Field Settings for Outdoor Unit
SiUS371901E
207
Field Settings and Test Operation
When operation parameters return to normal range, the capacity priority is switched OFF, enable to
reduce airflow rate depending on night-time low noise operation is still required (end time for night-time
low noise operation is not reached or external input night-time low noise operation is still closed).
[2-30]: Power consumption limitation level (step 1) via the external control adaptor (DTA104A61/62)
If the system needs to run under power consumption limitation conditions when an external signal is sent
to the unit, this setting defines the level power consumption limitation that will be applied for step 1. The
level is according to the table.
Default value: 3.
Change [2-30] to 1, 2, 3, 4, 5, 6, 7 or 8 in function of required limitation.
[2-31]: Power consumption limitation level (step 2) via the external control adaptor (DTA104A61/62)
If the system needs to run under power consumption limitation conditions when an external signal is sent
to the unit, this setting defines the level power consumption limitation that will be applied for step 2. The
level is according to the table.
Default value: 1.
Change [2-31] to 1, 2 or 3 in function of required limitation.
Value
[2-30]
Power consumption limitation
(approximately)
1
60%
2
65%
3 (default)
70%
4
75%
5
80%
6
85%
7
90%
8
95%
Value
[2-31]
Power consumption limitation
(approximately)
1 (default)
40%
2
50%
3
55%
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with "Night-time low
noise operation start setting"
Low noise mode
instructing
Operation sound set with
"External low noise setting"
10:00 PM
8:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Set with "Night-time low noise operation start
setting". (Factory setting is "10:00 PM".)
Set with "Night-time low noise operation end
setting". (Factory setting is "8:00 AM".)
∗
Low noise
mode instructing
∗
Operation sound set with
"External low noise setting"
∗
Night-time
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with "Night-time low
noise operation end setting"
∗
Operation sound mode
set with "Night-time low
noise operation setting"
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...