4. PREPARATIONS BEFORE INSTALLA-

TION

(1) Relative positions of indoor unit, suspension bolt, pip-

ing hole, drain piping hole, and electric wire hole posi-
tion. (Refer to Fig. 2)

(2) Make the suspension bolt hole, piping hole, drain pip-

ing hole.

• Refer to the paper pattern for installation for hole posi-

tions.

• Fix the positions for suspension bolt, piping hole, drain 

piping hole, and electric wire hole, and make the open-
ings.

(3) Detach the parts for indoor unit.

1) Detach the suction grille.

• Slide the suction grille fixing knobs (2 parts) backward 

(arrow direction) and open the suction grille widely. 

(Refer to Fig. 3)

• Keep the suction grille opened. Holding the knob on the 

back of suction grille, pull to the front direction to 
remove. 

(Refer to Fig. 4)

2) Detach the dressing boards (left and right).

• Remove the side panel fixing screw 1) and pull to the 

front direction (arrow direction) to remove. 

(Refer to Fig. 5)

• Pull out of the accessories.

3) Remove the hanger bracket.

• Loosen two hanger bracket setting bolts (M8) (two on 

each side) on each side for less than 10 mm. 

(Refer to Fig. 6 and  7)

• Remove two hanger bracket fixing bolts (M5) on the 

rear side. Detach the hanger bracket by pulling back-
wards. 

(Refer to Fig. 7)

Model

A

B

C

D

E

F

G

FXHQ32M(A)VE

960

920

390

375

310

400

375

FXHQ63M(A)VE

1160 1120

490

475

410

500

475

FXHQ100M(A)VE

1400 1360

610

595

530

620

595

160

135

F

G

Rear side piping hole 

(

φ 

100 )

Left side piping hole

Front view

A (Decoration panel)

B (Suspension bolt pitch)

B

(Suspension

bolt

pitch)

85

185

160

210

260

680

(Decoration

panel)

C
D
E

Top side drain

piping hole

Top liquid hole

Top gas

piping hole

Suspension

bolt (×4)

Air outlet

False ceiling view

(length : mm)

Fig. 2

Fig. 3

Fig. 4

Accessories

Dressing board securing

screw (M4)

Dressing board

Fig. 5

Indoor unit

Hanger bracket

Max. exposed

thread 10 mm

Fig. 6

Hanger bracket

fixing screw (M5)

Hanger bracket

Hanger bracket

setting bolt (M8)

Fig. 7

01_EN_3P172532-7.fm  Page 4  Thursday, December 15, 2005  2:45 PM

Summary of Contents for FXHQ32MVE

Page 1: ...E INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFE...

Page 2: ...VE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXLQ50MHV1 FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MA...

Page 3: ...lation work may result in the equipment falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified...

Page 4: ...ubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vic...

Page 5: ...wever if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for installation Check whether the ceiling is strong...

Page 6: ...on to remove Refer to Fig 5 Pull out of the accessories 3 Remove the hanger bracket Loosen two hanger bracket setting bolts M8 two on each side on each side for less than 10 mm Refer to Fig 6 and 7 Re...

Page 7: ...might cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Execute heat insulation work completely on both sides of t...

Page 8: ...hen connecting or disconnecting pipes to from the unit Refer to Fig 16 Refer to Table1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare section both inside and outsi...

Page 9: ...hose included with the main body Refer to Table 1 for tightening torque Table 1 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit witho...

Page 10: ...converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work Add 0 6 liter of water in the drain pan from the...

Page 11: ...electric parts box lid Align the phase and connect the wire to the power terminal block 6P inside the electric parts box After connecting use the included clamps 4 to bind the wire together with the...

Page 12: ...smission wiring at least 50 mm away from power supply wiring The equipment may mal function if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF...

Page 13: ...o perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...0602 HT 3P172532 7 EM02A086B 00_CV_3P172532 7 fm Page 2 Tuesday December 13 2005 12 58 PM...

Reviews: