background image

English

7

Use “ Table 2 ” as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque will sud-
denly increase. From that position, tighten the nut to the angle 
shown on “ Table 2 ”.

• Make absolutely sure to execute heat insulation works on the 

pipe-connecting section after checking gas leakage by thor-
oughly studying the following figure and using the attached 
heat insulating materials for fitting (6) and (7). (Fasten both 
ends with the clamps (4) (accessory).) 
 

(Refer to Fig. 18)

• Wrap the sealing pad (9) (accessory) only around the insula-

tion for the joints on the gas piping side. 

(Refer to Fig. 19)

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-

ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, use 
the phosphor copper brazing filler metal (BCuP-2: JIS Z 3264/
B-Cu93P-710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful infulence on refrigerant piping 
sysems. For instance, if the chlorine based flux is used, it will 
cause pipe corrosion or, in particular, if the flux contains fluo-
rine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 0.02 MPa with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping.

NOTE

NOTE

NOTE

NOTE

The flare nuts used must be those included with the main 

body.

• Refer to Table 1 for tightening torque.

Table 1

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to 
install the unit without a torque wrench, you may follow the 
installation method mentioned below.

After the work is finished, make sure to check that 
there is no gas leak.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque suddenly 
increases. From that position, further tighten the flare nut 
the angle shown below:

Table 2

7. DRAIN PIPING WORK

Rig the drain pipe as shown below and take measures against 
condensation. Improperly rigged piping could lead to leaks and 
eventually wet furniture and belongings.

(1)

Carry out the drain piping
• For drain work, rig the pipes so that they drain reliably.
• The drain pipe outlet direction can be chosen from the 

right rear, right, left rear, and left. Refer to “REFRIGER-
ANT PIPING WORK” for right rear and right direction, 
and refer to Fig. 20 for left rear and left direction. 

Insulation for gas pipe (6)

(accessory)

Insulation for

local piping

(Part to be procured

in the field)

(Up to the flare part)

Small sealing pad (9)

(accessory)

Wrap from the

bottom up

Insulation for

field piping

(Part to be

procured

in the field)

Flare nut

Flare nut

Gas piping

Liquid piping

Insulation for liquid pipe (7)

(accessory)

Clamp (4) (accessory) (× 4)

Attach to the bottom

(For both gas piping

and liquid piping)

Fig. 18

Fig. 19

Refrigerant

piping

Part to be 

brazed

Taping

Pressure-

reducing

valve

hands valve

Nitrogen

Nitrogen

Pipe 

size

Tightening torque

Flare 

dimensions

A (mm)

Flare

 φ

 6.4 

(1/4”)

14.2 – 17.2 N·m

8.7 – 9.1

 φ

 9.5 

(3/8”)

32.7 – 39.9 N·m

12.8 – 13.2

 φ

 12.7 

(1/4”)

49.5 – 60.3 N·m

16.2 – 16.6

 φ

 15.9

(5/8”)

61.8 – 75.4 N·m

19.3 – 19.7

Pipe size

Further tightening angle

Recommended arm 

length of tool

φ 

6.4 (1/4”)

60 to 90 degrees

Approx. 150mm

φ 

9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

φ 

12.7 (1/2”)

30 to 60 degrees

Approx. 250mm

φ 

15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

A

45

0

± 2

0

R0.4-0.8

90

0

± 2

0

 

Rear side (metal plate)

removable part

Left-facing drain piping

Left dressing board

removable part

Rear left-facing

drain piping

Fig. 20

01_EN_3P172532-7.fm  Page 7  Thursday, December 15, 2005  2:45 PM

Summary of Contents for FXHQ32MVE

Page 1: ...E INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFE...

Page 2: ...VE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXLQ50MHV1 FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MA...

Page 3: ...lation work may result in the equipment falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified...

Page 4: ...ubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoline is used Gas in the vic...

Page 5: ...wever if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for installation Check whether the ceiling is strong...

Page 6: ...on to remove Refer to Fig 5 Pull out of the accessories 3 Remove the hanger bracket Loosen two hanger bracket setting bolts M8 two on each side on each side for less than 10 mm Refer to Fig 6 and 7 Re...

Page 7: ...might cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Execute heat insulation work completely on both sides of t...

Page 8: ...hen connecting or disconnecting pipes to from the unit Refer to Fig 16 Refer to Table1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare section both inside and outsi...

Page 9: ...hose included with the main body Refer to Table 1 for tightening torque Table 1 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit witho...

Page 10: ...converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work Add 0 6 liter of water in the drain pan from the...

Page 11: ...electric parts box lid Align the phase and connect the wire to the power terminal block 6P inside the electric parts box After connecting use the included clamps 4 to bind the wire together with the...

Page 12: ...smission wiring at least 50 mm away from power supply wiring The equipment may mal function if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF...

Page 13: ...o perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...0602 HT 3P172532 7 EM02A086B 00_CV_3P172532 7 fm Page 2 Tuesday December 13 2005 12 58 PM...

Reviews: