![background image](http://html1.mh-extra.com/html/daikin/ftv-a-series/ftv-a-series_engineering-data_2459385046.webp)
44
Capacity Tables
(b) Indoor Condition:
25°C DB, 19°C WB
Outdoor Condition:
35°C DB
EWB
EDB
Outdoor temperature
35°C
TC
SC
PI
19
24
1.99
1.32
0.64
25
x
2
y
2
z
2
27
1.99
1.53
0.64
By Interpolation Method
⇒
25°C – 24°C
=
x
2
– 1.99kW
27°C – 24°C
1.99kW – 1.99kW
⇒
x
2
= 1.99kW
Similarly
,
y
2
= 1.39kW
z
2
= 0.64kW
Repeat the same process for (c) & (d) in 1
st
Step
(c) x
3
= 1.69 kW; y
3
= 1.63 kW; z
3
= 0.68 kW
(d) x
4
= 1.83 W; y
4
= 1.30 kW; z
4
= 0.69 kW
2
nd
Step:
To obtain the TC, SC & PI for
(a) Indoor Condition:
25°C DB, 17°C WB
Outdoor Condition:
35°C DB
EWB
EDB
Outdoor temperature
35°C
TC
SC
PI
16
25
1.81
1.75
0.63
17
x
5
y
5
z
5
19
1.99
1.39
0.64
By Interpolation Method
⇒
17°C – 16°C
=
x
5
– 1.81kW
19°C – 16°C
1.99kW – 1.81kW
⇒
x
5
= 1.87kW
Similarly
,
y
5
= 1.63kW
z
5
=0.63kW
Repeat the same process for (b) in 2
nd
Step
(c) x
6
= 1.74 kW; y
6
= 1.52 kW; z
6
= 0.68 kW
3
rd
Step:
To obtain the TC, SC & PI for
(a) Indoor Condition:
25°C DB, 17°C WB
Outdoor Condition:
37°C DB
EWB
EDB
Outdoor temperature
35°C
37°C
40°C
TC
SC
PI
TC
SC
PI
TC
SC
PI
25
17
1.87
1.63
0.63
x
y
z
1.74
1.52
0.68
By Interpolation Method
⇒
37°C – 35°C
=
x – 1.87kW
40°C – 35°C
1.74kW – 1.87kW
⇒
x = 1.82kW
Similarly
,
y = 1.59kW
z = 0.65kW
Summary of Contents for FTV-A Series
Page 1: ...TM FTV 1020 F Split Unit Air Conditioner Wall Mounted FTV A P PS Series Cooling Only 50Hz...
Page 2: ......
Page 30: ...28 Dimensions Model FTV85PS Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Page 33: ...31 Dimensions Model RC85A Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Page 35: ...33 Wiring Diagram Model RV35A Model RV50 60A R08024149386 3P548018 1...
Page 37: ...35 Wiring Diagram Model FTV50 60P Outdoor Unit Model RV50 60C R08024149860A R08024145839...
Page 56: ...54 Capacity Tables FTV28P RV28F FTV35P RV35F...
Page 68: ...66 Sound Level FTV85PS...