Installation Guideline
• When flared joints are reused indoors,the flare part shall be re-fabricated.
• Avoid installation of the air conditioner in a place where there is danger of exposure to continuously operating
open flames (for example an operating electric heaters).
• Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid
certificate from an industry-accredited assessment authority, which authorises their competence to handle
refrigerants safely in accordance with an industry recognised assessment specification.
• Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being
used is suitable for use with flammable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.
• Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to
the charging area.
• No ignition sources
All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of
installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released
to the surrounding space. “No Smoking” signs shall be displayed.
• The following checks shall be applied to installations:
– marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be
corrected;
– refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing components, unless the components are constructed
of materials which are inherently resistant to being corroded or are suitably protected against being so
corroded.
• Initial safety checks shall include:
– that capacitors are discharged, this shall be done in a safe manner to avoid possibility of sparking
– there shall be no live electrical components and wiring are exposed while charging, recovering or purgin
the system;
• Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not
exceed the permissible voltage and current permitted for the equipment in use.
Replace components only with parts specified by the manufacturer.
• Leak detection methods
Ensure that the detector is not a potential source of ignition (for example a halide torch) and is suitable for
the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant (for
R32, LFL is 13%) and shall be calibrated to the refrigerant employed and the appropriate percentage of gas
(25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine
shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak
is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which
requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged
through the system both before and during the brazing process.
WARNING
Prior to installation, ensure risk of ignition is minimised and avoid working in confined space.
Ensure adequate ventilation is available by opening windows or doors.
Summary of Contents for FTV-A Series
Page 1: ...TM FTV 1020 F Split Unit Air Conditioner Wall Mounted FTV A P PS Series Cooling Only 50Hz...
Page 2: ......
Page 30: ...28 Dimensions Model FTV85PS Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Page 33: ...31 Dimensions Model RC85A Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Page 35: ...33 Wiring Diagram Model RV35A Model RV50 60A R08024149386 3P548018 1...
Page 37: ...35 Wiring Diagram Model FTV50 60P Outdoor Unit Model RV50 60C R08024149860A R08024145839...
Page 56: ...54 Capacity Tables FTV28P RV28F FTV35P RV35F...
Page 68: ...66 Sound Level FTV85PS...