6 Configuration

Installation and operation manual

16

5TMV1B

VRV IV-S system air conditioner

4P399985-1B – 2015.06

6.1.2

To access the field setting components

See 

"5.1.1 To open the outdoor unit" on page 8

.

6.1.3

Field setting components

NOTICE

The DIP switch (DS1 on A1P) is not used. Do NOT change
the factory setting.

The components to make field settings are as follows:

A1P

X1M

X2M

BS2

SET

BS1

MODE

BS3

RETURN

BS4

TEST

BS5

RESET

H1P

H2P

H3P

H4P

H5P

H6P

H7P

MODE

TEST:

L.N.O.P. DEMAND

C/H SELECT

HWL:

IND

MASTER SLAVE

H8P

MULTI

BS1~BS5

Push buttons

H1P~H7P

7‑LEDs display

H8P

LED for indication during initialisation
ON (

) OFF ( ) Flashing (

)

Push buttons

Use  the  push  buttons  to  make  the  field  settings.  Operate  the  push
buttons  with  an  insulated  stick  (such  as  a  closed  ball-point  pen)  to
avoid touching of live parts.

BS1

MODE: For changing the set mode

BS2

SET: For field setting

BS3

RETURN: For field setting

BS4

TEST: For test operation

BS5

RESET: For resetting the address when the wiring is
changed or when an additional indoor unit is installed

7‑LEDs display

The  display  gives  feedback  about  the  field  settings,  which  are
defined as [Mode-Setting]=Value.

H1P

Shows the mode

H2P~H7P

Shows the settings and values, represented in binary code

Example: 

H1P H2P H3P H4P H5P H6P H7P

-

+

+

+

+

+

[

H1P

32 16

8

4

2

1]

Description

(H1P OFF)

Default situation

(H1P flashing)

Mode 1

(H1P ON)

Mode 2

+

+

+

+

+

0

0

8

0

0

0

(H2P~H7P = binary 8)

Setting 8

(in mode 2)

+

+

+

+

+

0

0

0

4

0

0

(H2P~H7P = binary 4)

Value 4

(in mode 2)

6.1.4

To access mode 1 or 2

After  the  units  are  turned  ON,  the  display  goes  to  its  default
situation. From there, you can access mode 1 and mode 2.

Initialisation: default situation

NOTICE

Be  sure  to  turn  on  the  power  6  hours  before  operation  in
order  to  have  power  running  to  the  crankcase  heater  and
to protect the compressor.

Turn  on  the  power  supply  of  the  outdoor  unit  and  all  indoor  units.
When  the  communication  between  indoor  units  and  outdoor  unit  is
established and normal, the display indication state will be as below
(default situation when shipped from factory).

10~12 min

b
c

a

a

Power ON

b

Default situation

c

LED indication when there is a malfunction

If  the  default  situation  is  not  displayed  after  10~12  minutes,  check
the  malfunction  code  on  the  indoor  unit  user  interface.  Solve  the
malfunction code accordingly. First, check the communication wiring.

Switching between modes

Use  BS1  to  switch  between  the  default  situation,  mode  1  and
mode 2.

BS1 [5 s]

BS1

BS1

BS1

a

c

b

a

Default situation (H1P OFF)

b

Mode 1 (H1P flashing)

c

Mode 2 (H1P ON)

BS1

Press BS1.

BS1 [5 s]

Press BS1 for at least 5 s.

INFORMATION

If you get confused in the middle of the process, press BS1
to return to the default situation.

6.1.5

To use mode 1

In  mode  1  (and  in  default  situation)  you  can  read  out  some
information.

Example: 7‑LEDs display – Default situation

You can read out the status of low noise operation as follows:

#

Action

Button/display

1

Make sure the LEDs are
showing the default situation.

(H1P OFF)

2

Check the status of LED
H6P.

H6P OFF: Unit is currently
not operating under low noise
restrictions.

H6P ON: Unit is currently
operating under low noise
restrictions.

Example: 7‑LEDs display – Mode 1

You  can  read  out  setting  [1‑5]  (=  the  total  number  of  connected
indoor units) as follows:

Summary of Contents for RXYSCQ4TMV1B

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...sete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti...

Page 4: ...settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 16 6 1 6 To use m...

Page 5: ...nit Outdoor unit installation and operation manual Installation and operation instructions Installer and user reference guide Preparation of the installation technical specifications reference data De...

Page 6: ...eep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warming up operation range b Operation range TAI Ambien...

Page 7: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6 2 To determine the additional refrigerant amount on page 12 A Piping...

Page 8: ...wer supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage protector in accordance with the applicable legislation Selection an...

Page 9: ...es dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 5 2 4 To prevent the outdoor unit from falling over Connect cables field supply as shown 4 5 3 Connecting the refrigerant pi...

Page 10: ...the service cover and the piping intake plate 6 Seal all gaps example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be u...

Page 11: ...be leak and vacuum tested Keep any possible field supplied field piping valves open as well Refer to the indoor unit installation manual for more details Leak test and vacuum drying should be done be...

Page 12: ...shed in a correct way between outdoor unit s and indoor units NOTICE Before starting charging procedures check if the 7 LEDs display is as normal see 6 1 4 To access mode 1 or 2 on page 16 and there i...

Page 13: ...valves At this point valve A must remain closed 7 Take all the precautions mentioned in 6 Configuration on page 15 and 7 Commissioning on page 20 into account 8 Turn on the power of the indoor units...

Page 14: ...to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when co...

Page 15: ...ed as applicable DANGER RISK OF ELECTROCUTION 6 1 Making field settings 6 1 1 About making field settings To configure the heat pump system you must give input to the outdoor unit s main PCB A1P This...

Page 16: ...ON the display goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have...

Page 17: ...he unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable...

Page 18: ...uto 46 C 43 C 2 12 Enable the low noise function and or power consumption limitation via external control adaptor DTA104A61 62 If the system needs to be running under low noise operation or under powe...

Page 19: ...efault Level 2 Level 3 2 26 Low noise operation start time This setting is used in conjunction with setting 2 22 20h00 default 22h00 24h00 2 27 Low noise operation stop time This setting is used in co...

Page 20: ...s Once all below checks are fulfilled the unit must be closed only then can the unit be powered up You read the complete installation and operation instructions as described in the installer and user...

Page 21: ...ud and the display indication may change These are not malfunctions 7 3 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 6 1 Making field settings on page 15...

Page 22: ...correctly Recalculate the required amount of refrigerant from the piping length and add an adequate amount of refrigerant Refrigerant overcharge Recalculate the required amount of refrigerant from th...

Page 23: ...the side is not possible Single unit Single row of units See figure 1 on the inside of the front cover A B C D Obstacles walls baffle plates E Obstacle roof a b c d e Minimum service space between the...

Page 24: ...pipe S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch Y1E Electronic expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way v...

Page 25: ...expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way valve Z1C Z7C Noise filter ferrite core Z1F Z5F Noise filter For the user 10 About the system The in...

Page 26: ...1 minute after the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 12 2 3 About the heating ope...

Page 27: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Page 28: ...and details of the defect WARNING Do not modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your deal...

Page 29: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Page 30: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Page 31: ...tem When another unit is running some refrigerant will still flow through the unit 15 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requires technical expert...

Page 32: ...4P399985 1 B 0000000E 4P399985 1B 2015 06 Copyright 2015 Daikin...

Reviews: