English

5

4) Set the suspension bolt. (Use W3/8 or M8-M10 size sus-

pension bolts.)
• Adjust the distance from the unit to the ceiling slab 

beforehand.

 (Refer to Fig. 8)

NOTE

NOTE

NOTE

NOTE

• All the above parts are field supplied.

5. INDOOR UNIT INSTALLATION

Installing optional accessories before installing the indoor 
unit is easier. 

As for the parts to be used for installation work, be sure to use 
the provided accessories and specified parts designated by our 
company.

(1) Secure the hooks to the eyebolts.

 

(Refer to Fig. 9)

NOTE

NOTE

NOTE

NOTE

• To ensure they are safely secured, use the included wash-

ers, and secure them with a double nut to make sure.

(2) Lift the indoor unit’s main body, insert the bolt (M8) for 

the hook into the attachment part on the hook, while 
sliding the main body from the front.

 

(Refer to Fig. 10)

(3) Fasten the bolts for the hooks (M8) securely in the four 

locations, left and right.

 

(Refer to Fig. 10)

(4) Replace the screws for the hooks which had been 

removed (M5) securely in 2 places left and right. This is 
necessary to prevent any forward and back deviance in 
the main body of the indoor unit.

 

(Refer to Fig. 10)

(5) When hanging the indoor unit main body, be sure to 

use a level or a plastic tube with water in it to make sure 
the drain piping is set either level or slightly tilted, in 
order to ensure proper drainage.

 

(Refer to Fig. 11)

A.When the drain piping is tilted to the right, or to the right 

and back.

Place it level, or tilt it slightly to the right or the back. 
(Within 1°.)

B.When the drain piping is tilted to the left, or to the left and 

back.

Place it level, or tilt it slightly to the left or the back. 
(Within 1°.)

CAUTION

Setting the unit at an angle opposite to the drain piping 
might cause leaks.

6. REFRIGERANT PIPING WORK

〈〈〈〈

For refrigerant piping of outdoor units, see the installation 

manual attached to the outdoor unit.

〉〉〉〉

〈〈〈〈

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.

〉〉〉〉

(When using a heat pump, the temperature of the gas piping 
can reach up to approximately 120

°

C, 

so

 

use

 

insulation which 

is sufficiently resistant

.)

〈〈〈〈

Also, in cases where the temperature and humidity of the 

refrigerant piping sections might exceed 30°C or RH80%, 
reinforce the refrigerant insulation. (20 mm or thicker) Con-
densation may form on the surface of the insulating mate-
rial.

〉〉〉〉

〈〈〈〈

Before refrigerant piping work, check which type of refrig-

erant is used. Proper operation is not possible if the types 
of refrigerant are not the same.

〉〉〉〉

CAUTION

Use a pipe cutter and flare suitable for the type of refrig-
erant.

Apply ester oil or ether oil around the flare portions 
before connecting.

To prevent dust, moisture or other foreign matter from 
infiltrating the tube, either pinch the end or cover it with 
tape.

Do not allow anything other than the designated refrig-
erant to get mixed into the refrigerant circuit, such as air, 
etc. If any refrigerant gas leaks while working on the 
unit, ventilate the room thoroughly right away.

Ceiling slab

Anchor

Suspension bolt

False ceiling

25-5

5

(length : mm)

Fig. 8

Use a hole-in-anchor for existing ceilings, and a sunken insert, 

sunken anchor or other part to be procured in the field for new 

ceilings to reinforce the ceiling to bearing the weight of the unit.

Adjust clearance from the ceiling before proceeding further.

Nut (Field supplied)

Washer (3) (accessory)

Double nut

Hanger bracket

Fig. 9

Hanger bracket

Attachment part

Hanger bracket

setting bolt (M8)

Hanger bracket

fixing screw (M5)

Fig. 10

≤ 

≤ 

≤ 

A

A.B

B

Fig. 11

01_EN_3P172532-7.fm  Page 5  Thursday, December 15, 2005  2:45 PM

Summary of Contents for FXHQ32MVE

Page 1: ...E INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFE...

Page 2: ...VE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXLQ50MHV1 FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MA...

Page 3: ...lation work may result in the equipment falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified...

Page 4: ...ubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vic...

Page 5: ...wever if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for installation Check whether the ceiling is strong...

Page 6: ...on to remove Refer to Fig 5 Pull out of the accessories 3 Remove the hanger bracket Loosen two hanger bracket setting bolts M8 two on each side on each side for less than 10 mm Refer to Fig 6 and 7 Re...

Page 7: ...might cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Execute heat insulation work completely on both sides of t...

Page 8: ...hen connecting or disconnecting pipes to from the unit Refer to Fig 16 Refer to Table1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare section both inside and outsi...

Page 9: ...hose included with the main body Refer to Table 1 for tightening torque Table 1 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit witho...

Page 10: ...converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work Add 0 6 liter of water in the drain pan from the...

Page 11: ...electric parts box lid Align the phase and connect the wire to the power terminal block 6P inside the electric parts box After connecting use the included clamps 4 to bind the wire together with the...

Page 12: ...smission wiring at least 50 mm away from power supply wiring The equipment may mal function if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF...

Page 13: ...o perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...0602 HT 3P172532 7 EM02A086B 00_CV_3P172532 7 fm Page 2 Tuesday December 13 2005 12 58 PM...