Nut
b
Compressor
c
Damper
INFORMATION
The compressor dampers may look different.
7
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
8
Wrap a wet rag around the compressor pipes and any other components near
the compressor and solder the compressor pipes to the refrigerant pipes.
a
a
a
Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
9
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
10
Connect the Faston connectors to the compressor wire terminals U, V and W