5 Installation

Installation and operation manual

13

5TMV1B
VRV IV-S system air conditioner
4P399985-1B – 2015.06

p< p>

R410A

N2

C

b

c

e

a

g

f

d

A

B

a

Pressure reducing valve

b

Nitrogen

c

Weighing scales

d

Refrigerant R410A tank (siphon system)

e

Vacuum pump

f

Liquid line stop valve

g

Gas line stop valve

A

Valve A

B

Valve B

C

Valve C

2

Open valves C and B.

3

Pre‑charge refrigerant until the determined additional refrigerant
amount is reached or pre‑charging is not possible anymore, and
then close valves C and B.

4

Do one of the following:

If

Then

The determined additional
refrigerant amount is 

reached

Disconnect the manifold from
the liquid line.

You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.

Too much

 refrigerant is

charged

Recover refrigerant.

Disconnect the manifold from
the liquid line.

You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.

The determined additional
refrigerant amount is 

not

reached

 yet

Disconnect the manifold from
the liquid line.

Continue with the "Charging
refrigerant (in manual
additional refrigerant charge
mode)" instructions.

Charging refrigerant (in manual additional refrigerant charge
mode)

The  remaining  additional  refrigerant  charge  can  be  charged  by
operating  the  outdoor  unit  by  means  of  the  manual  additional
refrigerant charge mode.

5

Connect as shown. Make sure valve A is closed.

p< p>

R410A

a

c

d

b

A

d

a

Weighing scales

b

Refrigerant R410A tank (siphon system)

c

Vacuum pump

d

Refrigerant charge port

A

Valve A

NOTICE

The  refrigerant  charging  port  is  connected  to  the  piping
inside  the  unit.  The  unit's  internal  piping  is  already  factory
charged  with  refrigerant,  so  be  careful  when  connecting
the charge hose.

6

Open  all  outdoor  unit  stop  valves.  At  this  point,  valve  A  must
remain closed!

7

Take  all  the  precautions  mentioned  in 

"6  Configuration"  on

page 15

 and 

"7 Commissioning" on page 20

 into account.

8

Turn on the power of the indoor units and outdoor unit.

9

Activate  setting  [2‑20]  to  start  the  manual  additional  refrigerant
charge mode. For details, see 

"6.1.8 Mode 2: Field settings" on

page 18

.

Result: 

The unit will start operation.

INFORMATION

The manual refrigerant charge operation will automatically
stop  within  30  minutes.  If  charging  is  not  completed  after
30  minutes,  perform  the  additional  refrigerant  charging
operation again.

INFORMATION

▪ When  a  malfunction  is  detected  during  the  procedure

(e.g., in case of closed stop valve), a malfunction code
will  be  displayed.  In  that  case,  refer  to 

"5.6.4  Error

codes  when  charging  refrigerant"  on  page  13

  and

solve  the  malfunction  accordingly.  Resetting  the
malfunction  can  be  done  by  pushing  BS3.  You  can
restart the "Charging" instructions.

▪ Aborting  the  manual  refrigerant  charge  is  possible  by

pushing  BS3.  The  unit  will  stop  and  return  to  idle
condition.

10

Open valve A.

11

Charge  refrigerant  until  the  remaining  determined  additional
refrigerant amount is added, and then close valve A.

12

Press  BS3  to  stop  the  manual  additional  refrigerant  charge
mode.

NOTICE

Make sure to open all stop valves after (pre-) charging the
refrigerant.

Operating  with  the  stop  valves  closed  will  damage  the
compressor.

NOTICE

After adding the refrigerant, do not forget to close the lid of
the  refrigerant  charging  port.  The  tightening  torque  for  the
lid is 11.5 to 13.9 N•m.

5.6.4

Error codes when charging refrigerant

INFORMATION

If a malfunction occurs, the error code is displayed on the
user interface of the indoor unit.

If  a  malfunction  occurs,  close  valve  A  immediately.  Confirm  the
malfunction  code  and  take  corresponding  action, 

"8.1  Solving

problems based on error codes" on page 22

.

5.6.5

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

c

b

a

a

Factory refrigerant charge: see unit name plate

Summary of Contents for RXYSCQ4TMV1B

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...sete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti...

Page 4: ...settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 16 6 1 6 To use m...

Page 5: ...nit Outdoor unit installation and operation manual Installation and operation instructions Installer and user reference guide Preparation of the installation technical specifications reference data De...

Page 6: ...eep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warming up operation range b Operation range TAI Ambien...

Page 7: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6 2 To determine the additional refrigerant amount on page 12 A Piping...

Page 8: ...wer supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage protector in accordance with the applicable legislation Selection an...

Page 9: ...es dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 5 2 4 To prevent the outdoor unit from falling over Connect cables field supply as shown 4 5 3 Connecting the refrigerant pi...

Page 10: ...the service cover and the piping intake plate 6 Seal all gaps example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be u...

Page 11: ...be leak and vacuum tested Keep any possible field supplied field piping valves open as well Refer to the indoor unit installation manual for more details Leak test and vacuum drying should be done be...

Page 12: ...shed in a correct way between outdoor unit s and indoor units NOTICE Before starting charging procedures check if the 7 LEDs display is as normal see 6 1 4 To access mode 1 or 2 on page 16 and there i...

Page 13: ...valves At this point valve A must remain closed 7 Take all the precautions mentioned in 6 Configuration on page 15 and 7 Commissioning on page 20 into account 8 Turn on the power of the indoor units...

Page 14: ...to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when co...

Page 15: ...ed as applicable DANGER RISK OF ELECTROCUTION 6 1 Making field settings 6 1 1 About making field settings To configure the heat pump system you must give input to the outdoor unit s main PCB A1P This...

Page 16: ...ON the display goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have...

Page 17: ...he unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable...

Page 18: ...uto 46 C 43 C 2 12 Enable the low noise function and or power consumption limitation via external control adaptor DTA104A61 62 If the system needs to be running under low noise operation or under powe...

Page 19: ...efault Level 2 Level 3 2 26 Low noise operation start time This setting is used in conjunction with setting 2 22 20h00 default 22h00 24h00 2 27 Low noise operation stop time This setting is used in co...

Page 20: ...s Once all below checks are fulfilled the unit must be closed only then can the unit be powered up You read the complete installation and operation instructions as described in the installer and user...

Page 21: ...ud and the display indication may change These are not malfunctions 7 3 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 6 1 Making field settings on page 15...

Page 22: ...correctly Recalculate the required amount of refrigerant from the piping length and add an adequate amount of refrigerant Refrigerant overcharge Recalculate the required amount of refrigerant from th...

Page 23: ...the side is not possible Single unit Single row of units See figure 1 on the inside of the front cover A B C D Obstacles walls baffle plates E Obstacle roof a b c d e Minimum service space between the...

Page 24: ...pipe S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch Y1E Electronic expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way v...

Page 25: ...expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way valve Z1C Z7C Noise filter ferrite core Z1F Z5F Noise filter For the user 10 About the system The in...

Page 26: ...1 minute after the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 12 2 3 About the heating ope...

Page 27: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Page 28: ...and details of the defect WARNING Do not modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your deal...

Page 29: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Page 30: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Page 31: ...tem When another unit is running some refrigerant will still flow through the unit 15 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requires technical expert...

Page 32: ...4P399985 1 B 0000000E 4P399985 1B 2015 06 Copyright 2015 Daikin...

Reviews: