Outline of Control (Indoor Unit)
SiUS371901E
159
Functions and Control
9.15 Fan Control (Heater Residual) (FXTQ-TA Models)
Outline
If the indoor heater turned OFF from ON during heating operation, the fan will keep operating for
further period of time in order to cool the heater.
Detail
∗
1. When the heater is ON, the airflow rate of the fan will be whichever is the largest between the
CFM dictated by the heater's own capacity, or the fan tap CFM determined by other controls.
∗
2. Fan residual operation will continue, even if the indoor unit is turned off with the remote
controller operation button.
9.16 Interlocked with External Equipment (FXTQ-TA and CXTQ-
TA Models)
9.16.1 Air Purifier (UV lamp)
When an air purifier is connected onsite, the fan is operated with the airflow rate set of the remote
controller or with the H tap.
∗
1. External input ON is an input signal to the X1M-AIR CLEANER terminal on the PCB.
9.16.2 Humidifier
When a humidifier is connected onsite, the fan operates with the airflow rate set of the remote
controller or with the H tap.
∗
1. External input ON is an input signal to the X1M-HUMIDIFIER terminal on the PCB.
Note:
This control is not applicable to the humidifier connected to the wiring adaptor, but to the humidifier
connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB.
•
Heater turned OFF from ON
OR
•
Heater ON
•
Time up (
∗
2)
Residual OFF
Residual ON
Fan (
∗
1)
ENTRY/
90 sec. timer starts.
&
Fan operation at preset tap
(Fan tap can be changed by field setting
14 (24)-4.)
•
Remote control operation
(including thermostat OFF)
•
External input: ON (
∗
1)
&
&
•
Remote control operation: ON
(including thermostat OFF)
•
When the external input
changes from ON to OFF.
•
Remote control operation: ON
(including thermostat OFF)
•
External input: ON (
∗
1)
Fan operation at preset tap
(Fan tap can be changed by field setting
14 (24)-4.)
Fan residual operation for 30 seconds
(Fan tap can be changed by field setting
14 (24)-4.)
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...