EDUS281008
Installation of indoor unit
Installation of indoor / outdoor unit
29
2
3P250363-3B
5
English
Table 1
A
B
C
D
E
F
G
H
I
53-1/4
24
20
22
12
14-1/2
11-
15/16
19-5/8
19-
15/16
Make sure the range of the unit’s external static pres-
(2)
sure is not exceeded. (up to 0.5 in.W.C. at “H” speed.)
Condensation may form on the product during COOL
(3)
operation. Be sure to provide (fi eld supplied) and
install a second drain pan.
If
i
n
s
talled
v
ert
ic
ally
If
i
n
s
talled hor
i
zontally
Second drain pan
Second drain pan
Drain piping
Drain piping
Check if the unit is horizontally level.
(4)
CAUTION
Make sure the unit is installed level using a level tube
:
four
•
sides. (One thing to watch out for in particular is if the unit is
installed so that the slope is not in the direction of the drain
piping, this might cause leaking.)
L
e
v
e
l
L
e
v
e
l
If installed vertically
If installed horizontally
Secure the unit fi rmly to prevent it from falling.
(5)
When the unit is installed in a hot and humid place, it
(6)
is recommended to use the following drain pan insu-
lation kit, which is an optional accessory.
Drain pan insulation Kit
Vertically
Horizontally
DPI 48-60/20
DPIH 48-61
Regarding the attachment of the drain pan insulation kit,
•
refer to the installation manual provided with the kit.
Summary of Contents for FTQ-PA
Page 1: ...EDUS281008 Split System Air Conditioners Air Handling Unit FTQ PA RZQ P9 ...
Page 12: ...EDUS281008 Dimensions and service space FTQ PA RZQ P 9 1 3D06421 ...
Page 15: ...Piping diagrams EDUS281008 12 FTQ PA RZQ P 5 2 Outdoor unit RZQ18PVJU9 RZQ24PVJU9 3D062238B ...
Page 20: ...EDUS281008 Electrical characteristics FTQ PA RZQ P 17 1 7 2 Electric heater ...