8

English

• For left drain pipe outlet, remove the rubber plug and the 

insulation on the drain pipe connecting opening on the 
left side of the unit and change the position to the right 
side.

• Insert the rubber stopper securely, all the way to the 

base, in order to prevent water leakage.

• The diameter of the drain pipe should be greater than or 

equal to the diameter of the connecting pipe. (Vinyl tube; 
pipe size: 20 mm; outer dimension: 26 mm)

• Keep the drain pipe short and sloping downwards at a 

gradient of at least 1/100 to prevent air pockets from 
forming. 

(Refer to Fig. 21)

• Use the drain hose (1) and the metal clamp (2). 

Insert the drain hose into the drain socket, up to the gray 
tape. 

(Refer to Fig. 22)

 

Tighten the metal clamp until the screw head is less than 
4 mm from the hose. 

(Refer to Fig. 23)

(Be careful of the installation direction. Install so that the 
metal clamp does not contact the intake grill.)

• Wrap the sealing pad (8) (accessory) over the clamp and 

drain hose to insulate. 

(Refer to Fig. 23)

• No folding of drain hose inside the indoor unit. 

(Refer to Fig. 24)

(If there is slack in the drain hose, it may cause damage 
to the intake grill.)

NOTE

NOTE

NOTE

NOTE

• To ensure no excessive pressure is applied to the included 

drain hose (1), do not bend or twist when installing. (This may 
cause leakage.)

• If converging multiple drain pipes, install according to the 

procedure shown below.

Select converging drain pipes whose gauge is suitable for the 
operating capacity of the unit.

(2) Confirm that smooth drainage is achieved after the pip-

ing work.

• Add 0.6 liter of water in the drain pan from the air outlet 

for confirming drainage. 

(Refer to Fig. 25)

CAUTION

• Drain piping connections

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain pipes and corrode the heat 
exchanger.

• Keep in mind that it will become the cause of getting drain 

pipe blocked if water collects on drain pipe.

8. ELECTRIC WIRING WORK 

8-1

GENERAL INSTRUCTIONS 

• All field supplied parts and materials and electric works must 

conform to local codes.

• Use copper wire only.
• For electric wiring work, refer to also

 “

Wiring diagram label

” 

attached to the electric parts box lid.

• For remote controller wiring details, refer to the installation 

manual attached to the remote controller.

• All wiring must be performed by an authorized electrician.

Tilt down

Do not lift

(When drain hose is connected)

Make sure there

is no slack

Make sure it is

not in the water

Good

Wrong

Fig. 21

Taping area

Drain hose (1) 

(accessory)

Metal clamp (2) (accessory)

Fig. 22

Sealing pad (8)

(accessory)

Metal clamp (2)

(accessory)

Sealing pad (8)

(accessory)

Metal clamp (2)

(accessory)

4

4

(length : mm)

< Facing rear right or right >

< Facing rear left or left >

Fig. 23

100

mm

T-joint converging drain pipes

Slope downwards at a gradient

of at least 1/100

Wrong

Fig. 24

Air outlet

Portable pump

Bucket

Fig. 25

01_EN_3P172532-7.fm  Page 8  Thursday, December 15, 2005  2:45 PM

Summary of Contents for FXHQ32MVE

Page 1: ...E INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFE...

Page 2: ...VE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXLQ50MHV1 FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MA...

Page 3: ...lation work may result in the equipment falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified...

Page 4: ...ubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vic...

Page 5: ...wever if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for installation Check whether the ceiling is strong...

Page 6: ...on to remove Refer to Fig 5 Pull out of the accessories 3 Remove the hanger bracket Loosen two hanger bracket setting bolts M8 two on each side on each side for less than 10 mm Refer to Fig 6 and 7 Re...

Page 7: ...might cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Execute heat insulation work completely on both sides of t...

Page 8: ...hen connecting or disconnecting pipes to from the unit Refer to Fig 16 Refer to Table1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare section both inside and outsi...

Page 9: ...hose included with the main body Refer to Table 1 for tightening torque Table 1 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit witho...

Page 10: ...converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work Add 0 6 liter of water in the drain pan from the...

Page 11: ...electric parts box lid Align the phase and connect the wire to the power terminal block 6P inside the electric parts box After connecting use the included clamps 4 to bind the wire together with the...

Page 12: ...smission wiring at least 50 mm away from power supply wiring The equipment may mal function if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF...

Page 13: ...o perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...0602 HT 3P172532 7 EM02A086B 00_CV_3P172532 7 fm Page 2 Tuesday December 13 2005 12 58 PM...

Reviews: