15
Installation Guideline
• Connect the drain hose, as described below.
The drain hose should
be inclined downward.
No trap is permitted.
Do not put the end
of the hose in water.
• Water Drainage
End
dipped
into
water
Water
leaking
Water
leaking
Water
leaking
Wrong
Wrong
Wrong
Drain
Water
retention
Correct
• Remove the air filters and pour some water into
the drain pan to check the water flows smoothly.
• When drain hose requires extension, obtain
an extension hose commercially available.
Be sure to thermally insulate the indoor section
of the extension hose.
φ16
Extension drain hose
Indoor unit
drain hose
Heat insulation tube (Field supply)
• When connecting a rigid polyvinyl chloride pipe
(inner diameter 16mm) directly to the drain hose
attached to the indoor unit as with embedded
piping work, use any commercially available drain
socket (inner diameter 16mm) as a joint.
φ16
Drain hose supplied
with the indoor unit
socket (inner
diameter 16mm)
polyvinyl pipe
(diameter 16mm)
4. Drain Piping
Summary of Contents for FTV-A Series
Page 1: ...TM FTV 1020 F Split Unit Air Conditioner Wall Mounted FTV A P PS Series Cooling Only 50Hz...
Page 2: ......
Page 30: ...28 Dimensions Model FTV85PS Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Page 33: ...31 Dimensions Model RC85A Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Page 35: ...33 Wiring Diagram Model RV35A Model RV50 60A R08024149386 3P548018 1...
Page 37: ...35 Wiring Diagram Model FTV50 60P Outdoor Unit Model RV50 60C R08024149860A R08024145839...
Page 56: ...54 Capacity Tables FTV28P RV28F FTV35P RV35F...
Page 68: ...66 Sound Level FTV85PS...