Check
SiUS042113E
140
Part 6 Service Diagnosis
2. On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
5.8 Rotation Pulse Check on the Outdoor Unit PCB
Check No.16
Outdoor fan motor
09/12 class
Check if the sinusoidal voltage is generated between pins 1 - 3 and 3 - 5 when the fan motor is
manually rotated once.
18/24 class
Make sure that the voltage of 320 ± 30 V is applied.
1. Set operation OFF and power OFF. Disconnect the connector S70.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 3 - 4 is 15 VDC.
4. Check that the rotation command voltage between the pins 2 - 4 is 0 ~ 6.5 VDC.
5. Keep operation OFF and power OFF. Connect the connector S70.
6. Check whether 4 pulses (0 ~ 15 VDC) are output at the pins 1 - 4 when the fan motor is rotated
1 turn by hand.
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2
Defective PCB
Replace the outdoor unit PCB (main PCB).
If NG in step 4
Defective Hall IC
Replace the outdoor fan motor.
If OK in both steps 2 and 4
Replace the outdoor unit PCB (main PCB).
(R15292)
Direction of crimp
FASTON terminal
This size is shortened
by the crimp.
5
3
1
Phase U
Phase V
Phase W
S70
PCB
Summary of Contents for FTXM-V Series
Page 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Page 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Page 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Page 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Page 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...