Field Settings
SiUS042113E
156
Part 7 Trial Operation and Field Settings
Overview of the Settings
* 09/12 class: N/A
Setting items
Setting options
Factory
setting
Contents
1
Brightness
0: OFF
1: Dark
2: Bright
N/A
Brightness of indoor unit LED lamp
2
Filter cleaning setting
0: Short
1: Long
N/A
Determines the duration/time to display Filter cleaning sign.
3
Suspend
0: OFF
1: ON
1
Activation/Deactivation of Standby electricity saving (suspend
function)
0:
Power will still be supplied to the outdoor unit PCB after the unit
operation stopped.
1:
Three minutes after the unit operation stops, the power supply to
the outdoor unit PCB is shut off.
4
Dry keep
0: OFF
1: ON
0
Stops the airflow of indoor unit when the thermostat is OFF to
prevent increase of room humidity.
0:
When thermostat is OFF, the fan rotor will still be OPERATING,
hence there is airflow.
1:
When thermostat is OFF, the fan rotor will be STOPPED, hence
there is no airflow.
5
Preheating control
0: OFF
1: ON
0*
Activation/Deactivation of compressor preheating
0:
Deactivation of compressor preheating
1:
Activation of compressor preheating
6
Room temperature
adjustment (cooling)
0: Low 2 (–2°C)
1: Low 1 (–1°C)
2: Standard (0°C)
3: High 1 (+1°C)
4: High 2 (+2°C)
2
Adjustment of indoor temperature thermistor in cooling operation
Used for adjustment of room temperature control.
7
Room temperature
adjustment (heating)
0: Low 2 (–2°C)
1: Low 1 (–1°C)
2: Standard (0°C)
3: High 1 (+1°C)
4: High 2 (+2°C)
2
Adjustment of indoor temperature thermistor in heating operation.
Used for adjustment of room temperature control.
8
Airflow setting when
thermostat off during
cooling operation
0: Keep
1: Soft breeze
N/A
Airflow setting when indoor unit thermostat is off.
0:
Same airflow as "thermostat on"
1:
Lowered to LL tap
9
Wireless/HA priority setting
during automatic operation
0: Wireless
1: HA
N/A
Determination of priority control method when HA system is used.
0:
Wireless remote controller can be used.
1:
Temperature setting from wireless remote controller is disabled.
10
Auto-restart
0: OFF
1: ON
1
This setting decides the operation of the unit when the power supply
resumed after a power supply shutdown (i.e. power failure).
0:
When the power supply resumes, the unit remains in stopped
operation.
1:
When the power supply resumes, the unit resumes the operation
before the shutdown of power supply.
12 Warmer airflow setting
0: OFF
1: ON
0
This setting makes the discharge airflow temperature warmer.
1
Field settings mode
Room temperature adjustment settings may be applied.
When changing the settings, make sure the button was correctly pressed by listening for
the beep sound. (The beep can be heard even if the button is pressed within a setting
which is unavailable. In this case, the setting will be invalid.)
Press the
buttons to change the setting items and the setting values.
•
Confirm/Send
Setting items
Setting values
(R24995)
Summary of Contents for FTXM-V Series
Page 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Page 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Page 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Page 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Page 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...