![background image](http://html1.mh-extra.com/html/daikin/ftxa20a/ftxa20a_service-manual_2459411073.webp)
2
|
Components
Service manual
73
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
2.7 Indoor unit fan motor
2.7.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the DC fan motor assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Check the fan for damage, deformations and cracks. Replace the fan as
needed.
2
Check that the fan is correctly installed on the DC fan motor. Correct as
needed.
3
Manually rotate the fan and check the friction of the DC fan motor shaft
bearing.
Is the DC fan motor shaft friction
normal?
Action
Yes
Perform an electrical check of the DC
fan motor assembly, see
No
Replace the DC fan motor assembly, see
To perform an electrical check of the DC fan motor assembly
Prerequisite:
First perform a mechanical check of the DC fan motor assembly, see
1
Remove the cover from the switch box; see
2
Disconnect the DC fan motor connector from the appropriate PCB.
3
Measure the resistance between the pins 1-2, 1-3, and 2-3 of the DC fan
motor connector.
Result:
All measurements MUST be 15~20 Ω.
DC fan motor measurements are
correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the DC fan motor, see
2.7.2 Repair procedures
To remove the DC fan motor assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.