EDUS281008
Installation of indoor unit
Installation of indoor / outdoor unit
37
2
3P250363-3B
13
English
REMOTE CONTROL SETTING
10-2
Force
d
off an
d
ON/OFF operation shoul
d
b
e selecte
d
b
y select-
•
ing the
S
ECOND CODE NO. as shown in the ta
b
le Ta
b
le 4.
Table 4
External ON/OFF input
Mo
d
e No.
FI
RS
T
CODE NO.
S
ECOND
CODE NO.
Force
d
off
12 (22)
1
01*
ON/OFF operation
02
* factory set
Input
A
of force
d
off an
d
ON/OFF operation work as shown
•
in Ta
b
le 5.
Table 5
Force
d
off
ON/OFF operation
Input
A
“on” to force a stop
(remote controller reception
prohi
b
ite
d
)
Unit operate
d
b
y changing input
A
from “off” to “on”
Input
A
“off” to allow remote
controller
Unit stoppe
d
b
y changing input
A
from “on” to “off”
SETTING THE FILTER SIGN DISPLAY INTERVAL
10-3
Explain the following to the customer if the fi lter
d
irt settings
•
have
b
een change
d
.
The fi lter sign
d
isplay time is set to 2500 hours (equivalent
•
to 1 year’s use) when shippe
d
.
The settings can
b
e change
d
to not
d
isplay.
•
When installing the unit in a
d
usty place, set the fi lter sign
•
d
isplay time to shorter intervals (1,250 hours).
Explain it to the customer that the fi lter nee
d
s to
b
e cleane
d
•
regularly to prevent clogging an
d
also the time that is set.
Mo
d
e No.
FI
RS
T CODE NO.
S
ECOND
CODE NO.
01
02
10 (20)
0
Filter
d
irt
low
high
1 (low/high)
Displaye
d
time
(units: hours)
2500/
1250
10000/
5000
3
Filter sign
d
isplay
ON
OFF
INSTALLATION OF THE OPTIONAL AIR FILTER
10-4
Purchase an
d
install the air fi lter as in Ta
b
le 6 .
•
Table 6
A
ir fi lter
18 · 24 type
FIL 48-61
Take off the part on the bottom of the front panel.
(1)
Insert the air fi lter as far as it can go.
(2)
Air filter (optional accessories)
INSTALLATION OF THE ELECTRIC HEATER KIT
10-5
WARNING
A
ll phases of the electrical installation must comply with
•
national, state, provincial, an
d
local co
d
es.
When connecting an electric heater,
b
e sure to install an
•
earth leakage circuit
b
reaker procure
d
locally.
If an earth leakage circuit
b
reaker is not installe
d
, electric
•
shock or fi re may result.
R
egar
d
ing the rate
d
current of the earth leakage circuit
•
b
reaker to
b
e installe
d
, refer to the H.M.C.
A
. value in
d
icate
d
on the manufacturer’s la
b
el or in a technical
d
ocument.
The recommen
d
e
d
rapi
d
sensitive current an
d
tripping time
•
are in
d
icate
d
b
elow.
Recommended specifi cations of circuit breaker
R
api
d
sensitive current
30m
A
Tripping time
0.1sec
Summary of Contents for FTQ-PA
Page 1: ...EDUS281008 Split System Air Conditioners Air Handling Unit FTQ PA RZQ P9 ...
Page 12: ...EDUS281008 Dimensions and service space FTQ PA RZQ P 9 1 3D06421 ...
Page 15: ...Piping diagrams EDUS281008 12 FTQ PA RZQ P 5 2 Outdoor unit RZQ18PVJU9 RZQ24PVJU9 3D062238B ...
Page 20: ...EDUS281008 Electrical characteristics FTQ PA RZQ P 17 1 7 2 Electric heater ...