background image

4 Preparation

Installation and operation manual

7

5TMV1B
VRV IV-S system air conditioner
4P399985-1B – 2015.06

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

9.5 mm (3/8")

12.7 mm (1/2")

Annealed (O)

≥0.80 mm

t

Ø

15.9 mm (5/8")

Annealed (O)

≥0.99 mm

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

Flare connections:

 Only use annealed material.

4.2.3

To select the piping size

Determine the proper size referring to following tables and reference
figure (only for indication).

INFORMATION

▪ Combination of VRV DX and RA DX indoor units is not

allowed.

▪ Combination  of  RA  DX  and  AHU  indoor  units  is  not

allowed.

▪ Combination of RA DX and aircurtain indoor units is not

allowed.

INFORMATION

If  you  install  RA  DX  indoor  units,  you  have  to  configure
field  setting  [2‑38]  (=  type  of  installed  indoor  units).  See

"6.1.8 Mode 2: Field settings" on page 18

.

A

B-1

B-2

C-1

C-2

C-3

C-4

E

E

E

E

1

1

3-1

3-2

3-3

3-4

A

D

RA DX

VRV DX

D

4

4

5

5

5

5

2

2

2

2

1

Outdoor unit

2

Refrigerant branch kits

3-1~3-4

VRV DX indoor units

4

BP units

5

RA DX indoor units

A

Piping between outdoor unit and (first) refrigerant branch
kit

B-1 B-2

Piping between refrigerant branch kits

C-1~C-4

Piping between refrigerant branch kit and indoor unit

D

Piping between refrigerant branch kit and BP unit

E

Piping between BP unit and RA DX indoor unit

In  case  the  required  pipe  sizes  (inch  sizes)  are  not  available,  it  is
also allowed to use other diameters (mm sizes), taken the following
into account:

▪ Select the pipe size nearest to the required size.

▪ Use  the  suitable  adapters  for  the  change-over  from  inch  to  mm

pipes (field supply).

▪ The  additional  refrigerant  calculation  has  to  be  adjusted  as

mentioned  in 

"5.6.2  To  determine  the  additional  refrigerant

amount" on page 12

.

A: Piping between outdoor unit and (first)
refrigerant branch kit

When the equivalent pipe length between outdoor and indoor units is
90 m or more, the size of the main gas pipe must be increased (size-
up).  If  the  recommended  gas  pipe  (size-up)  is  not  available,  you
must  use  the  standard  size  (which  might  result  in  a  small  capacity
decrease).

a

e

b

c

d

a

Outdoor unit

b

Main gas pipe

c

Increase

d

First refrigerant branch kit

e

Indoor unit

Outdoor unit

capacity type (HP)

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

Standard

Size-up

4+5

15.9

19.1

9.5

B: Piping between refrigerant branch kits

Choose  from  the  following  table  in  accordance  with  the  indoor  unit
total  capacity  type,  connected  downstream.  Do  not  let  the
connection  piping  exceed  the  refrigerant  piping  size  chosen  by  the
general system model name.

Indoor unit capacity

index

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

<150

15.9

9.5

150≤x≤162.5

19.1

Example: 

Downstream capacity for B-1 = capacity index of unit 3-1

+ capacity index of unit 3-2

C: Piping between refrigerant branch kit and
indoor unit

Use  the  same  diameters  as  the  connections  (liquid,  gas)  on  the
indoor units. The diameters of the indoor units are as follows:

Indoor unit capacity

index

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

15~50

12.7

6.4

63~140

15.9

9.5

D: Piping between refrigerant branch kit and BP
unit

Total capacity index
of connected indoor

units

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

15~62

12.7

6.4

63~149

15.9

9.5

E: Piping between BP unit and RA DX indoor unit

Indoor unit capacity

index

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

15~42

9.5

6.4

50

12.7

60

9.5

71

15.9

Summary of Contents for RXYSCQ4TMV1B

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...sete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti...

Page 4: ...settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 16 6 1 6 To use m...

Page 5: ...nit Outdoor unit installation and operation manual Installation and operation instructions Installer and user reference guide Preparation of the installation technical specifications reference data De...

Page 6: ...eep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warming up operation range b Operation range TAI Ambien...

Page 7: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6 2 To determine the additional refrigerant amount on page 12 A Piping...

Page 8: ...wer supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage protector in accordance with the applicable legislation Selection an...

Page 9: ...es dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 5 2 4 To prevent the outdoor unit from falling over Connect cables field supply as shown 4 5 3 Connecting the refrigerant pi...

Page 10: ...the service cover and the piping intake plate 6 Seal all gaps example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be u...

Page 11: ...be leak and vacuum tested Keep any possible field supplied field piping valves open as well Refer to the indoor unit installation manual for more details Leak test and vacuum drying should be done be...

Page 12: ...shed in a correct way between outdoor unit s and indoor units NOTICE Before starting charging procedures check if the 7 LEDs display is as normal see 6 1 4 To access mode 1 or 2 on page 16 and there i...

Page 13: ...valves At this point valve A must remain closed 7 Take all the precautions mentioned in 6 Configuration on page 15 and 7 Commissioning on page 20 into account 8 Turn on the power of the indoor units...

Page 14: ...to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when co...

Page 15: ...ed as applicable DANGER RISK OF ELECTROCUTION 6 1 Making field settings 6 1 1 About making field settings To configure the heat pump system you must give input to the outdoor unit s main PCB A1P This...

Page 16: ...ON the display goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have...

Page 17: ...he unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable...

Page 18: ...uto 46 C 43 C 2 12 Enable the low noise function and or power consumption limitation via external control adaptor DTA104A61 62 If the system needs to be running under low noise operation or under powe...

Page 19: ...efault Level 2 Level 3 2 26 Low noise operation start time This setting is used in conjunction with setting 2 22 20h00 default 22h00 24h00 2 27 Low noise operation stop time This setting is used in co...

Page 20: ...s Once all below checks are fulfilled the unit must be closed only then can the unit be powered up You read the complete installation and operation instructions as described in the installer and user...

Page 21: ...ud and the display indication may change These are not malfunctions 7 3 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 6 1 Making field settings on page 15...

Page 22: ...correctly Recalculate the required amount of refrigerant from the piping length and add an adequate amount of refrigerant Refrigerant overcharge Recalculate the required amount of refrigerant from th...

Page 23: ...the side is not possible Single unit Single row of units See figure 1 on the inside of the front cover A B C D Obstacles walls baffle plates E Obstacle roof a b c d e Minimum service space between the...

Page 24: ...pipe S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch Y1E Electronic expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way v...

Page 25: ...expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way valve Z1C Z7C Noise filter ferrite core Z1F Z5F Noise filter For the user 10 About the system The in...

Page 26: ...1 minute after the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 12 2 3 About the heating ope...

Page 27: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Page 28: ...and details of the defect WARNING Do not modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your deal...

Page 29: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Page 30: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Page 31: ...tem When another unit is running some refrigerant will still flow through the unit 15 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requires technical expert...

Page 32: ...4P399985 1 B 0000000E 4P399985 1B 2015 06 Copyright 2015 Daikin...

Reviews: