background image

English

9

• This system consists of multiple indoor units. Mark each 

indoor unit as unit A, unit B..., and be sure the terminal board 
wiring to the outdoor unit and BS unit are properly matched. 
If wiring and piping between the outdoor unit and an indoor 
unit are mismatched, the system may cause a malfunction.

• A circuit breaker capable of shutting down power supply to 

the entire system must be installed.

• Refer to the installation manual attached to the outdoor unit 

for the size of power supply wiring connected to the outdoor 
unit, the capacity of the circuit breaker and switch, and wiring 
instructions.

• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, light-

ning rods, or telephone ground wires.

• Gas pipes

 

:

 

might

 

cause explosions or fire if gas leaks.

• Water pipes : no grounding effect if hard vinyl piping is used.
• Telephone ground wires or lightning rods : might cause 

abnormally high electric potential in the ground during 
lighting storms.

8-2

ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A);

MFA: Max. Fuse Amps (A) 

kW: Fan Motor Rated Output (kW);FLA: Full Load Amps (A)

8-3

SPECIFICATIONS FOR FIELD SUPPLIED 
FUSES AND WIRE 

NOTE

NOTE

NOTE

NOTE

1.

Allowable length of transmission wiring between indoor/
outdoor units and between the indoor unit and the remote 
controller is as follows. 

(1) Outdoor unit – Indoor unit: 

Max. 1000 m (Total wiring length: 2000 m) 

(2) Indoor unit – Remote controller: 

Max. 500 m

9. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER

9-1

HOW TO CONNECT WIRINGS 

〈〈〈〈

Method of wiring power supply, units and connecting 

remote controller wiring

〉 〉 〉 〉 

(Refer to Fig. 26)

Power supply wiring

Hold the electric parts box lid and loosen the anchoring 
screws (2 pc.), then remove the electric parts box lid. Align 
the phase and connect the wire to the power terminal block 
(6P) inside the electric parts box. After connecting, use the 
included clamps (4) to bind the wire, together with the ground 
wire, to the anchor. 

(Refer to Fig. 27)

Remote controller wiring and transmission wiring

Hold the electric parts box lid and loosen the anchoring 
screws (2 pc.), then remove the electric parts box lid. Con-
nect the wires to the power terminal block (6P) inside the 
electric parts box. After connecting, use the included clamps 
(4) to bind the remote controller wire, together with the trans-
mission wire, to the anchor. 

(Refer to Fig. 27)

Units

Power supply

Fan motor

Model

Hz

Volts

Voltage 

range

MCA

MFA

kW

FLA

FXHQ32M(A)VE

50

220-240

Max. 264
Min.  198

0.8

15

0.062 0.6

FXHQ63M(A)VE

0.8

15

0.062 0.6

FXHQ100M(A)VE

0.9

15

0.130 0.7

FXHQ32M(A)VE

60

220

Max. 242
Min.  198

0.9

15

0.062 0.7

FXHQ63M(A)VE

0.9

15

0.062 0.7

FXHQ100M(A)VE

1.3

15

0.130 1.0

Model

Power supply wiring

Remote controller 

wiring

Transmission wiring

Field 

fuses  Wire

Size

Wire

Size

FXHQ32M(A)VE

15A

H05VV-

U3G

Wire size must 

comply with 

local codes

Sheathed wire

(2 wire)

0.75 - 

1.25 
mm

2

FXHQ63M(A)VE

FXHQ100M(A)VE

Ground

terminal

Refer to Fig. 27

Rear

penetration lid

Ground wiring (*)

(Field wiring)
Power supply

wiring (*)

(Field wiring)

Electric

parts box

Terminal block

for remote

controller (6P)

Power supply terminal block (2P)

Electric parts

box lid fixation

screw (2 P)

Fig. 26

Electric parts box lid

Electric wiring

diagram plate

Remote controller wiring

and transmission wiring (*)

(Field wiring)

How to connect power supply

terminal block (2P)

power supply

cord

power supply

L N

Fastener Clamp (4) (accessory)

Clamp (4)

(accessory)

Ground wiring

After securing the

cramp material

to the bracket,

cut off any extra

material.

Remote controller wiring and

transmission wiring

Fastener

Power supply 

wiring

Fig. 27

01_EN_3P172532-7.fm  Page 9  Thursday, December 15, 2005  2:45 PM

Summary of Contents for FXHQ32MVE

Page 1: ...E INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFE...

Page 2: ...VE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXLQ50MHV1 FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MA...

Page 3: ...lation work may result in the equipment falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified...

Page 4: ...ubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vic...

Page 5: ...wever if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for installation Check whether the ceiling is strong...

Page 6: ...on to remove Refer to Fig 5 Pull out of the accessories 3 Remove the hanger bracket Loosen two hanger bracket setting bolts M8 two on each side on each side for less than 10 mm Refer to Fig 6 and 7 Re...

Page 7: ...might cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Execute heat insulation work completely on both sides of t...

Page 8: ...hen connecting or disconnecting pipes to from the unit Refer to Fig 16 Refer to Table1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare section both inside and outsi...

Page 9: ...hose included with the main body Refer to Table 1 for tightening torque Table 1 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit witho...

Page 10: ...converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work Add 0 6 liter of water in the drain pan from the...

Page 11: ...electric parts box lid Align the phase and connect the wire to the power terminal block 6P inside the electric parts box After connecting use the included clamps 4 to bind the wire together with the...

Page 12: ...smission wiring at least 50 mm away from power supply wiring The equipment may mal function if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF...

Page 13: ...o perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...0602 HT 3P172532 7 EM02A086B 00_CV_3P172532 7 fm Page 2 Tuesday December 13 2005 12 58 PM...

Reviews: