VRV SYSTEM Inverter Air Conditioners

Installation manual

CONTENTS

1. SAFETY CONSIDERATIONS ......................................... 1
2. BEFORE INSTALLATION................................................ 2
3. SELECTING INSTALLATION SITE ................................. 3
4. PREPARATIONS BEFORE INSTALLATION ................... 4
5. INDOOR UNIT INSTALLATION....................................... 5
6. REFRIGERANT PIPING WORK ..................................... 5
7. DRAIN PIPING WORK .................................................... 7
8. ELECTRIC WIRING WORK ............................................ 8
9. WIRING EXAMPLE AND HOW TO SET THE 

REMOTE CONTROLLER................................................ 9

10. INSTALLATION OF THE SUCTION GRILLE AND THE 

AIR FILTER ................................................................... 12

11. FIELD SETTING............................................................ 12

12. TEST OPERATION ....................................................... 12

1. SAFETY CONSIDERATIONS

Please read these “SAFETY CONSIDERATIONS” carefully 
before installing air conditioning equipment and be sure to 
install it correctly.  After completing the installation, make sure 
that the unit operates properly during the start-up operation.  
Please instruct the customer on how to operate the unit and 
keep it maintained.
Also, inform customers that they should store this installation 
manual along with the operation manual for future reference.
This air conditioner comes under the term “appliances not acces-
sible to the general public”.

Safety Precaution

This unit is a class A product. In a domestic environment this prod-
uct may cause radio interference in which case the user may be 
required to take adequate measures.

Meaning of warning and caution symbols.

WARNING

  ............ Failure to observe a warning may 

result in death or serious injury.

CAUTION

  ............. Failure to observe a caution may 

result in injury or damage to the equip-
ment.

WARNING

• Ask your dealer or qualified personnel to carry out installation 

work. Do not try to install the machine yourself.
Improper installation may result in water leakage, electric 
shocks or fire.

• Perform installation work in accordance with this installation 

manual.
Improper installation may result in water leakage, electric 
shocks or fire.

• When installing the unit in a small room, take measures 

against to keep refrigerant concentration from exceeding 
allowable safety limits in the event of refrigerant leakage. 
Contact the place of purchase for more information. Exces-
sive refrigerant in a closed ambient can lead to oxygen defi-
ciency.

• Be sure to use only the specified accessories and parts for 

installation work.
Failure to use the specified parts may result in water leakage, 
electric shocks, fire or the unit falling.

• Install the air conditioner on a foundation strong enough to 

withstand the weight of the unit.
A foundation of insufficient strength may result in the equip-
ment falling and causing injuries.

• Carry out the specified installation work after taking into 

account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling 
and causing accidents.

• Make sure that a separate power supply circuit is provided 

for this unit and that all electrical work is carried out by qual-
ified personnel according to local laws and regulations and 
this installation manual.
An insufficient power supply capacity or improper electrical 
construction may lead to electric shocks or fire.

• Make sure that all wiring is secured, the specified wires and 

used, and no external forces act on the terminal connections 
or wires.
Improper connections or installation may result in fire.

• When wiring the power supply and connecting the remote 

controller wiring and transmission wiring, position the wires 
so that the electric parts box lid can be securely fastened.
Improper positioning of the electric part box lid may result in 
electric shocks, fire or the terminals overheating. 

• If the refrigerant gas leaks during installation, ventilate the 

area immediately.
Toxic gas may be produced if the refrigerant gas comes into 
contact with fire.

• After completing the installation work, check that the refriger-

ant gas does not leak.
Toxic gas may be produced if the refrigerant gas leaks into 
the room and comes into contact with a source of fire, such 
as a fan heater, stove or cooker.

• Before touching electrical parts, turn off the unit.
• Be sure to establish an earth.

Do not earth the unit to a utility pipe, arrester, or telephone 
earth.
Incomplete earth may cause electrical shock, or fire. 
A high surge current from lightning or other sources may 
cause damage to the air conditioner.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in elec-
tric shocks, or fire.

CAUTION

• While following the instructions in this installation manual, 

install drain piping in order to ensure proper drainage and 
insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and prop-
erty damage.

• Install the indoor and outdoor units, power supply wiring and 

connecting wires at least 1 meter away from televisions or 
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may 
not be sufficient enough to eliminate the noise.)

• Remote controller (wireless kit) transmitting distance can 

result shorter than expected in rooms with electronic fluores-
cent lamps. (inverter or rapid start types) 
Install the indoor unit as far away from fluorescent lamps as 
possible.

• Do not install the air conditioner in the following locations:

(a) where a mineral oil mist or an oil spray or vapor is pro-

duced, for example in a kitchen
Plastic parts may deteriorate and fall off or result in 
water leakage.

01_EN_3P172532-7.fm  Page 1  Thursday, December 15, 2005  2:45 PM

Summary of Contents for FXHQ32MVE

Page 1: ...E INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFE...

Page 2: ...VE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXLQ50MHV1 FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MA...

Page 3: ...lation work may result in the equipment falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified...

Page 4: ...ubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vic...

Page 5: ...wever if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for installation Check whether the ceiling is strong...

Page 6: ...on to remove Refer to Fig 5 Pull out of the accessories 3 Remove the hanger bracket Loosen two hanger bracket setting bolts M8 two on each side on each side for less than 10 mm Refer to Fig 6 and 7 Re...

Page 7: ...might cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Execute heat insulation work completely on both sides of t...

Page 8: ...hen connecting or disconnecting pipes to from the unit Refer to Fig 16 Refer to Table1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare section both inside and outsi...

Page 9: ...hose included with the main body Refer to Table 1 for tightening torque Table 1 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit witho...

Page 10: ...converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work Add 0 6 liter of water in the drain pan from the...

Page 11: ...electric parts box lid Align the phase and connect the wire to the power terminal block 6P inside the electric parts box After connecting use the included clamps 4 to bind the wire together with the...

Page 12: ...smission wiring at least 50 mm away from power supply wiring The equipment may mal function if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF...

Page 13: ...o perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...0602 HT 3P172532 7 EM02A086B 00_CV_3P172532 7 fm Page 2 Tuesday December 13 2005 12 58 PM...