background image

11 User interface

Installation and operation manual

26

5TMV1B

VRV IV-S system air conditioner

4P399985-1B – 2015.06

11

User interface

CAUTION

Never touch the internal parts of the controller.

Do  not  remove  the  front  panel.  Some  parts  inside  are
dangerous  to  touch  and  appliance  problems  may  happen.
For checking and adjusting the internal parts, contact your
dealer.

This  operation  manual  will  give  a  non-exhaustive  overview  of  the
main functions of the system.

Detailed information on required actions to achieve certain functions
can  be  found  in  the  dedicated  installation  and  operation  manual  of
the indoor unit.

Refer to the operation manual of the installed user interface.

12

Operation

12.1

Operation range

Use the system in the following temperature and humidity ranges for
safe and effective operation.

Cooling

Heating

Outdoor
temperature

–5~46°C DB

–20~21°C DB

–20~15.5°C WB

Indoor
temperature

21~32°C DB

14~25°C WB

15~27°C DB

Indoor humidity

≤80%

(a)

(a)

To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions,
safety devices may be put in action and the air conditioner
may not operate.

Above operation range is only valid in case direct expansion indoor
units are connected to the VRV IV-S system.

Special  operation  ranges  are  valid  in  case  of  using  AHU.  They  can
be  found  in  the  installation/operation  manual  of  the  dedicated  unit.
Latest information can be found in the technical engineering data.

12.2

Operating the system

12.2.1

About operating the system

▪ Operation  procedure  varies  according  to  the  combination  of

outdoor unit and user interface.

▪ To protect the unit, turn on the main power switch 6 hours before

operation.

▪ If the main power supply is turned off during operation, operation

will restart automatically after the power turns back on again.

12.2.2

About cooling, heating, fan only, and
automatic operation

▪ Changeover cannot be made with a user interface whose display

shows 

  "change-over  under  centralised  control"  (refer  to

installation and operation manual of the user interface).

▪ When  the  display 

  "change-over  under  centralised  control"

flashes,  refer  to 

"12.5.1  About  setting  the  master  user

interface" on page 27

.

▪ The fan may keep on running for about 1 minute after the heating

operation stops.

▪ The  air  flow  rate  may  adjust  itself  depending  on  the  room

temperature  or  the  fan  may  stop  immediately.  This  is  not  a
malfunction.

12.2.3

About the heating operation

It  may  take  longer  to  reach  the  set  temperature  for  general  heating
operation than for cooling operation.

The following operation is performed in order to prevent the heating
capacity from dropping or cold air from blowing.

Defrost operation

In  heating  operation,  freezing  of  the  outdoor  unit's  air  cooled  coil
increases  over  time,  restricting  the  energy  transfer  to  the  outdoor
unit's coil. Heating capability decreases and the system needs to go
into defrost operation to be able to deliver enough heat to the indoor
units:

The  indoor  unit  will  stop  fan  operation,  the  refrigerant  cycle  will
reverse  and  energy  from  inside  the  building  will  be  used  to  defrost
the outdoor unit coil.

The  indoor  unit  will  indicate  defrost  operation  on  the  displays

.

Hot start

In order to prevent cold air from blowing out of an indoor unit at the
start  of  heating  operation,  the  indoor  fan  is  automatically  stopped.
The  display  of  the  user  interface  shows 

.  It  may  take  some

time before the fan starts. This is not a malfunction.

12.2.4

To operate the system

1

Press the operation mode selector button on the user interface
several times and select the operation mode of your choice.

Cooling operation

Heating operation

Fan only operation

2

Press the ON/OFF button on the user interface.

Result: 

The  operation  lamp  lights  up  and  the  system  starts

operating.

12.3

Using the dry program

12.3.1

About the dry program

▪ The  function  of  this  program  is  to  decrease  the  humidity  in  your

room with minimal temperature decrease (minimal room cooling).

▪ The  micro  computer  automatically  determines  temperature  and

fan speed (cannot be set by the user interface).

▪ The system does not go into operation if the room temperature is

low (<20°C).

12.3.2

To use the dry program

To start

1

Press the operation mode selector button on the user interface
several times and select 

 (program dry operation).

2

Press the ON/OFF button of the user interface.

Result: 

The  operation  lamp  lights  up  and  the  system  starts

operating.

3

Press  the  air  flow  direction  adjust  button  (only  for  double-flow,
multi-flow,  corner,  ceiling-suspended  and  wall-mounted).  Refer
to 

"12.4 Adjusting the air flow direction" on page 27

 for details.

To stop

4

Press the ON/OFF button on the user interface once again.

Summary of Contents for RXYSCQ4TMV1B

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...sete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti...

Page 4: ...settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 16 6 1 6 To use m...

Page 5: ...nit Outdoor unit installation and operation manual Installation and operation instructions Installer and user reference guide Preparation of the installation technical specifications reference data De...

Page 6: ...eep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warming up operation range b Operation range TAI Ambien...

Page 7: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6 2 To determine the additional refrigerant amount on page 12 A Piping...

Page 8: ...wer supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage protector in accordance with the applicable legislation Selection an...

Page 9: ...es dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 5 2 4 To prevent the outdoor unit from falling over Connect cables field supply as shown 4 5 3 Connecting the refrigerant pi...

Page 10: ...the service cover and the piping intake plate 6 Seal all gaps example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be u...

Page 11: ...be leak and vacuum tested Keep any possible field supplied field piping valves open as well Refer to the indoor unit installation manual for more details Leak test and vacuum drying should be done be...

Page 12: ...shed in a correct way between outdoor unit s and indoor units NOTICE Before starting charging procedures check if the 7 LEDs display is as normal see 6 1 4 To access mode 1 or 2 on page 16 and there i...

Page 13: ...valves At this point valve A must remain closed 7 Take all the precautions mentioned in 6 Configuration on page 15 and 7 Commissioning on page 20 into account 8 Turn on the power of the indoor units...

Page 14: ...to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when co...

Page 15: ...ed as applicable DANGER RISK OF ELECTROCUTION 6 1 Making field settings 6 1 1 About making field settings To configure the heat pump system you must give input to the outdoor unit s main PCB A1P This...

Page 16: ...ON the display goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have...

Page 17: ...he unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable...

Page 18: ...uto 46 C 43 C 2 12 Enable the low noise function and or power consumption limitation via external control adaptor DTA104A61 62 If the system needs to be running under low noise operation or under powe...

Page 19: ...efault Level 2 Level 3 2 26 Low noise operation start time This setting is used in conjunction with setting 2 22 20h00 default 22h00 24h00 2 27 Low noise operation stop time This setting is used in co...

Page 20: ...s Once all below checks are fulfilled the unit must be closed only then can the unit be powered up You read the complete installation and operation instructions as described in the installer and user...

Page 21: ...ud and the display indication may change These are not malfunctions 7 3 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 6 1 Making field settings on page 15...

Page 22: ...correctly Recalculate the required amount of refrigerant from the piping length and add an adequate amount of refrigerant Refrigerant overcharge Recalculate the required amount of refrigerant from th...

Page 23: ...the side is not possible Single unit Single row of units See figure 1 on the inside of the front cover A B C D Obstacles walls baffle plates E Obstacle roof a b c d e Minimum service space between the...

Page 24: ...pipe S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch Y1E Electronic expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way v...

Page 25: ...expansion valve main Y3E Electronic expansion valve subcool heat exchanger Y1S Solenoid valve 4 way valve Z1C Z7C Noise filter ferrite core Z1F Z5F Noise filter For the user 10 About the system The in...

Page 26: ...1 minute after the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 12 2 3 About the heating ope...

Page 27: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Page 28: ...and details of the defect WARNING Do not modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your deal...

Page 29: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Page 30: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Page 31: ...tem When another unit is running some refrigerant will still flow through the unit 15 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requires technical expert...

Page 32: ...4P399985 1 B 0000000E 4P399985 1B 2015 06 Copyright 2015 Daikin...

Reviews: