Components
Service manual
136
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
d
d
c
c
a
b
c
d
c
d
A
A
RXA42~50A unit
a
L803
b
L804
c
Measuring point
d
Measuring point
d
d
c
c
a
b
c
d
c
d
A
A
RXA42~50B unit
a
L803
b
L804
c
Measuring point
d
Measuring point
Is the inductance measurement
correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next step.
No
Replace the reactor, see
2.15.2 Repair procedures
As the reactors are part of the main PCB, replace the complete main PCB. See