Troubleshooting
SiUS042113E
98
Part 6 Service Diagnosis
Reference
Troubleshooting
Check No.01
(R24716)
Caution
YES
NG
NO
NO
YES
YES
YES
NO
YES
NO
NO
YES
NO
∗
Discharge pipe thermistor
∗
Indoor or outdoor heat exchanger thermistor
∗
Room temperature thermistor
∗
Outdoor temperature thermistor
Check for refrigerant shortage.
Change for a specified amount of
fresh refrigerant.
Reconnect the thermistor(s).
Open the stop valve.
Repair the pipe flare or
replace the union.
Check if any harnesses are
in contact with the piping
and correct as required.
Also, replace any cracked
pipes.
Check the connection of the
power transistor harness.
Also, replace any cracked
pipes.
Replace the defective
thermistor(s).
Completed.
Refrigerant shortage error
again?
Oil leak at internal
piping?
Stop valve closed?
Compressor vibrating
too much?
Oil leak at relay pipe
connections?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
OK
NO
YES
Replace the outdoor unit PCB
(main PCB).
Replace the compressor.
Completed.
Error again?
Summary of Contents for FTXM-V Series
Page 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Page 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Page 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Page 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Page 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...