SiUS042113E
Troubleshooting
Part 6 Service Diagnosis
125
Reference
Reference
Troubleshooting
Check No.15
Check No.21
(R23155)
Caution
YES
2 sec
Time
NO
YES
YES
NO
NO
NO
YES
YES
NO
Current
(guideline)
Turn off the power. Then, turn on
the power to restart the system.
Start operation.
Check No. 21
Check the capacitor voltage.
Measure the rectifier input voltage.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn off the power and reconnect
the harnesses. Then turn on the
power again and restart operation.
Check No.15
Check with the inverter analyzer.
Inverter analyzer:
RSUK0917C
Voltage
within the allowable
range (Power supply
voltage ± 15%)?
Replace the outdoor unit
PCB (main PCB).
Check the power supply
voltage.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Capacitor charged when
the indoor unit or outdoor
unit main relay turns on
Rising with increasing
frequency
Correct the power supply or
replace the outdoor unit PCB
(main PCB).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Running current
as shown at right
with relay cable 1
or 2?
Within 320 VDC?
Any LED off?
Compressor running?
+ 100
- 50
Summary of Contents for FTXM-V Series
Page 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Page 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Page 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Page 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Page 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...