...be leak and vacuum tested Keep any possible field supplied field piping valves open as well Refer to the indoor unit installation manual for more details Leak test and vacuum drying should be done be...

Page 12: ...shed in a correct way between outdoor unit s and indoor units NOTICE Before starting charging procedures check if the 7 LEDs display is as normal see 6 1 4 To access mode 1 or 2 on page 16 and there i...

Page 13: ...valves At this point valve A must remain closed 7 Take all the precautions mentioned in 6 Configuration on page 15 and 7 Commissioning on page 20 into account 8 Turn on the power of the indoor units...

Page 14: ...to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when co...

Page 15: ...ed as applicable DANGER RISK OF ELECTROCUTION 6 1 Making field settings 6 1 1 About making field settings To configure the heat pump system you must give input to the outdoor unit s main PCB A1P This...

Page 16: ...ON the display goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have...

Page 17: ...he unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable...

Page 18: ...uto 46 C 43 C 2 12 Enable the low noise function and or power consumption limitation via external control adaptor DTA104A61 62 If the system needs to be running under low noise operation or under powe...

Page 19: ...efault Level 2 Level 3 2 26 Low noise operation start time This setting is used in conjunction with setting 2 22 20h00 default 22h00 24h00 2 27 Low noise operation stop time This setting is used in co...

Page 20: ...s Once all below checks are fulfilled the unit must be closed only then can the unit be powered up You read the complete installation and operation instructions as described in the installer and user...

Page 21: ...ud and the display indication may change These are not malfunctions 7 3 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 6 1 Making field settings on page 15...

Page 22: ...correctly Recalculate the required amount of refrigerant from the piping length and add an adequate amount of refrigerant Refrigerant overcharge Recalculate the required amount of refrigerant from th...

Page 23: ...the side is not possible Single unit Single row of units See figure 1 on the inside of the front cover A B C D Obstacles walls baffle plates E Obstacle roof a b c d e Minimum service space between the...

Page 24: ...pipe S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch Y1E Electronic expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way v...

Page 25: ...expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way valve Z1C Z7C Noise filter ferrite core Z1F Z5F Noise filter For the user 10 About the system The in...

Page 26: ...1 minute after the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 12 2 3 About the heating ope...

Page 27: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Page 28: ...and details of the defect WARNING Do not modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your deal...

Page 29: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Page 30: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Page 31: ...tem When another unit is running some refrigerant will still flow through the unit 15 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requires technical expert...

Page 32: ...4P399985 1 B 0000000E 4P399985 1B 2015 06 Copyright 2015 Daikin...

Reviews: