3

FOR THE FOLLOWING ITEMS, TAKE SPECIAL 
CARE DURING CONSTRUCTION AND CHECK 
AFTER INSTALLATION IS FINISHED.

a. Items to be checked after completion of work

b. Items to be checked at time of delivery

Also review the “SAFETY CONSIDERATIONS”

c. Points for explanation about operations

2-4

NOTE TO THE INSTALLER

Be sure to instruct customers how to properly operate the 
unit (especially cleaning filters, operating different functions, 
and adjusting the temperature) by having them carry out 
operations themselves while looking at the manual.

3. SELECTING INSTALLATION SITE

(1) Select an installation site where the following condi-

tions are fulfilled and that meets your customer’s 
approval.

• In the upper space of the indoor unit where there is no 

possible dripping of water from the refrigerant pipe, drain 
pipe, water pipe, etc.

• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• If supporting structural members are not strong enough 

to take the unit’s weight, the unit could fall out of place 
and cause serious injury.

• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service 

can be ensured. 

(Refer to Fig. 1)

If sufficient clearance could be ensured at*, leave a 
space of 200 mm or more between the unit and it’s sur-
roundings easier maintenance and service.

• Where piping between indoor and outdoor units is possi-

ble within the allowable limit. (Refer to the installation 
manual for the outdoor unit.)

CAUTION

• Install the indoor and outdoor units, power supply wiring and 

connecting wires at least 1 meter away from televisions or 
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may 
not be sufficient enough to eliminate the noise.)

(2) This indoor unit may be installed on ceilings up to 3.5 m 

in height. However, if the ceiling is higher than 2.7m, 
the remote control will have to be set locally. (Refer to  
“11. FIELD SETTING” on page 12)

(3) Use suspension bolts for installation. Check whether 

the ceiling is strong enough to support the weight of 
the unit or not. If there is a risk, reinforce the ceiling 
before installing the unit.

(Installation pitch is marked on the paper pattern for instal-
lation. Refer to it to check for points requiring reinforcing.)

Items to be checked

If not properly done, what is 
likely to occur

Check

Are the indoor and outdoor 
unit fixed firmly?

The units may drop, vibrate 
or make noise.

Is the gas leak test finished? 

It may result in insufficient 
cooling.

Is the unit fully insulated?

Condensate water may drip.

Dose drainage flow 
smoothly?

Condensate water may drip.

Dose the power supply volt-
age correspond to that 
shown on the name plate?

The unit may malfunction or 
the components burn out.

Are wiring and piping cor-
rect?

The unit may malfunction or 
the components burn out.

Is the unit safely grounded?

Dangerous at electric leak-
age.

Is wiring size according to 
specifications?

The unit may malfunction or 
the components burn out.

Is something blocking the air 
outlet or inlet of either the 
indoor or outdoor units?

It may result in insufficient 
cooling.

Are refrigerant piping length 
and additional refrigerant 
charge noted down?

The refrigerant charge in the 
system is not clear.

Items to be checked

Check

Did you explain about operations while showing the 
instruction manual to your customer?
Did you hand the instruction manual over to your cus-
tomer?

The items with  

  WARNING and  

  CAUTION marks 

in the instruction manual are the items pertaining to 
possibilities for bodily injury and material damage in 
addition to the general usage of the product. Accordingly, it 
is necessary that you make a full explanation about the 
described contents and also ask your customers to read the 
instruction manual.

*

30

*

30

300

2500 or higher

from the floor

For installation

in high places

Air inlet

Air outlet

Obstruction

Floor

Required service

space

(length : mm)

Fig. 1

01_EN_3P172532-7.fm  Page 3  Thursday, December 15, 2005  2:45 PM

Summary of Contents for FXHQ32MVE

Page 1: ...E INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFE...

Page 2: ...VE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXLQ50MHV1 FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MA...

Page 3: ...lation work may result in the equipment falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified...

Page 4: ...ubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vic...

Page 5: ...wever if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for installation Check whether the ceiling is strong...

Page 6: ...on to remove Refer to Fig 5 Pull out of the accessories 3 Remove the hanger bracket Loosen two hanger bracket setting bolts M8 two on each side on each side for less than 10 mm Refer to Fig 6 and 7 Re...

Page 7: ...might cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Execute heat insulation work completely on both sides of t...

Page 8: ...hen connecting or disconnecting pipes to from the unit Refer to Fig 16 Refer to Table1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare section both inside and outsi...

Page 9: ...hose included with the main body Refer to Table 1 for tightening torque Table 1 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit witho...

Page 10: ...converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work Add 0 6 liter of water in the drain pan from the...

Page 11: ...electric parts box lid Align the phase and connect the wire to the power terminal block 6P inside the electric parts box After connecting use the included clamps 4 to bind the wire together with the...

Page 12: ...smission wiring at least 50 mm away from power supply wiring The equipment may mal function if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF...

Page 13: ...o perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to...