background image

6

English

(1) In case of backward piping

• Remove the rear cover for piping. 

(Refer to Fig. 12, 14)

(2) In case of upward piping

• In case of upward piping,optional L-shape piping kit is 

required.

• Remove the cover for ceiling outlet and use optional 

L-shape piping kit for piping. 

(Refer to Fig.12, 13)

(3) In case of right side piping

• Cut the slit on the dressing board (Right) and perform pip-

ing. 

(Refer to Fig. 14)

• When piping is complete, cut the removed penetration lid into 

the shape of the piping using scissors and attach. As when 
before removing the top penetration lid, secure the lead lines 
for the swing motor and thermistor by passing them through 
the cramp part on the top penetration lid. 

(Refer to Fig. 12, 15)

• When doing this, block any gaps between the piping penetra-

tion lid and the pipes using putty to prevent dust from enter-
ing the indoor unit.

• The outdoor units is charged with refrigerant.
• Be sure to use both a spanner and torque wrench together, 

when connecting or disconnecting pipes to/from the unit.

 

(Refer to Fig. 16)

• Refer to Table1 for the dimensions of flare nut spaces.
• When connecting the flare nut, coat the flare section (both 

inside and outside) with ester oil or ether oil, rotate three or  
four times first, then screw in. 

(Refer to Fig. 17)

CAUTION

• Do not let oil get on the screw holders on the dressing board. 

Oil can weaken the screw holders.

• Overtightening may damage the flare and cause a refrigerant 

leakage.

Top plate

Cut out

Rear

penetration lid

Top penetration lid

Cut out

Fig. 12

Upward-facing

refrigerant piping

L-shaped branch piping

kit (Optional accessories)

Fig. 13

Rear-facing

refrigerant piping

Rear right-facing

drain piping

Right-facing drain piping

Right-facing

refrigerant

piping

Dressing board (right)

removable part

If only setting the drain piping to

face right, cut this section only.

Fig. 14

Top penetration

lid cramp section

Clamp

Electric valve lead line

Thermistor lead line

Swing motor

lead line

Thermistor

lead line

Fig.15

Torque wrench

Spanner

Piping union

Flare nut

Fig. 16

Ester oil or ether oil

Fig. 17

01_EN_3P172532-7.fm  Page 6  Thursday, December 15, 2005  2:45 PM

Summary of Contents for FXHQ32MVE

Page 1: ...E INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFE...

Page 2: ...VE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXLQ50MHV1 FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MA...

Page 3: ...lation work may result in the equipment falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified...

Page 4: ...ubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vic...

Page 5: ...wever if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for installation Check whether the ceiling is strong...

Page 6: ...on to remove Refer to Fig 5 Pull out of the accessories 3 Remove the hanger bracket Loosen two hanger bracket setting bolts M8 two on each side on each side for less than 10 mm Refer to Fig 6 and 7 Re...

Page 7: ...might cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Execute heat insulation work completely on both sides of t...

Page 8: ...hen connecting or disconnecting pipes to from the unit Refer to Fig 16 Refer to Table1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare section both inside and outsi...

Page 9: ...hose included with the main body Refer to Table 1 for tightening torque Table 1 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit witho...

Page 10: ...converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work Add 0 6 liter of water in the drain pan from the...

Page 11: ...electric parts box lid Align the phase and connect the wire to the power terminal block 6P inside the electric parts box After connecting use the included clamps 4 to bind the wire together with the...

Page 12: ...smission wiring at least 50 mm away from power supply wiring The equipment may mal function if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF...

Page 13: ...o perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...0602 HT 3P172532 7 EM02A086B 00_CV_3P172532 7 fm Page 2 Tuesday December 13 2005 12 58 PM...

Reviews: