1.5.18 F8-00 – System shutdown due to compressor internal temperature abnormality
Trigger
Effect
Reset
Temperature discharge
pipe thermistor exceeds
the determined limit.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
3
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
4
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
5
Perform
a
check
of
the
discharge
pipe
thermistor.
See
Possible cause:
Faulty discharge pipe thermistor or connector fault.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.19 H0-00 – Outdoor unit: Voltage/current sensor problem
Trigger
Effect
Reset
Compressor voltage (DC)
is out of range before
start‑up.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
2
Check if the power supply is conform with the regulations. See