background image

5 Installation

Installation and operation manual

12

5TMV1B

VRV IV-S system air conditioner

4P399985-1B – 2015.06

5.5

To insulate the refrigerant piping

After  finishing  the  leak  test  and  vacuum  drying,  the  piping  must  be
insulated. Take into account the following points:

▪ Make sure to insulate the connection piping and refrigerant branch

kits entirely.

▪ Be sure to insulate the liquid and gas piping (for all units).

▪ Use  heat  resistant  polyethylene  foam  which  can  withstand  a

temperature of 70°C for liquid piping and polyethylene foam which
can withstand a temperature of 120°C for gas piping.

▪ Reinforce the insulation on the refrigerant piping according to the

installation environment.

Ambient

temperature

Humidity

Minimum thickness

≤30°C

75% to 80% RH

15 mm

>30°C

≥80% RH

20 mm

Condensation might form on the surface of the insulation.

▪ If  there  is  a  possibility  that  condensation  on  the  stop  valve  might

drip  down  into  the  indoor  unit  through  gaps  in  the  insulation  and
piping  because  the  outdoor  unit  is  located  higher  than  the  indoor
unit,  this  must  be  prevented  by  sealing  up  the  connections.  See
below figure.

b

a

a

Insulation material

b

Caulking etc.

5.6

Charging refrigerant

5.6.1

Precautions when charging refrigerant

WARNING

▪ Only use R410A as refrigerant. Other substances may

cause explosions and accidents.

▪ R410A  contains  fluorinated  greenhouse  gases.  Its

global warming potential value is 2087.5. Do NOT vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  always  use  protective

gloves and safety glasses.

NOTICE

If  the  power  of  some  units  is  turned  off,  the  charging
procedure cannot be finished properly.

NOTICE

Be  sure  to  turn  on  the  power  6  hours  before  operation  in
order  to  have  power  running  to  the  crankcase  heater  and
to protect the compressor.

NOTICE

If operation is performed within 12 minutes after the indoor
and  outdoor  units  are  turned  on,  the  compressor  will  not
operate  before  the  communication  is  established  in  a
correct way between outdoor unit(s) and indoor units.

NOTICE

Before  starting  charging  procedures,  check  if  the  7‑LEDs
display is as normal (see 

"6.1.4 To access mode 1 or 2" on

page  16

),  and  there  is  no  malfunction  code  on  the  user

interface  of  the  indoor  unit.  If  a  malfunction  code  is
present,  see 

"8.1  Solving  problems  based  on  error

codes" on page 22

.

NOTICE

Make  sure  all  connected  indoor  units  are  recognised
(setting [1‑5]).

NOTICE

Close  the  front  panel  before  any  refrigerant  charge
operation is executed. Without the front panel attached the
unit cannot judge correctly whether it is operating properly
or not.

NOTICE

In case of maintenance and the system (outdoor unit+field
indoor  units)  does  not  contain  any  refrigerant  any
more (e.g., after refrigerant reclaim operation), the unit has
to  be  charged  with  its  original  amount  of  refrigerant  (refer
to the nameplate on the unit) and the determined additional
refrigerant amount.

5.6.2

To determine the additional refrigerant
amount

INFORMATION

For  final  charge  adjustment  in  a  test  laboratory,  contact
your dealer.

Additional refrigerant to be charged=R (kg). R should be rounded off
in units of 0.1 kg.

R=[(X

1

×

Ø9.5

)×0.059+(X

2

×

Ø6.4

)×0.022]

X

1...2

=Total length (m) of liquid piping size at 

Øa

INFORMATION

Piping  length  is  considered  the  distance  from  the  outdoor
unit to the farthest indoor unit.

When  using  metric  piping,  please  take  into  account  following  table
concerning the weight factor to be allocated. It should be substituted
in the formula for R.

Inch piping

Metric piping

size (Ø) (mm)

Weight factor

size (Ø) (mm)

Weight factor

6.4

0.022

6

0.018

9.5

0.059

10

0.065

5.6.3

To charge refrigerant

To speed up the refrigerant charging process, it is in case of larger
systems  recommended  to  first  pre-charge  a  portion  of  refrigerant
through the liquid line before proceeding with the manual charging. It
can be skipped, but charging will take longer then.

Pre-charging refrigerant

Pre-charging  can  be  done  without  compressor  operation,  by
connecting the refrigerant bottle to the service port of the liquid stop
valve.

1

Connect as shown. Make sure that all outdoor unit stop valves,
as well as valve A are closed.

Summary of Contents for RXYSCQ4TMV1B

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...sete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti...

Page 4: ...settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 16 6 1 6 To use m...

Page 5: ...nit Outdoor unit installation and operation manual Installation and operation instructions Installer and user reference guide Preparation of the installation technical specifications reference data De...

Page 6: ...eep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warming up operation range b Operation range TAI Ambien...

Page 7: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6 2 To determine the additional refrigerant amount on page 12 A Piping...

Page 8: ...wer supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage protector in accordance with the applicable legislation Selection an...

Page 9: ...es dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 5 2 4 To prevent the outdoor unit from falling over Connect cables field supply as shown 4 5 3 Connecting the refrigerant pi...

Page 10: ...the service cover and the piping intake plate 6 Seal all gaps example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be u...

Page 11: ...be leak and vacuum tested Keep any possible field supplied field piping valves open as well Refer to the indoor unit installation manual for more details Leak test and vacuum drying should be done be...

Page 12: ...shed in a correct way between outdoor unit s and indoor units NOTICE Before starting charging procedures check if the 7 LEDs display is as normal see 6 1 4 To access mode 1 or 2 on page 16 and there i...

Page 13: ...valves At this point valve A must remain closed 7 Take all the precautions mentioned in 6 Configuration on page 15 and 7 Commissioning on page 20 into account 8 Turn on the power of the indoor units...

Page 14: ...to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when co...

Page 15: ...ed as applicable DANGER RISK OF ELECTROCUTION 6 1 Making field settings 6 1 1 About making field settings To configure the heat pump system you must give input to the outdoor unit s main PCB A1P This...

Page 16: ...ON the display goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have...

Page 17: ...he unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable...

Page 18: ...uto 46 C 43 C 2 12 Enable the low noise function and or power consumption limitation via external control adaptor DTA104A61 62 If the system needs to be running under low noise operation or under powe...

Page 19: ...efault Level 2 Level 3 2 26 Low noise operation start time This setting is used in conjunction with setting 2 22 20h00 default 22h00 24h00 2 27 Low noise operation stop time This setting is used in co...

Page 20: ...s Once all below checks are fulfilled the unit must be closed only then can the unit be powered up You read the complete installation and operation instructions as described in the installer and user...

Page 21: ...ud and the display indication may change These are not malfunctions 7 3 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 6 1 Making field settings on page 15...

Page 22: ...correctly Recalculate the required amount of refrigerant from the piping length and add an adequate amount of refrigerant Refrigerant overcharge Recalculate the required amount of refrigerant from th...

Page 23: ...the side is not possible Single unit Single row of units See figure 1 on the inside of the front cover A B C D Obstacles walls baffle plates E Obstacle roof a b c d e Minimum service space between the...

Page 24: ...pipe S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch Y1E Electronic expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way v...

Page 25: ...expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way valve Z1C Z7C Noise filter ferrite core Z1F Z5F Noise filter For the user 10 About the system The in...

Page 26: ...1 minute after the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 12 2 3 About the heating ope...

Page 27: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Page 28: ...and details of the defect WARNING Do not modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your deal...

Page 29: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Page 30: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Page 31: ...tem When another unit is running some refrigerant will still flow through the unit 15 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requires technical expert...

Page 32: ...4P399985 1 B 0000000E 4P399985 1B 2015 06 Copyright 2015 Daikin...

Reviews: