Electric Characteristic
67
Electric Characteristic
Unit Combination
Power Supply
COMP
OFM
IFM
Indoor Unit Outdoor Unit
Hz
Volts
Voltage Range
MCA
MFA LRA
RLA
kW
FLA
kW
FLA
FTV28A
RV28A
50
220
Max. 50Hz 264V
Min. 50Hz 198V
4.70
16.0
16.0
3.34 0.050 0.22 0.037 0.20
50
230
50
240
FTV35A
RV35A
50
220
Max. 50Hz 264V
Min. 50Hz 198V
5.96
16.0
30.1
4.34 0.051 0.23 0.042 0.20
50
230
50
240
FTV50A
RV50A
50
220
Max. 50Hz 264V
Min. 50Hz 198V
9.19
20.0
38.0
6.74 0.092 0.41 0.044 0.20
50
230
50
240
FTV60A
RV60A
50
220
Max. 50Hz 264V
Min. 50Hz 198V
12.4
20.0
52.0
9.11
0.092 0.41 0.077 0.36
50
230
50
240
Symbols:
MCA
: Min. circuit amps (A)
MFA
: Max. fuse amps (A)
LRA
: Locked Rotor Ampere (A)
RLA
: Rated loads amps (A)
OFM
: Outdoor fan motor
IFM
: Indoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
Notes:
1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB.
Outdoor temp. 35°CDB.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
detector capable of handling high harmonics must be used in
order to prevent malfuctioning of the earth leak detector.)
Summary of Contents for FTV-A Series
Page 1: ...TM FTV 1020 F Split Unit Air Conditioner Wall Mounted FTV A P PS Series Cooling Only 50Hz...
Page 2: ......
Page 30: ...28 Dimensions Model FTV85PS Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Page 33: ...31 Dimensions Model RC85A Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Page 35: ...33 Wiring Diagram Model RV35A Model RV50 60A R08024149386 3P548018 1...
Page 37: ...35 Wiring Diagram Model FTV50 60P Outdoor Unit Model RV50 60C R08024149860A R08024145839...
Page 56: ...54 Capacity Tables FTV28P RV28F FTV35P RV35F...
Page 68: ...66 Sound Level FTV85PS...