Control Specification
Part 4 Functions and Control
75
3.13.8 Target Discharge Pipe Temperature Control
The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger
temperature, and the electronic expansion valve opening is adjusted so that the actual discharge
pipe temperature becomes close to the target discharge pipe temperature. (Indirect SH
(superheating) control using the discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every 20 seconds. The opening degree of the electronic expansion valve is adjusted by the
following.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
3.14 Malfunctions
3.14.1 Sensor Malfunction Detection
Sensor malfunction can be detected in the following thermistor:
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
3.14.2 Detection of Overcurrent and Overload
Outline
In order to protect the inverter, an excessive output current is detected and the OL temperature is
observed to protect the compressor.
Details
If the inverter current exceeds
A
A, the system shuts down the compressor.
If the OL (Compressor head) temperature exceeds
B
°C (°F), the compressor stops.
SC
(S
u
bcooling)
SH
(S
u
perheating)
The target discharge pipe
temperat
u
re is set as to become
the target SH.
The inclination does not change
depending on the operating condition.
(R23014)
09/12 class
18 class
24 class
Cooling
Heating
Cooling
Heating
Cooling
Heating
A
(A)
13.0
13.0
20
20
20
20
B
(°C)
125
125
125
125
125
125
(°F)
257
257
257
257
257
257
Summary of Contents for FTXM-V Series
Page 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Page 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Page 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Page 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Page 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...