Outline of Control (Indoor Unit)
SiUS371901E
143
Functions and Control
9.4.2 With Optional Infrared Presence/Floor Sensor
Whether the thermostat is turned on or off is determined by the difference between the remote
controller set temperature and the detected temperature around people.
Normal operation
· Cooling operation
· Heating operation
Dry operation
· When Tro
≤
24.5°C (76.1°F)
· When Tro > 24.5°C (76.1°F)
∆
T : Room temperature or temperature around people – Remote controller set temperature
Tro : Room temperature or temperature around people at the start of dry operation
Tr : Room temperature or temperature around people
Control range of temperature around people
When the floor temperature is very low, operation using the temperature around people may cause
the suction air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use range of
the temperature around people.
•
Cooling operation
· When the floor temperature is lower than suction air temperature (R1T), R1T will be treated as
the control target temperature for operation.
· When the temperature around people is 15°C (59°F) or lower, R1T will be treated as the
control temperature for operation.
•
Heating operation
· When the floor temperature is higher than suction air temperature (R1T), R1T will be treated
as the control target temperature in operation.
· When the temperature around people is 33°C (91.4°F) or higher, R1T will be treated as the
control temperature for operation.
Thermostat OFF
Normal operation
(Thermostat ON)
∆
T
≤
–1.0˚C (–1.8˚F)
∆
T
≥ +
1.0˚C (
+
1.8˚F)
Thermostat OFF
Normal operation
(Thermostat ON)
∆
T
≥ +
1.0˚C (
+
1.8˚F)
∆
T
≤
–1.0˚C (–1.8˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.0˚C (– 1.8˚F)
Tr > Tro + 1.0˚C (+ 1.8˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.5˚C (– 2.7˚F)
Tr > Tro + 0.5˚C (+ 0.9˚F)
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...